Heat Controller VMH18SC-1, VMH12SC-1, VMH24SC-1, VMH09SC-1 Frequency decreases Holds, Model Current

Page 23

Heat Controller, Inc.

VMH Series

Service Manual

 

 

 

Note:

When T1-Ts stays in the same temp. zone for 3 minutes, the compressor will run as follows: A~E: Increases the frequency to level F8.

F:Maintains the current frequency.

G:Decreases the frequency to the lower level F1.

H:Runs at F1 for 1h.(if T1-Ts<28°F/-2°C, compressor will stop) Meanwhile, the compressor running frequency is limited by the current.

Frequency decreases

Frequency

holds

If the current increases more than I2COOL, the frequency will decrease automatically, if the current raises to over I3COOL, the compressor will stop and restart 3min later.

When the frequency decreases and the current deceases to between I1COOL and I2COOL, the frequency will hold. If the frequency does not change for 3min, the frequency will increase to a higher level, and it can increase twice at most.

If the current deceases to lower than I1COOL, the frequency limit will be invalid.

Model

 

Current

 

I1COOL

I2COOL

I3COOL

 

VMH09SC-1

5.2

6.4

7.5

VMH12SC-1

5.2

6.4

7.5

VMH18SC-1

5.2

6.4

7.5

VMH24SC-1

10

11

13

23

Image 23
Contents Inverter Single Zone Ductless Mini Split Heat Pump Contents  Installation PrecautionSafety Precaution  For installation, always contact the dealer  Caution  Do not block the inlet or outlet of air flow  Keep level even when installing the product Operational  Use two or more people to lift and transport the product Do not drink the water drained from the product Anti-freeze protection in cooling FunctionOutdoor unit Compressor delay Indoor Unit DimensionOutdoor Unit Model Dimension mmIndoor Outdoor Refrigerant Cycle DiagramWiring Diagrams VMH09SC-1 A-VMH12SC-1 VMH18SC-1 Installation details Single Zone V Series Inverter System Pipe length and the elevationSystem Evacuation and Charging Pressure Test & EvacuationOperation characteristics Display function Electronic functionAbbreviation Main Protection Preheat termination Preheat modeFan only mode Operation Modes and FunctionsCooling Mode Compressor running rules Model Current Frequency decreases HoldsIndoor fan running rules Condenser high temperature T3 protectionOutdoor fan rules Heating Mode Compressor running rules Evaporator low temperature T2 protectionT1-Ts-ΔT +5.0 +4.5 +3.5 +3.0 +2.5 +2.0 +1.5 +1.0 +0.5 Outdoor fan running rules I1HEAT I2HEAT I3HEATVMH18SC-1 Indoor fan rulesUnit TEL0 TEL1 VMH09SC-1 VMH12SC-1Defrost mode: Defrost Actions For 9K and 12K unit For 18K and 24K unit Auto-mode High evaporator coil temp.T2 protectionForced operation function Dehumidify modeSleep function mode Timer functionAutomatic front panel function Ionizer Clean Air functionAuto-Restart function Safety TroubleshootingEeprom parameter error diagnosis and solution Indoor Unit Error DisplayDiagnosis and Solution VMH Series E3 Indoor or E7 Outdoor Igbt over current protection diagnosis and solution VMH Series Inverter compressor drive error diagnosis and solution 29 P3 Error Low Ambient ProtectionPosition Resistance Value Key parts checkingVMH Series Some frequently-used R-T data for T1, T2, T3 and T4 sensor 2012