Heat Controller, Inc. | VMH Series | Service Manual |
|
|
|
Auto fan action in heating mode.
| |
°F | °C |
5° | (2.5) |
4° | (2.0) |
3° | (1.5) |
2° | (1.0) |
|
|
8.4.3.4 Defrost mode:
Conditions of defrost:
When the unit is running, if any one of the following conditions is satisfied, the unit starts defrost:
1 .Defrost is available after 40 minutes of run time if T3 (Condenser coil temperature) is<37°F/3°C and there is a 11°F/6°C temperature difference for 3 minutes.
2.Defrost is available after 80 minutes of run time if T3 (Condenser coil temperature) is<37°F/3°C and there is a 7°F/4°C temperature difference for 3 minutes.
3.Defrost is available after 120 minutes of run time if T3 Condenser coil temperature) is<37°F/3°C and there is a 4°F/2°C temperature difference for 3 minutes.
4.If any of the above conditions are satisfied and the T2 (Evaporator coil temperature) has decreased 9°F/5°F below the normal maximum indoor pipe temperature, unit starts defrost.
Note: T2 is the maximum value of the evaporator temperature during the
Terminating defrost:
If any one of following items is satisfied, defrost will stop and unit will return to normal heating mode. 1 .Defrost time has reached 10 minutes
2 .T3 (Condenser coil temperature) >46°F/8°C for 80 seconds.
29