Installation of Indoor, Outdoor Unit
Piping lengthand elevation
Multi Piping Type
| Max total length | Max length of |
| Min length of |
| Max Elevation |
| Max elevation | |||||
|
|
| between each |
| |||||||||
Capacity(Btu/h) | of all pipes | each pipe |
|
| each pipe |
|
| between indoor | |||||
|
|
| indoor unit and | ||||||||||
| (A+B/A+B+C) | (A/B/C) |
|
| (A/B/C) |
| outdoor unit (h1) | units (h2) | |||||
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
24k | 30m(100ft) | 15m(50ft) |
|
| 3m(10ft) |
| 7.5m(25ft) |
| 7.5m(25ft) | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
36k | 45m(150ft) | 15m(50ft) |
|
| 3m(10ft) |
| 7.5m(25ft) |
| 7.5m(25ft) | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Indoor Capacity |
|
|
|
|
| Pipe Size |
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| Additional | ||
(Btu/h) |
| Gas |
| Liquid |
| Standard Length |
|
| |||||
|
|
|
|
| Refrigerant | ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| |||
12k |
| 3/8" |
| 1/4" |
|
|
| 7.5m(25ft) |
| 20g/m(0.32oz/ft) | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
24k | 36k |
A | A |
B
h2
B
h2
h2
h1
h1
C
h1
h1
h1
B
CAUTION: Capacity is based on standard length and maximum allowance length is on the basis of reliability. Oil trap should be installed every 5~7 meters (16.4~23.0ft).
10Room Air Conditioner