Connecting the Cable between Indoor Unit and Outdoor Unit

Connecting the Cable between Indoor Unit and Outdoor Unit

Connectthecable totheIndoor unit.

Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the terminal No. are the same as those of the indoor unit.)

The earth wire should be longer than the common wires. The circuit diagram is not subject to change without notice.

When installing, refer to the electrical diagram behind the front panel of Indoor Unit.

The wiring for the outdoor unit can be found on the inside of the Outdoor Unit control cover.

WARNING:

The circuit diagram is not subject to change without notice.

Be sure to connect wires according to the wiring diagram.

Connect the wires firmly, so that not to be pulled out easily.

Connect the wires according to color codes by referring to the wiring diagram.

WARNING: Provide a circuit breaker between power source and the outdoor unit as shown below.

Main power source

 

Air

Circuit Breaker

Conditioner

Use a circuit breaker

 

or time delay fuse.

WARNING! : The power wire to the outdoor unit must be of sufficient gauge to meet the Minimum Circuit Ampacity (MCA) as indicated on the outdoor unit rating plate and be of type required by NEC and local codes.

24k

 

 

 

 

36k

 

 

 

 

Line voltage (208~230V)

 

 

 

 

Line voltage (208~230V)

 

 

 

 

G

N

/Y

 

 

G

N

/Y

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L

 

 

 

 

L

 

 

 

 

2

 

 

 

 

2

 

 

 

 

0

 

 

 

0

 

 

 

 

m

m

 

 

 

m

m

The connecting cable between the indoor and outdoor unit should be SJOW type, minimum 18 gauge, and meet requirements of NEC and local codes.

Low voltage (below 40V)

AWG18

GN/YL

2

 

 

0

 

 

m

 

 

m

WARNING! Secure the interconnecting on both ends by using the clamps provided.

Installation Manual 19

Image 19
Contents DMC24DB-1, DMH24DB-1 DMC36TB-1, DMH36TB-1 Table of Contents 24k Installation Parts Provided36k Be sure not to do Be sure to follow the instruction Safety PrecautionsThere is risk of fire, electric shock, explosion or injury Oxygen deficiency could occur Could cause personal injury Personal injuryMoisture may condense and wet or damage furnishings There is risk of fire or product failureThere could result in personal injury and product damage There is risk of fire or electrical shockThere is risk of electric shock There is risk of electrical shockThere is risk of damage or loss of property It may cause a problem for your neighborsAvoid personal injury This could damage your healthBe careful and avoid personal injury It is not sanitary and could cause serious health issuesThere is risk of personal injury There is risk of personal injury and failure of productIndoor unit Installation of Indoor, Outdoor UnitRooftop Installations Select the best locationMulti Piping Type Piping length and elevation24k 36k Drill a hole in the wall Fixing Installation PlatePutting nut on Flaring workCut the pipes and the cable Burrs removalFoamed polyethylene or equivalent is recommended Connecting the PipingCheck IndoorFlare nut Pipes Indoor unit installationOutside diameter Torque Kg .mlbf .ftOpen-end wrench fixed Flare nut Wrench Indoor unit SpacerIndoor unit tubing Piping hole Piping forBad case Good caseOutside diameter Torque OutdoorConnect the cable to the Indoor unit Connect the cable to the Outdoor unit Power supplyWith the screw How to connect wiring to the terminals Circuit Breaker MOC rating on the unit rating plate Pour a glass of water on the evaporator Checking the drainageTo check the drainage Drain pipingSeal a small Opening around Pipings with Forming the pipingGum type sealer Checking method Air Purging and EvacuationEvacuation Repeat evacuation procedure for each indoor unitFinishing the job Max total ChargingAdditional Test Running Prepare remote controlEvaluation of the performance Heat CONTROLLER, INC