Heat Controller DMH36TB-1, DMC24DB-1 manual Air Purging and Evacuation, Checking method

Page 25

Air Purging and Evacuation

Air Purging and Evacuation

Air and moisture remaining in the refrigerant system have undesirable effects as indicated below.

1.Pressure in the system rises.

2.Operating current rises.

3.Cooling(or heating) efficiency drops.

4.Moisture in the refrigerant circuit may freeze and block capillary tubing.

5.Water may lead to corrosion of parts in the refrigeration system.

Therefore, the indoor/outdoor unit and connecting tube must be checked for leak tight, and vacuumed to remove incondensible gas and moisture in the system.

Checkingmethod

Preparation

Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed. Remove the service valve caps from both the gas and the liquid side on the outdoor unit. Check that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage.

Leakage test

1.Do a leakage test of all joints of the tubing(both indoor and outdoor) and both gas and liquid side service valves.

Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth.

2.After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder.

• Connect the manifold valve(with pressure gauges)

 

 

 

 

and dry nitrogen gas cylinder to this service port

 

 

 

 

with charge hoses.

 

 

Indoor unit

 

CAUTION: Be sure to use a

 

 

 

 

 

 

 

manifold valve for leak testing.

 

 

 

 

The high side manifold valve must

Outdoor unit

 

 

always be kept closed.

 

 

 

 

 

 

• Pressurize the system to no more than 150

 

 

 

 

P.S.I.G. with dry nitrogen gas and close the

 

 

 

 

cylinder valve when the gauge reading

 

 

 

 

reached 150 P.S.I.G. Next, test for leaks with

 

 

 

 

liquid soap.

Manifold valve

 

CAUTION: To avoid nitrogen

Pressure

Lo

Hi

 

entering the refrigerant system in a

gauge

 

 

 

 

 

 

 

liquid state, the top of the cylinder must be

 

 

Charge hose

 

higher than its bottom when you pressurize

 

 

 

 

 

 

 

the system. Usually, the cylinder is used in

 

 

 

 

a vertical standing position.

 

 

Nitrogen gas

 

 

 

 

 

 

 

 

cylinder(in vertical

 

NOTICE : Leakage test shoud be done for

 

 

standing position)

 

 

 

 

 

each indoor unit connection set, separately.

 

 

 

 

 

 

 

Installation Manual

25

Image 25
Contents DMC24DB-1, DMH24DB-1 DMC36TB-1, DMH36TB-1 Table of Contents 24k Installation Parts Provided36k Be sure not to do Be sure to follow the instruction Safety PrecautionsThere is risk of fire, electric shock, explosion or injury Moisture may condense and wet or damage furnishings Could cause personal injury Personal injuryThere is risk of fire or product failure Oxygen deficiency could occurThere is risk of electric shock There is risk of fire or electrical shockThere is risk of electrical shock There could result in personal injury and product damageAvoid personal injury It may cause a problem for your neighborsThis could damage your health There is risk of damage or loss of propertyThere is risk of personal injury It is not sanitary and could cause serious health issuesThere is risk of personal injury and failure of product Be careful and avoid personal injuryRooftop Installations Installation of Indoor, Outdoor UnitSelect the best location Indoor unitMulti Piping Type Piping length and elevation24k 36k Drill a hole in the wall Fixing Installation PlateCut the pipes and the cable Flaring workBurrs removal Putting nut onCheck Connecting the PipingIndoor Foamed polyethylene or equivalent is recommendedOutside diameter Torque Indoor unit installationKg .mlbf .ft Flare nut PipesOpen-end wrench fixed Flare nut Wrench Indoor unit SpacerIndoor unit tubing Piping hole Piping forBad case Good caseOutside diameter Torque OutdoorConnect the cable to the Indoor unit Connect the cable to the Outdoor unit Power supplyWith the screw How to connect wiring to the terminals Circuit Breaker MOC rating on the unit rating plate To check the drainage Checking the drainageDrain piping Pour a glass of water on the evaporatorSeal a small Opening around Pipings with Forming the pipingGum type sealer Checking method Air Purging and EvacuationEvacuation Repeat evacuation procedure for each indoor unitFinishing the job Max total ChargingAdditional Test Running Prepare remote controlEvaluation of the performance Heat CONTROLLER, INC
Related manuals
Manual 70 pages 47.27 Kb Manual 35 pages 26.68 Kb Manual 25 pages 18.28 Kb