Charging

Charging

Each outdoor unit is factory charged (nameplate charge) for the evaporator as well as a 7.5m(25ft) line set for each indoor line.

Any time total line set is used either shorter or longer then the nominal 22.5m(75ft: for tri-zone) line set length the refrigerant charge has to be adjusted.

Whether the line set is made shorter or longer you must adjust the charge based on how many ft of tubing are either added or removed based on 20g(0.22oz) of R-410A per meter(foot).

 

Max total

Max length of

Min length of

Max Elevation

Max elevation

Additional

Capacity

between each

between

length of all

each pipe

each pipe

(Btu/h)

indoor unit and

indoor units

Refrigerant

pipes (A+B+C)

(A/B/C)

(A/B/C)

 

outdoor unit (h1)

(h2)

 

 

 

 

 

 

 

 

 

 

 

 

 

24k

30m(100ft)

15m(50ft)

3m(10ft)

7.5m(25ft)

7.5m(25ft)

20g/m(0.22oz/ft)

 

 

 

 

 

 

 

36k

45m(150ft)

15m(50ft)

3m(10ft)

7.5m(25ft)

7.5m(25ft)

20g/m(0.22oz/ft)

Example: A 80ft line set is used for tri - zone 5 additional ft X 0.22 ounces per foot= add 1.1 ounces of R-410A

Important:(Unit is critically charge)

If you are ever uncertain of the unit charge, reclaim, evacuate and weigh in the correct charge using the unit nameplate charge adjusting for line sets longer or shorter than 7.5m(25ft) for each indoor unit.

Installation Manual 27

Image 27
Contents DMC24DB-1, DMH24DB-1 DMC36TB-1, DMH36TB-1 Table of Contents Installation Parts Provided 24k36k Safety Precautions Be sure not to do Be sure to follow the instructionThere is risk of fire, electric shock, explosion or injury Oxygen deficiency could occur Could cause personal injury Personal injuryMoisture may condense and wet or damage furnishings There is risk of fire or product failureThere could result in personal injury and product damage There is risk of fire or electrical shockThere is risk of electric shock There is risk of electrical shockThere is risk of damage or loss of property It may cause a problem for your neighborsAvoid personal injury This could damage your healthBe careful and avoid personal injury It is not sanitary and could cause serious health issuesThere is risk of personal injury There is risk of personal injury and failure of productIndoor unit Installation of Indoor, Outdoor UnitRooftop Installations Select the best locationPiping length and elevation Multi Piping Type24k 36k Drill a hole in the wall Fixing Installation PlatePutting nut on Flaring workCut the pipes and the cable Burrs removalFoamed polyethylene or equivalent is recommended Connecting the PipingCheck IndoorFlare nut Pipes Indoor unit installationOutside diameter Torque Kg .mlbf .ftIndoor unit Spacer Open-end wrench fixed Flare nut WrenchIndoor unit tubing Piping hole Piping forBad case Good caseOutside diameter Torque OutdoorConnect the cable to the Indoor unit Power supply Connect the cable to the Outdoor unitWith the screw How to connect wiring to the terminals Circuit Breaker MOC rating on the unit rating plate Pour a glass of water on the evaporator Checking the drainageTo check the drainage Drain piping Forming the piping Seal a small Opening around Pipings with Gum type sealer Checking method Air Purging and EvacuationRepeat evacuation procedure for each indoor unit EvacuationFinishing the job Charging Max totalAdditional Prepare remote control Test RunningEvaluation of the performance Heat CONTROLLER, INC