Installation of Indoor Unit
CONNECTION PIPE REQUIREMENT
Table 1
M o d e l | Diameter | Maximum | Maximum height | |
|
| (between indoor | ||
| Liquid side | Gas side | length | and outdoor) |
For series 522, 482, 602 | 9.52 mm | 19.05mm | 50 m | 30 m |
| ||||
|
|
|
|
|
For series 282, 362 | 9.52 mm | 15.88mm | 30 m | 150 m |
INSTALLATION PROCEDURE
Install the room air conditioner as follows:
1. REMOVE THE INTAKE GRILL AND SIDE COVER
Air filter
(1) Remove the Air filters
(2) Remove the intake grilles
(3) Remove the Side cover A (Right and left side)
(4)This air conditioner can be set up to intake fresh air . For information about how to install for
2.LOCATION OF CEILING SUSPENSION BOLTS
Intake grille
Fig. 3
30mm
Suspension bolt pitch 1530mm
INDOOR UNIT (TOP VIEW)
30mm
Dimensions
(Space Required for installation)
10mm
155mm
300mm
Suspension bolt should extend outward 30 to 50mm.
For
Supension-bolt pitch should be as shown in Fig.4.
Fig. 4 | 40mm | Ceiling Opening:1530mm | 40mm | |||
|
|
|
|
|
|
|
Ceiling panel
Ceiling Opening:640mm | Suspension bolt should |
15mm | |
| extend outward 30 to 50mm. |
Ceiling panel |
|
14