Haier AC362AFEAA, AC522AFERA, AC482AFEAA, AC602AFEAA Install the room air conditioner as follows

Page 16
Side cover A (Right side) Side cover A (Left side)

Installation of Indoor Unit

CONNECTION PIPE REQUIREMENT

Table 1

M o d e l

Diameter

Maximum

Maximum height

 

 

(between indoor

 

Liquid side

Gas side

length

and outdoor)

For series 522, 482, 602

9.52 mm

19.05mm

50 m

30 m

 

 

 

 

 

 

For series 282, 362

9.52 mm

15.88mm

30 m

150 m

INSTALLATION PROCEDURE

Install the room air conditioner as follows:

1. REMOVE THE INTAKE GRILL AND SIDE COVER

Air filter

(1) Remove the Air filters

(2) Remove the intake grilles

(3) Remove the Side cover A (Right and left side)

(4)This air conditioner can be set up to intake fresh air . For information about how to install for

fresh-air intake, refer to page 22 "FRESH-AIR INTAKE".

2.LOCATION OF CEILING SUSPENSION BOLTS

Intake grille

Fig. 3

30mm

Suspension bolt pitch 1530mm

INDOOR UNIT (TOP VIEW)

30mm

Dimensions

(Space Required for installation)

10mm

155mm

300mm

Suspension bolt should extend outward 30 to 50mm.

For half-concealed installation

Supension-bolt pitch should be as shown in Fig.4.

Fig. 4

40mm

Ceiling Opening:1530mm

40mm

 

 

 

 

 

 

 

Ceiling panel

Ceiling Opening:640mm

Suspension bolt should

15mm

 

extend outward 30 to 50mm.

Ceiling panel

 

14

Image 16
Contents Operation & Installation Manual Contents Disposal of the old air conditioner EAA ERASafety Precautions Safety Precautions Features and Functions Automatic OperationPress the AIR Flow Direction Vertical SET button Press the AIR Flow Direction Horizontal SET buttonRIGHT/LEFT Name of Parts For series 282, 362, 422, 482Cleaning and Care Following four procedures are for series 282, 362, 422, 482Operation Tips Operation and Performance Heating PerformanceInstallation of Indoor Unit LocationSelecting the Mounting Position Indoor Unit Install the room air conditioner as follows Supension-bolt pitch should be as shownDrilling the Holes and Attaching the Suapension Bolts For HALF-CONCESLED Installation Installing the Coupler Heat Insulation Flat washerGood Badbad Installation of Indoor Unit Electrical Wiring Electrical Requirement FRESH-AIR Intake T N 1 2 Customer Guidance Trouble Shooting Followings are not problemsPoor cooling or heating Poor coolingSeries RemarksError display For EAA series Haier Group