Haier AC602AFEAA, AC522AFERA, AC482AFEAA Drilling the Holes and Attaching the Suapension Bolts

Page 17

Installation of Indoor Unit

3.DRILLING THE HOLES AND ATTACHING THE SUAPENSION BOLTS

(1)Drill **25mm holes at the suspension-bolt locations.

(The two special nuts are provided with the unit. The M10 nut must be obtained locally.) Refer to Fig.5.

(2)Install the bolts, then temporarily attach Special nuts A and B and a normal M10 nut to each bolt.

Fig. 5

Bolt Strength

980 to 1470 N (100 TO 150 kgf)

Ceiling panel

Special nut A (included)

10 to 15 mm

Special nut B (included)

M10 nut (Obtained locally)

IF USING ANCHOR BOLTS

(1)Drill holes for anchor bolts at the locations at which you will set the suspension bolts. Note that anchor bolts (to be obtained locally).

(2)Install the anchor bolts ,then temporarily attach special nut "B" (included) and a locally-procurde M10 nut to each of the bolts. (See Fig.6.)

Fig. 6

Anchor-Bolt Strength 980 to 1470 N (100 to 150 kgf)

 

mm

Special nut B

 

(included)

 

15

M10 Nut

 

to

M10 Nut

(Obtaied locally)

10

 

(Obtaied locally)

 

 

 

INSTALLING THE INDOOR UNIT

(1)Lift unit so that suspension bolts pass through suspension fittings at the sides (four places),and slide the unit back.(See Fig.8.)

15

Image 17
Contents Operation & Installation Manual Contents Disposal of the old air conditioner ERA EAASafety Precautions Safety Precautions Automatic Operation Features and FunctionsPress the AIR Flow Direction Horizontal SET button Press the AIR Flow Direction Vertical SET buttonRIGHT/LEFT For series 282, 362, 422, 482 Name of PartsFollowing four procedures are for series 282, 362, 422, 482 Cleaning and CareOperation and Performance Heating Performance Operation TipsLocation Installation of Indoor UnitSelecting the Mounting Position Indoor Unit Supension-bolt pitch should be as shown Install the room air conditioner as followsDrilling the Holes and Attaching the Suapension Bolts For HALF-CONCESLED Installation Flat washer Installing the Coupler Heat InsulationGood Badbad Installation of Indoor Unit Electrical Wiring Electrical Requirement FRESH-AIR Intake T N 1 2 Customer Guidance Followings are not problems Trouble ShootingPoor cooling Poor cooling or heatingRemarks SeriesError display For EAA series Haier Group