Haier AC362AFEAA, AC522AFERA, AC482AFEAA, AC602AFEAA, AC362AFERA Error display For EAA series

Page 30

28

 

For remote

 

Failure code

 

For central

 

Failure description

 

Reason

 

Remarks

 

 

 

 

 

 

 

type, flash

 

on wired

 

control,

 

 

 

 

 

 

 

times

 

controller

 

failure code

 

 

 

 

 

 

1

 

01(01H)

 

01D

 

Indoor ambient temp. sensor failure

 

Sensor broken down or short circuit for more than 2m continuously

 

 

2

 

02(02H)

 

02D

 

Indoor coil temp. sensor failure

 

Sensor broken down or short circuit for more than 2m continuously

 

 

3

 

74(4AH)

 

11D

 

Outdoor ambient temp. sensor failure

 

Sensor broken down or short circuit for more than 2m continuously

 

 

4

 

73(49H)

 

12D

 

Outdoor coil temp. sensor failure/Compressor

 

Sensor broken down or short circuit for more than 2m continuously

 

 

 

 

 

 

 

 

 

discharging temp. sensor abnormal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

72(48H)

 

10D

 

Over-current protection

 

CT check abnormal 3 times in 30m

 

 

6

 

83(53H)

 

14D

 

High/Low pressure abnormal

 

High pressure switch acts 3 times in 30m/Low pressure switch acts

 

 

 

 

 

 

 

 

 

 

 

in normal running

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

71(47H)

 

22D

 

Power supply abnormal

 

Fault phase, short of phase, out of balance greatly

 

 

8

 

07(07H)

 

06D

 

Communication between wired

 

Communication abnormal for more than 4m continuously

 

 

 

 

 

 

 

 

 

controller and indoor abnormal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

06(06H)

 

06D

 

Communication between indoor and outdoor abnormal

 

Communication abnormal for more than 4m continuously

 

 

10

 

08(08H)

 

21D

 

Drainage system abnormal

 

Float switch broken down for more than 25m continuously

 

 

11

 

11(0BH)

 

30D

 

Outside alarm signal input

 

Outside signal broken down for more than 10s

 

 

12

 

03(03H)

 

20D

 

Gas pipe temp. sensor abnormal

 

Sensor broken down or short circuit for more than 2m continuously

 

 

13

 

13(0DH)

 

31D

 

Temperature protection malfunction

 

Solenoid valve act incorrectly 3 times continuously

 

 

15

 

05(05H)

 

17D

 

EEPROM abnormal

 

EEPROM data missing

 

 

17

 

80(50H)

 

15D

 

Compressor overheat

 

The discharging temperature is higher than 120degree

 

Resumable if

 

 

 

 

 

lower than

 

 

 

 

 

 

 

 

 

 

 

100 degree

 

 

 

 

 

 

 

 

 

 

 

18

 

12(0CH)

 

23D

 

Abnormal mode

 

Indoor operation mode is different with the running indoor unit.

 

 

19

 

75(4BH)

 

18D

 

Outdoor coil B(suction temp sensor-for MRV II)

 

Sensor broken down or short circuit for more than 2m continuously

 

 

20

 

77(4DH)

 

15D

 

Outdoor discharging B(oil temp sensor-for MRV II)

 

Sensor broken down or short circuit for more than 2m continuously

 

 

 

 

 

 

 

 

 

 

 

 

 

 

shows resumable fault, * shows it is not resumable fault.

Error display ( For EAA series )

Trouble Shooting

Image 30
Contents Operation & Installation Manual Contents Disposal of the old air conditioner EAA ERASafety Precautions Safety Precautions Features and Functions Automatic OperationPress the AIR Flow Direction Vertical SET button Press the AIR Flow Direction Horizontal SET buttonRIGHT/LEFT Name of Parts For series 282, 362, 422, 482Cleaning and Care Following four procedures are for series 282, 362, 422, 482Operation Tips Operation and Performance Heating PerformanceInstallation of Indoor Unit LocationSelecting the Mounting Position Indoor Unit Install the room air conditioner as follows Supension-bolt pitch should be as shownDrilling the Holes and Attaching the Suapension Bolts For HALF-CONCESLED Installation Installing the Coupler Heat Insulation Flat washerGood Badbad Installation of Indoor Unit Electrical Wiring Electrical Requirement FRESH-AIR Intake T N 1 2 Customer Guidance Trouble Shooting Followings are not problemsPoor cooling or heating Poor coolingSeries RemarksError display For EAA series Haier Group