Haier HSU-12HSA03/R2(DB), HSU-09HSA03/R2(DB) manual Control the temperature the area, Deviation

Page 11

 

 

Haier air conditioner

Edition: 20070116

 

 

 

 

 

 

 

Mode

Corrected contents

Corrected variable

Corrected

 

 

parameter

 

 

 

 

 

 

 

 

Correct the operating mode

ETBL0

4.67

 

 

 

 

 

 

 

 

 

Correct forced operating mode

ETBL1

6

 

 

 

 

 

 

 

 

Heat

When the air capacity is low to

ETBL2

4.67

 

 

 

correct it

 

 

 

 

 

 

 

 

When the air capacity is low to

ETBL3

4.67

 

 

 

correct it

 

 

 

 

 

 

 

 

 

 

 

 

 

Cool and

Correct the operating mode

ETBL4

-0.33

 

 

dry mode

 

 

 

 

 

Correct the forced operating mode

ETBL5

-4

 

2.4 Control the temperature the area

2.4.1 Deviation

Calculation the deviation of the temperature area, as following:

Heat: E= (remote control preset temperature + corrected value)-room temperature

Cool and dry: E=room temperature - (remote control preset temperature+ corrected value)

2.4.2 Compressor OFF OFF When E is negative and E>?T:

 

Heat

 

Cool

 

 

 

 

 

 

?T

TCHAHL

0.67

TCHACL

 

0.33

After ?T variation

TCHAHH

0.67

TCHACH

 

1

?T variation condition

When the system is start to operate, E=3.0

,

The compressor will be stopped after detected continuously for 120 seconds.

After operation starts, when compressor turns off at the first time, based on the above conditions, the unit should operate according to ?T variable data. Between the time when compressor is off and restarts, the unit should operate on ?T starting data (Except dry) and operating mode is transferring. (Except the case that waiting unit is off). Compressor starts when the wrap E is larger than –?T. When compressor is operating and the set temperature by the remote control changes in the orientation that compressor is off, in addition, it is below –?T, compressor will be off.

2.4.3 Compressor operating

During the time when compressor is off, after waiting for 3 minutes, the deviation E is much larger

than- T +0.67 , compressor will start to operate.

2.4.4 DASH operation

When the system starts to operate or to switch the operation mode (except compressor first to off and then to on), when the compressor is on, the system will indicate the maximum frequency satisfied condition as following:

Cool

deviate to 0

Dry

deviate to G area

Heat

deviate to F area

 

- 11 -

Image 11
Contents Haier air conditioner Domestic Air conditionerContents Related Publications General informationMain Specification Product FeaturesModel HSU-12HSA03/R2DB Specification Edition Chip pin definition Scope of ApplicationII. Temperature adjustment function Preset temperature correction When frequency increase to holding frequencyDeviation Control the temperature the areaControl frequency in the same area Air capacity limited DefrostHeat operation Indoor fan motor controlHaier air conditioner Dry operation Cool operationEnhanced Cool Enhanced operationEnhanced heat Fresh air Timer operatingSilence operation Automatic operation Timer ON/OFFAutomation operating mode Sleep operatingLow load protection controlling Full-automation operationRunning-in Low load protection control High load protection controlEeprom control Low temperature treatment in the heat modeIndoor unit single operating Error list recordPower failure compensation Special functionRating cool Rating operatingFault explain Emergency switch Vertical swing Air deflector controlSetting position range Cool/dry +DLHUDLUFRQGLWLRQHUGLWLRQ +RULRQWDOVZLQJ Room temperature sensor Thermistor resistance chart10.76 10.31 Indoor pipe sensor&outdoor ambient sensor, defrosting sensor Haier air conditioner Haier air conditioner Temperature Haier air conditioner Haier air conditioner 111 Haier air conditioner Trouble shooting System may have been over or under Yes Room temperature sensor failureHeat-exchange sensor failure CN9 ‡ ‡ 1R ‡  Malfunction Unsolved F11 The malfunction of the compressor’ rotor circuitF4 Overheat protection for exhaust temperature F22 AC electricity protection F1 The protection of IPM E9 High work-intense protection F12 Outdoor Eeprom error E4 Indoor Eeprom errorYES Indoor fan motor malfunctionF3 Communication fault between the IPM and outdoor PCB F19 Power voltage is too high or low Yes High drop and long pipe capacity modification curves Performance curves diagramHSU-09HSA03/R2DB Cooling capacity-temperature curvesCooling value Temperature table HSU-12HSA03/R2DB Heating capacity Temp. curves Heating capacity-temperature curvesHaier air conditioner Air outlet temp. Ambient temp. table Air outlet temp.-ambient temperature curves HSU-09HSA03/R2DB10.15 Cooling discharge pressure table Cooling discharge pressure curves HSU-09HSA03/R2DBHaier air conditioner Cooling suction pressure table Cooling suction pressure curves HSU-09HSA03/R2DBHaier air conditioner Heating discharge pressure table Heating discharge pressure curves HSU-09HSA03/R2DBHaier air conditioner Heating suction pressure table Heating suction pressure curves HSU-09HSA03/R2DB600 Sensible cooling value Temperature table Sensible cooling value-temperature curves HSU-09HSA03/R2DBHSU-12HSA03/R2DB Power consumption value Temp. table Power consumption-temp. Curves HSU-09HSA03/R2DB18/12 843 969 1152 1348 1564 1687 1820 1972 18/14 855 Noise curves HSU-09HSA03/R2DB HSU-09HSA03/R2DB Compressor performance curvesHaier air conditionerEdition HSU-12HSA03/R2DB Compressor C-6RZ092H1AWiring diagram ,$*5$0228722581,7 Circuit Diagram Indoor unit Outdoor Unit Installation Manual of Room Air Conditioner Selection of Installation Place Outdoor Unit Indoor unit Installation of the Indoor Unit Drawing of pipe When connecting the cable after installing the indoor unit Outdoor unit Purging MethodTo use vacuum pump Power Source Installation Haier air conditioner