Haier HSU-09HSA03/R2(DB), HSU-12HSA03/R2(DB) manual Purging MethodTo use vacuum pump

Page 88

Haier air conditioner

Edition: 20070116

Outdoor unit

5.Purging Method:To use vacuum pump

3-way valve Gas Side 12.7mm(1/2")

2-way valve Liquid Side 6.35mm(1/4")

Detach the service port's cap of 3-way valve, the valve rod's cap for 2-way valve and 3-way's, connect the service port into the projection of charge hose (Iow) for gaugemanifold. Then connect the projection of charge hose (center) for gaugemanifold into vacuum pump.

Gaugemanifold(for R410A)

Anti countercurrent joint

Tube(for R410A)

Vacuum pump(for R410A)

Open the handle at Iow in gaugemanifold, operate vacuum pump. If the scale-moves of gause (Iow)

reach vacuum condition in a moment, check again.

Vacuumize for over 15min. And check the level gauge which should read -0.1 MPa (-76 cm Hg) at Iow pressure side. After the completion of vacuumizing, close the handle 'Lo' in gaugemanifold and stop the operation of the vacuum pump.

Check the condition of the scale and hold it for 1-2min. If the scale-moves back in spite of tightening, make flaring work again, the return to the beginning of .

Open the valve rod for the 2-way valve to an angle of anticlockwise 90 degrees.

After 6 seconds, close the 2-way valve and make the inspection of gas leakage.

In case of gas leakage, tighten

No gas leakage? parts of pipe connection. If leakage stops, then proceed steps.

Detach the charge hose from the service port, open

2-way valve and 3-way. Turn the valve rod anticlockwise until hitting lightly.

Open

Close

Open

90O

If it does not stop gas leakage, discharge whole refrigerants from the service port. After flaring work again and vacuumize, fill up prescribed refrigerant from the gas cylinder

3-way valve

2-way valve

2-way valve

3-way valve

6.35mm(1/4")

9.52mm(3/8")

 

12.7mm(1/2")

HSU-09HSA03/R2(DB)

HSU-12HSA03/R2(DB)

2-way valve 6.35mm(1/4")

3-way valve 9.52mm(3/8") 12.7mm(1/2")

HSU-18HSA03/R2(DB)

HSU-22HSA03/R2(DB)

To prevent the gas leakage, turn the service port's cap, the valve rod's cap for 2-way valve and 3-way's a little more than the point where the torque increases suddenly.

After attaching the each caps, check the gas leakage around the caps.

CAUTION:

1.If the refrigerant of the air conditioner leaks, it is necessary to discharge all the refrigerant. Vacuumize first, then charge the liquid refrigerant into air conditioner according to the amount marked on the name plate.

2-way valve

Valve rod cap

Valve rod cap

Service port cap

2.Please do not let other cooling medium, except specified one (R410A),

or air enter into the cooling circulation system. Otherwise, there will be

abnormal high pressure in the system to make it crack and lead to

personal injuries.

- 88 -

Image 88
Contents Domestic Air conditioner Haier air conditionerContents General information Related PublicationsProduct Features Main SpecificationModel HSU-12HSA03/R2DB Specification Edition Scope of Application Chip pin definitionII. Temperature adjustment function When frequency increase to holding frequency Preset temperature correctionControl the temperature the area DeviationControl frequency in the same area Defrost Air capacity limitedIndoor fan motor control Heat operationHaier air conditioner Cool operation Dry operationEnhanced heat Enhanced operationEnhanced Cool Silence operation Timer operatingFresh air Timer ON/OFF Automation operating modeSleep operating Automatic operationRunning-in Full-automation operationLow load protection controlling High load protection control Low load protection controlLow temperature treatment in the heat mode Eeprom controlError list record Power failure compensationSpecial function Indoor unit single operatingRating operating Rating coolFault explain Emergency switch Air deflector control Vertical swingSetting position range Cool/dry +DLHUDLUFRQGLWLRQHUGLWLRQ +RULRQWDOVZLQJ Thermistor resistance chart Room temperature sensor10.76 10.31 Indoor pipe sensor&outdoor ambient sensor, defrosting sensor Haier air conditioner Haier air conditioner Temperature Haier air conditioner Haier air conditioner 111 Haier air conditioner Trouble shooting System may have been over or under Heat-exchange sensor failure Room temperature sensor failureYes CN9 ‡ ‡ 1R ‡  F11 The malfunction of the compressor’ rotor circuit Malfunction UnsolvedF4 Overheat protection for exhaust temperature F22 AC electricity protection F1 The protection of IPM E9 High work-intense protection E4 Indoor Eeprom error F12 Outdoor Eeprom errorIndoor fan motor malfunction YESF3 Communication fault between the IPM and outdoor PCB F19 Power voltage is too high or low Yes Performance curves diagram High drop and long pipe capacity modification curvesCooling value Temperature table Cooling capacity-temperature curvesHSU-09HSA03/R2DB HSU-12HSA03/R2DB Heating capacity-temperature curves Heating capacity Temp. curvesHaier air conditioner Air outlet temp.-ambient temperature curves HSU-09HSA03/R2DB Air outlet temp. Ambient temp. table10.15 Cooling discharge pressure curves HSU-09HSA03/R2DB Cooling discharge pressure tableHaier air conditioner Cooling suction pressure curves HSU-09HSA03/R2DB Cooling suction pressure tableHaier air conditioner Heating discharge pressure curves HSU-09HSA03/R2DB Heating discharge pressure tableHaier air conditioner Heating suction pressure curves HSU-09HSA03/R2DB Heating suction pressure table600 Sensible cooling value-temperature curves HSU-09HSA03/R2DB Sensible cooling value Temperature tableHSU-12HSA03/R2DB Power consumption-temp. Curves HSU-09HSA03/R2DB Power consumption value Temp. table18/12 843 969 1152 1348 1564 1687 1820 1972 18/14 855 Noise curves HSU-09HSA03/R2DB Haier air conditionerEdition Compressor performance curvesHSU-09HSA03/R2DB Compressor C-6RZ092H1A HSU-12HSA03/R2DBWiring diagram ,$*5$0228722581,7 Circuit Diagram Indoor unit Outdoor Unit Installation Manual of Room Air Conditioner Selection of Installation Place Outdoor Unit Indoor unit Installation of the Indoor Unit Drawing of pipe When connecting the cable after installing the indoor unit Outdoor unit Purging MethodTo use vacuum pump Power Source Installation Haier air conditioner