Haier HSU-09HSA03/R2(DB), HSU-12HSA03/R2(DB) manual Indoor fan motor malfunction, Yes

Page 52

HSU-09/12HR03/R2(DB)

Service diagnosis

7.3.2Indoor fan motor malfunction

Indoor Display E14

Method of

The rotation speed detected by the Hall IC during fan motor operation is used to

Malfunction

determine abnormal fan motor operation

Detection

 

Malfunction

when the detected rotation feedback singal don’t receiced in 2 minutes

Decision

 

Conditions

 

Supposed

Operation halt due to breaking of wire inside the fan motor .

Causes

Operation halt due to breaking of the fan motor lead wires

 

Detection error due to faulty indoor unit PCB

whether terminal CN13

NO

and CN7 on indoor PCB

 

 

well inserted or not?

 

YES

Electrify the machine again and turn it on in the cooling operation, Measure voltage between the positions 1 ( blue wire) and 3( yellow wire) of Terminal CN13 on the indoor PCB

Pull out and reinsert the terminals

NO

the voltage is about 90-200vac

Yes

NO

check whether motor can run when turn on the unit

the indoor pcb is damaged and need replace

When motor is running Measure whether there is voltage pulse(12VDC) between the positions 1(middle wire) and 4( black wire) of Terminal CN7 on the indoor PCB

Yes

the indoor motor is damaged and need replace

is nomal or not?

YES

NO

the indoor motor is damaged and need replace

the indoor pcb is damaged and need replace

52

Domestic air conditioner5

Image 52
Contents Domestic Air conditioner Haier air conditionerContents General information Related PublicationsProduct Features Main SpecificationModel HSU-12HSA03/R2DB Specification Edition Scope of Application Chip pin definitionII. Temperature adjustment function When frequency increase to holding frequency Preset temperature correctionControl the temperature the area DeviationControl frequency in the same area Defrost Air capacity limitedIndoor fan motor control Heat operationHaier air conditioner Cool operation Dry operationEnhanced heat Enhanced operationEnhanced Cool Silence operation Timer operatingFresh air Timer ON/OFF Automation operating modeSleep operating Automatic operationRunning-in Full-automation operationLow load protection controlling High load protection control Low load protection controlLow temperature treatment in the heat mode Eeprom controlError list record Power failure compensationSpecial function Indoor unit single operatingRating operating Rating coolFault explain Emergency switch Air deflector control Vertical swingSetting position range Cool/dry +DLHUDLUFRQGLWLRQHUGLWLRQ +RULRQWDOVZLQJ Thermistor resistance chart Room temperature sensor10.76 10.31 Indoor pipe sensor&outdoor ambient sensor, defrosting sensor Haier air conditioner Haier air conditioner Temperature Haier air conditioner Haier air conditioner 111 Haier air conditioner Trouble shooting System may have been over or under Heat-exchange sensor failure Room temperature sensor failureYes CN9 ‡ ‡ 1R ‡  F11 The malfunction of the compressor’ rotor circuit Malfunction UnsolvedF4 Overheat protection for exhaust temperature F22 AC electricity protection F1 The protection of IPM E9 High work-intense protection E4 Indoor Eeprom error F12 Outdoor Eeprom errorIndoor fan motor malfunction YESF3 Communication fault between the IPM and outdoor PCB F19 Power voltage is too high or low Yes Performance curves diagram High drop and long pipe capacity modification curvesCooling value Temperature table Cooling capacity-temperature curvesHSU-09HSA03/R2DB HSU-12HSA03/R2DB Heating capacity-temperature curves Heating capacity Temp. curvesHaier air conditioner Air outlet temp.-ambient temperature curves HSU-09HSA03/R2DB Air outlet temp. Ambient temp. table10.15 Cooling discharge pressure curves HSU-09HSA03/R2DB Cooling discharge pressure tableHaier air conditioner Cooling suction pressure curves HSU-09HSA03/R2DB Cooling suction pressure tableHaier air conditioner Heating discharge pressure curves HSU-09HSA03/R2DB Heating discharge pressure tableHaier air conditioner Heating suction pressure curves HSU-09HSA03/R2DB Heating suction pressure table600 Sensible cooling value-temperature curves HSU-09HSA03/R2DB Sensible cooling value Temperature tableHSU-12HSA03/R2DB Power consumption-temp. Curves HSU-09HSA03/R2DB Power consumption value Temp. table18/12 843 969 1152 1348 1564 1687 1820 1972 18/14 855 Noise curves HSU-09HSA03/R2DB Haier air conditionerEdition Compressor performance curvesHSU-09HSA03/R2DB Compressor C-6RZ092H1A HSU-12HSA03/R2DBWiring diagram ,$*5$0228722581,7 Circuit Diagram Indoor unit Outdoor Unit Installation Manual of Room Air Conditioner Selection of Installation Place Outdoor Unit Indoor unit Installation of the Indoor Unit Drawing of pipe When connecting the cable after installing the indoor unit Outdoor unit Purging MethodTo use vacuum pump Power Source Installation Haier air conditioner