Service diagnosis |
7.3.2Indoor fan motor malfunction
Indoor Display E14
Method of | The rotation speed detected by the Hall IC during fan motor operation is used to |
Malfunction | determine abnormal fan motor operation |
Detection |
|
Malfunction | when the detected rotation feedback singal don’t receiced in 2 minutes |
Decision |
|
Conditions |
|
Supposed | Operation halt due to breaking of wire inside the fan motor . |
Causes | Operation halt due to breaking of the fan motor lead wires |
| Detection error due to faulty indoor unit PCB |
whether terminal CN13 | NO |
and CN7 on indoor PCB |
|
| |
well inserted or not? |
|
YES
Electrify the machine again and turn it on in the cooling operation, Measure voltage between the positions 1 ( blue wire) and 3( yellow wire) of Terminal CN13 on the indoor PCB
Pull out and reinsert the terminals
NO
the voltage is about
Yes
NO
check whether motor can run when turn on the unit
the indoor pcb is damaged and need replace
When motor is running Measure whether there is voltage pulse(12VDC) between the positions 1(middle wire) and 4( black wire) of Terminal CN7 on the indoor PCB
Yes
the indoor motor is damaged and need replace
is nomal or not?
YES
NO
the indoor motor is damaged and need replace
the indoor pcb is damaged and need replace