Haier HSU-09HSA03/R2(DB), HSU-12HSA03/R2(DB) manual Haier air conditioner

Page 68

Haier air conditioner

Edition: 20070116

HSU-12HSA03/R2(DB)

Heating discharge pressure table

Outdoor temp. (Humidity 46%)

 

Indoor temp.

 

 

 

 

 

DB/WB

15

20

25

15

2087

2226

2400

 

 

 

 

10

2179

2320

2462

5

2309

2417

2560

0

2446

2569

2734

 

 

 

 

5

2520

2668

2877

 

 

 

 

10

2590

2779

2990

15

2713

2903

3067

 

 

 

 

20

2728

2945

3145

 

 

 

+($7,1*',6&+$5*(35(6685(

 



 

 

 

 



 

 

 

 

 

 

 

 

 



 

 

 

 

 

 



 

 

 

 

 

 

 

 

PRESSUR



 

 

 

 

 

 

 



 

 

 

 

 

 

 



 

 

 

 

 

 

 

DISCHARGE

 

 

 

 

 

 

 



 

 

 

 

 

 

 



 

 

 

 

 

 

 



 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 



 

 

 

 

 

 

 

 

















 

 

 

 

Outdoor Temp

 

 

 

- 68 -

Image 68
Contents Domestic Air conditioner Haier air conditionerContents General information Related PublicationsProduct Features Main SpecificationModel HSU-12HSA03/R2DB Specification Edition Scope of Application Chip pin definitionII. Temperature adjustment function When frequency increase to holding frequency Preset temperature correctionControl the temperature the area DeviationControl frequency in the same area Defrost Air capacity limitedIndoor fan motor control Heat operationHaier air conditioner Cool operation Dry operationEnhanced Cool Enhanced operationEnhanced heat Fresh air Timer operatingSilence operation Timer ON/OFF Automation operating modeSleep operating Automatic operationLow load protection controlling Full-automation operationRunning-in High load protection control Low load protection controlLow temperature treatment in the heat mode Eeprom controlError list record Power failure compensationSpecial function Indoor unit single operatingRating operating Rating coolFault explain Emergency switch Air deflector control Vertical swingSetting position range Cool/dry +DLHUDLUFRQGLWLRQHUGLWLRQ +RULRQWDOVZLQJ Thermistor resistance chart Room temperature sensor10.76 10.31 Indoor pipe sensor&outdoor ambient sensor, defrosting sensor Haier air conditioner Haier air conditioner Temperature Haier air conditioner Haier air conditioner 111 Haier air conditioner Trouble shooting System may have been over or under Yes Room temperature sensor failureHeat-exchange sensor failure CN9 ‡ ‡ 1R ‡  F11 The malfunction of the compressor’ rotor circuit Malfunction UnsolvedF4 Overheat protection for exhaust temperature F22 AC electricity protection F1 The protection of IPM E9 High work-intense protection E4 Indoor Eeprom error F12 Outdoor Eeprom errorIndoor fan motor malfunction YESF3 Communication fault between the IPM and outdoor PCB F19 Power voltage is too high or low Yes Performance curves diagram High drop and long pipe capacity modification curvesHSU-09HSA03/R2DB Cooling capacity-temperature curvesCooling value Temperature table HSU-12HSA03/R2DB Heating capacity-temperature curves Heating capacity Temp. curvesHaier air conditioner Air outlet temp.-ambient temperature curves HSU-09HSA03/R2DB Air outlet temp. Ambient temp. table10.15 Cooling discharge pressure curves HSU-09HSA03/R2DB Cooling discharge pressure tableHaier air conditioner Cooling suction pressure curves HSU-09HSA03/R2DB Cooling suction pressure tableHaier air conditioner Heating discharge pressure curves HSU-09HSA03/R2DB Heating discharge pressure tableHaier air conditioner Heating suction pressure curves HSU-09HSA03/R2DB Heating suction pressure table600 Sensible cooling value-temperature curves HSU-09HSA03/R2DB Sensible cooling value Temperature tableHSU-12HSA03/R2DB Power consumption-temp. Curves HSU-09HSA03/R2DB Power consumption value Temp. table18/12 843 969 1152 1348 1564 1687 1820 1972 18/14 855 Noise curves HSU-09HSA03/R2DB HSU-09HSA03/R2DB Compressor performance curvesHaier air conditionerEdition Compressor C-6RZ092H1A HSU-12HSA03/R2DBWiring diagram ,$*5$0228722581,7 Circuit Diagram Indoor unit Outdoor Unit Installation Manual of Room Air Conditioner Selection of Installation Place Outdoor Unit Indoor unit Installation of the Indoor Unit Drawing of pipe When connecting the cable after installing the indoor unit Outdoor unit Purging MethodTo use vacuum pump Power Source Installation Haier air conditioner