Haier air conditioner

Edition: 20070116

3.3.2 Compressor ON

When the air capacity is set High, Middle and Low, the compressor will operate by the set mode. When the air capacity is set auto fan, the air capacity will be adjusted by the temperature.

. Enhanced operation

Enhanced operation will continue for 15 minutes.

Enhanced operation will finish if the operation is off or after 15 minutes.

Enhanced operation will finish when the status be changed.

Enhanced operation will finish if the unit enters the status of “silence”, operates normally or on-timer signal control.

In the auto mode, there are enhanced /silence function; the main unit operating is based on enhanced cool /silence function in the cool mode; the main unit operated by the enhanced heat/silence function in the heat mode; the main unit will operate is based on no-enhanced/silence function in the fan mode.

4.1 Enhanced heat

Modify the set temperature. It has temperature-adjustment function.

Air capacity will be automatic middle fan speed.

When operating for defrosting, outdoor unit will not receive the communication signal of enhanced operation. After operation for defrosting, the system will operate enhanced function only in the remaining time.

After enhanced operation continues for 15 minutes, compressor is forbidden to be OFF for 10 minutes. (Except the error)

4.2 Enhanced Cool

Modify the set temperature. It has temperature-adjustment function.

The high air capacity will be set for hand controlling.

- 17 -

Image 17
Contents Haier air conditioner Domestic Air conditionerContents Related Publications General informationMain Specification Product FeaturesModel HSU-12HSA03/R2DB Specification Edition Chip pin definition Scope of ApplicationII. Temperature adjustment function Preset temperature correction When frequency increase to holding frequencyDeviation Control the temperature the areaControl frequency in the same area Air capacity limited DefrostHeat operation Indoor fan motor controlHaier air conditioner Dry operation Cool operationEnhanced Cool Enhanced operationEnhanced heat Fresh air Timer operatingSilence operation Automation operating mode Timer ON/OFFSleep operating Automatic operationLow load protection controlling Full-automation operationRunning-in Low load protection control High load protection controlEeprom control Low temperature treatment in the heat modePower failure compensation Error list recordSpecial function Indoor unit single operatingRating cool Rating operatingFault explain Emergency switch Vertical swing Air deflector controlSetting position range Cool/dry +DLHUDLUFRQGLWLRQHUGLWLRQ +RULRQWDOVZLQJ Room temperature sensor Thermistor resistance chart10.76 10.31 Indoor pipe sensor&outdoor ambient sensor, defrosting sensor Haier air conditioner Haier air conditioner Temperature Haier air conditioner Haier air conditioner 111 Haier air conditioner Trouble shooting System may have been over or under Yes Room temperature sensor failureHeat-exchange sensor failure CN9 ‡ ‡ 1R ‡  Malfunction Unsolved F11 The malfunction of the compressor’ rotor circuitF4 Overheat protection for exhaust temperature F22 AC electricity protection F1 The protection of IPM E9 High work-intense protection F12 Outdoor Eeprom error E4 Indoor Eeprom errorYES Indoor fan motor malfunctionF3 Communication fault between the IPM and outdoor PCB F19 Power voltage is too high or low Yes High drop and long pipe capacity modification curves Performance curves diagramHSU-09HSA03/R2DB Cooling capacity-temperature curvesCooling value Temperature table HSU-12HSA03/R2DB Heating capacity Temp. curves Heating capacity-temperature curvesHaier air conditioner Air outlet temp. Ambient temp. table Air outlet temp.-ambient temperature curves HSU-09HSA03/R2DB10.15 Cooling discharge pressure table Cooling discharge pressure curves HSU-09HSA03/R2DBHaier air conditioner Cooling suction pressure table Cooling suction pressure curves HSU-09HSA03/R2DBHaier air conditioner Heating discharge pressure table Heating discharge pressure curves HSU-09HSA03/R2DBHaier air conditioner Heating suction pressure table Heating suction pressure curves HSU-09HSA03/R2DB600 Sensible cooling value Temperature table Sensible cooling value-temperature curves HSU-09HSA03/R2DBHSU-12HSA03/R2DB Power consumption value Temp. table Power consumption-temp. Curves HSU-09HSA03/R2DB18/12 843 969 1152 1348 1564 1687 1820 1972 18/14 855 Noise curves HSU-09HSA03/R2DB HSU-09HSA03/R2DB Compressor performance curvesHaier air conditionerEdition HSU-12HSA03/R2DB Compressor C-6RZ092H1AWiring diagram ,$*5$0228722581,7 Circuit Diagram Indoor unit Outdoor Unit Installation Manual of Room Air Conditioner Selection of Installation Place Outdoor Unit Indoor unit Installation of the Indoor Unit Drawing of pipe When connecting the cable after installing the indoor unit Outdoor unit Purging MethodTo use vacuum pump Power Source Installation Haier air conditioner