Friedrich PTAC - R410A service manual Keep the air tightness well. Try not to use the electic

Page 27

A/C on. No cooling (or heating)

Refrigerant is insuffi cient or leaking

Refrigeration system is blocked

Too much refrigerant

The effi ciency of the compressor is low

Condenser can’t discharge smoothly

At the time of heating, the electric heater

can’t run

Outdoor temperature is too high

Check leakage, carry out vacuum-pumping after repairing leakage and charge refrigerant according to requirements

Check whether the system is blocked by observing the condensation of the evaporator and the pressure value of the high pressure manometer, and then take measures to deal with the system.

Release the redundant refrigerant in system

Replace the compressor

Get rid of the obstacle

1.the wire is loosened; 2. thermal fuse is broken;

3.temperature limiter is damaged; 4. electric heater is damaged; 5. controller is broken. correct the wore correctly or replace those parts which has malfunction.

You can install the rain-proof and sun-proof board. If the

cooling air is still insuffi cient, you are suggested

to replace the A/C

 

Whether the cooling (heating) load is suitable

 

 

 

 

 

 

 

Check the preset cooling (heating) load

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The air tightness in room is not good. People

 

 

 

 

 

 

 

Keep the air tightness well. Try not to use the electic

 

come in and go out frequently. There are

 

 

 

 

 

appliances with a large quantity of heat

 

heating devices in the room when A/C is cooling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Call for fan

motor but fan motor will not come on

Supply voltage is unstable

Wrong wire connection

The fan’s capacitor is broken

The motor winding is of broken circuit or short circuit or the built in temperature limiter device in open circuit due to overheat.

The controller has malfunction

The compressor capacitor is broken; wrong wire

connection

Check the reason and correct it.

Check the circuit and connect the wire correctly

according to the electic circuit diagram

Replace fan’s capacitor with the same

mode and specifi cation

Replace those parts which has malfunction

Replace the controller

Replace capacitor; connect the wire correctly

according to the electric circuit diagram

Compressor isn’t running (controller is with output)

The compressor’s motor is burned out

The compressor is jammed or blocked

Check with a multimeter if the enclosed motor windings of compressor is with short or broken circuit or earthing. If so, it is needed to replace it with the same type and specifi cations.

Knock the compressor housing with a rubber bar or with a hammer padding with a wood, the compressor might be shocked and run. If not, change the compressor.

25

Image 27
Contents Ptac R410A Models Technical Support Contact Information Table of Contents Your safety and the safety of others are very important Important Safety InformationPersonal Injury or Death Hazards Mechanical Hazards IntroductionGeneral Product Features Digital Packaged Terminal Air Conditioners & Heat Pumps Component Identification Accessories Pxfta Unit Identification Chassis Specifications Cooling & Heating Performance PDE 265V Extended Cooling Performance Electric Heat Data Power Cord Information 230/208V Models only Electrical Rating TablesElectric Shock Hazard Electrical Wiring for 265 Volt Models To Chassis Junction Remote Control Thermostat Installation Desk Control Terminals Digital Temperature Friedrich Digital Control Features+*&-.4-*2+4 #$%&#*%&+,-*&./0#&1!0*$# DIP SwitchDigital Control Diagnostics Fan can’t run or the fan speed is too slow Malfunction AnalysisKeep the air tightness well. Try not to use the electic Supply voltage is abnormal Capacitor Connections Components TestingCapacitors Capacitor Check with Capacitor AnalyzerDrain PAN Valve Heater Elements and Limit SWITCHES’ SpecificationsRefrigeration Sequence of Operation Risk of Electric Shock 410A Sealed Refrigeration System RepairsEquipment Required Equipment Must be CapableFreeze Hazard Method Of Charging / RepairsUndercharged Refrigerant Systems Burn HazardRestricted Refrigerant System Overcharged Refrigerant SystemsCapillary Tube Systems Hermetic Components CheckMetering Device Check ValveTesting the Coil Reversing Valve DESCRIPTION/OPERATIONChecking the Reversing Valve Procedure For Changing Reversing Valve Touch Test in Heating/Cooling CycleFire Hazard Compressor Checks Single Phase Resistance Test External OverloadGround Test Compressor Replacement Recommended procedure for compressor replacementHigh Temperatures Electrical Shock Hazard Routine MaintenanceTroubleshooting Chart Heating Troubleshooting Chart CoolingElectrical Troubleshooting Chart Heat Pump System Cools When Heating is DesiredYES Electronic Control Board Electronic Control Board Component ID Wiring DiagramRT6 5558+131!8 Resistance Table for Air Indoor Temperature Sensor Temp Resistance Friedrich Packaged Terminal AIR Conditioners and Heat Pumps Ptac Exploded View Ptac Parts List PDE Models Ptac Parts List PDH Models Friedrich AIR Conditioning CO