ELECTRICAL TROUBLESHOOTING CHART - HEAT PUMP

WARNING

ELECTRIC SHOCK HAZARD

Turn off electric power before service or installation.

Extreme care must be used, if it becomes necessary to work on equipment with power applied.

Failure to do so could result in serious injury or death.

CAUTION

BURN HAZARD

Certain unit components operate at temperatures hot enough to cause burns.

Proper safety procedures must be followed, and proper protective clothing must be worn.

Failure to do so could result in minor to moderate injury.

HEAT PUMP

SYSTEM COOLS WHEN HEATING IS DESIRED.

Is Line Voltage

Present at the

Solenoid Valve?

YES

NO

Is the Selector Switch Set for Heat?

Is the Solenoid Coil Good?

YES

NO

Replace the Solenoid Coil

Reversing Valve Stuck

Replace the Reversing Valve

41

Image 43
Contents Ptac R410A Models Technical Support Contact Information Table of Contents Your safety and the safety of others are very important Important Safety InformationPersonal Injury or Death Hazards Mechanical Hazards IntroductionGeneral Product Features Digital Packaged Terminal Air Conditioners & Heat Pumps Component Identification Accessories Pxfta Unit Identification Chassis Specifications Cooling & Heating Performance PDE 265V Extended Cooling Performance Electric Heat Data Electrical Rating Tables Power Cord Information 230/208V Models onlyElectric Shock Hazard Electrical Wiring for 265 Volt Models To Chassis Junction Remote Control Thermostat Installation Desk Control Terminals Digital Temperature Friedrich Digital Control Features+*&-.4-*2+4 #$%&#*%&+,-*&./0#&1!0*$# DIP SwitchDigital Control Diagnostics Fan can’t run or the fan speed is too slow Malfunction AnalysisKeep the air tightness well. Try not to use the electic Supply voltage is abnormal Capacitor Connections Components TestingCapacitors Capacitor Check with Capacitor AnalyzerDrain PAN Valve Heater Elements and Limit SWITCHES’ SpecificationsRefrigeration Sequence of Operation Risk of Electric Shock 410A Sealed Refrigeration System RepairsEquipment Required Equipment Must be CapableFreeze Hazard Method Of Charging / RepairsUndercharged Refrigerant Systems Burn HazardRestricted Refrigerant System Overcharged Refrigerant SystemsCapillary Tube Systems Hermetic Components CheckMetering Device Check ValveReversing Valve DESCRIPTION/OPERATION Testing the CoilChecking the Reversing Valve Touch Test in Heating/Cooling Cycle Procedure For Changing Reversing ValveFire Hazard Compressor Checks External Overload Single Phase Resistance TestGround Test Recommended procedure for compressor replacement Compressor ReplacementHigh Temperatures Electrical Shock Hazard Routine MaintenanceTroubleshooting Chart Heating Troubleshooting Chart CoolingSystem Cools When Heating is Desired Electrical Troubleshooting Chart Heat PumpYES Electronic Control Board Electronic Control Board Component ID Wiring DiagramRT6 5558+131!8 Resistance Table for Air Indoor Temperature Sensor Temp Resistance Friedrich Packaged Terminal AIR Conditioners and Heat Pumps Ptac Exploded View Ptac Parts List PDE Models Ptac Parts List PDH Models Friedrich AIR Conditioning CO