Friedrich Understanding Overcharged and Undercharged 410A System Symptoms

Page 34

After the unit has run 10 to 15 minutes, check the gauge pressures.Gaugesconnectedtosystemwithanundercharge will have low head pressures and substantially low suction pressures.

Improper air fl ow over the evaporator coil may indicate some of the same symptoms as an over charged system. An overcharge can cause the compressor to fail, since it would be “slugged” with liquid refrigerant.

The charge for any system is critical. When the compressor is noisy, suspect an overcharge, when you are sure that the air quantity over the evaporator coil is correct. Icing of the evaporator will not be encountered because the refrigerant will boil later if at all. Gauges connected to system will usually have higher head pressure (depending upon amount of over charge). Suction pressure should be slightly higher.

Overcharged Refrigerant Systems

Compressor amps will be near normal or higher. Noncondensables can also cause these symptoms. To confi rm, remove some of the charge, if conditions improve, system may be overcharged. If conditions don’t improve, Noncondensables are indicated.

Wheneveranoverchargedsystemisindicated,alwaysmake sure that the problem is not caused by air fl ow problems.

Restricted Refrigerant System

Troubleshooting a restricted refrigerant system can be diffi cult. The following procedures are the more common problems and solutions to these problems. There are two types of refrigerant restrictions: Partial restrictions and complete restrictions.

A partial restriction allows some of the refrigerant to circulate through the system.

With a complete restriction there is no circulation of refrigerant in the system.

Restricted refrigerant systems display the same symptoms as a “low-charge condition.”

When the unit is shut off, the gauges may equalize very slowly.

Gauges connected to a completely restricted system will run in a deep vacuum. When the unit is shut off, the gauges

will not equalize at all.

A quick check for either condition begins at the evaporator. With a partial restriction, there may be gurgling sounds at the metering device entrance to the evaporator. The evaporator in a partial restriction could be partially frosted or have an ice ball close to the entrance of the metering device. Frost may continue on the suction line back to the compressor.

Often a partial restriction of any type can be found by feel, as there is a temperature difference from one side of the restriction to the other.

With a complete restriction, there will be no sound at the metering device entrance. An amperage check of the compressor with a partial restriction may show normal

32current when compared to the unit specifi cation.

With a complete restriction the current drawn may be considerably less than normal, as the compressor is running in a deep vacuum (no load.) Much of the area of the condenser will be relatively cool since most or all of the liquid refrigerant will be stored there.

The following conditions are based primarily on a system in the cooling mode.

Image 34
Contents Ptac R410A Models Technical Support Contact Information Table of Contents Important Safety Information Your safety and the safety of others are very importantPersonal Injury or Death Hazards Introduction Mechanical HazardsGeneral Product Features Digital Packaged Terminal Air Conditioners & Heat Pumps Component Identification Accessories Pxfta Unit Identification Chassis Specifications Cooling & Heating Performance PDE 265V Extended Cooling Performance Electric Heat Data Electrical Rating Tables Power Cord Information 230/208V Models onlyElectric Shock Hazard Electrical Wiring for 265 Volt Models To Chassis Junction Remote Control Thermostat Installation Desk Control Terminals Friedrich Digital Control Features Digital Temperature+*&-.4-*2+4 DIP Switch #$%&#*%&+,-*&./0#&1!0*$#Digital Control Diagnostics Malfunction Analysis Fan can’t run or the fan speed is too slowKeep the air tightness well. Try not to use the electic Supply voltage is abnormal Capacitor Check with Capacitor Analyzer Components TestingCapacitors Capacitor ConnectionsHeater Elements and Limit SWITCHES’ Specifications Drain PAN ValveRefrigeration Sequence of Operation Equipment Must be Capable 410A Sealed Refrigeration System RepairsEquipment Required Risk of Electric ShockBurn Hazard Method Of Charging / RepairsUndercharged Refrigerant Systems Freeze HazardOvercharged Refrigerant Systems Restricted Refrigerant SystemCheck Valve Hermetic Components CheckMetering Device Capillary Tube SystemsReversing Valve DESCRIPTION/OPERATION Testing the CoilChecking the Reversing Valve Touch Test in Heating/Cooling Cycle Procedure For Changing Reversing ValveFire Hazard Compressor Checks External Overload Single Phase Resistance TestGround Test Recommended procedure for compressor replacement Compressor ReplacementHigh Temperatures Routine Maintenance Electrical Shock HazardTroubleshooting Chart Cooling Troubleshooting Chart HeatingSystem Cools When Heating is Desired Electrical Troubleshooting Chart Heat PumpYES Electronic Control Board Electronic Control Board Wiring Diagram Component IDRT6 5558+131!8 Resistance Table for Air Indoor Temperature Sensor Temp Resistance Friedrich Packaged Terminal AIR Conditioners and Heat Pumps Ptac Exploded View Ptac Parts List PDE Models Ptac Parts List PDH Models Friedrich AIR Conditioning CO