COMPONENTS TESTING

BLOWER / FAN MOTOR

A single phase permanent split capacitor motor is used to drive the evaporator blower and condenser fan. A self-resetting overload is located inside the motor to protect against high temperature and high amperage conditions.

WARNING

ELECTRIC SHOCK HAZARD

Disconnect power to the unit before servicing. Failure to follow this warning could result in serious injury or death.

BLOWER / FAN MOTOR TEST

1.Make sure the motor has cooled down.

2.Disconnect the fan motor wires from the control board.

3.Test for continuity between the windings also, test to ground.

4.If any winding is open or grounded replace the motor.

Capacitor Check with Capacitor Analyzer

The capacitor analyzer will show whether the capacitor is “open” or “shorted.” It will tell whether the capacitor is within its micro farads rating and it will show whether the capacitor is operating at the proper power-factor percentage. The instrument will automatically discharge the capacitor when the test switch is released.

Capacitor Connections

The starting winding of a motor can be damaged by a shorted and grounded running capacitor. This damage usually can be avoided by proper connection of the running capacitor terminals.

From the supply line on a typical 230 volt circuit, a 115 volt potential exists from the “R” terminal to ground through a possible short in the capacitor. However, from the “S” or start terminal, a much higher potential, possibly as high as 400 volts, exists because of the counter EMF generated in the start winding. Therefore, the possibility of capacitor failure is much greater when the identifi ed terminal is connected to the “S” or start terminal. The identifi ed terminal should always be connected to the supply line, or “R” terminal, never to the “S” terminal.

When connected properly, a shorted or grounded running capacitor will result in a direct short to ground from the “R” terminal and will blow the line fuse. The motor protector will protect the main winding from excessive temperature.

CAPACITORS

WARNING

ELECTRIC SHOCK HAZARD

Turn off electric power before servicing. Discharge capacitor with a 20,000 Ohm 2 Watt resistor before handling.

Failure to do so may result in personal injury, or death.

Many motor capacitors are internally fused. Shorting the terminals will blow the fuse, ruining the capacitor. A 20,000 ohm 2 watt resistor can be used to discharge capacitors safely. Remove wires from capacitor and place resistor across terminals. When checking a dual capacitor with a capacitor analyzer or ohmmeter, both sides must be tested.

27

Image 29
Contents Ptac R410A Models Technical Support Contact Information Table of Contents Your safety and the safety of others are very important Important Safety InformationPersonal Injury or Death Hazards Mechanical Hazards IntroductionGeneral Product Features Digital Packaged Terminal Air Conditioners & Heat Pumps Component Identification Accessories Pxfta Unit Identification Chassis Specifications Cooling & Heating Performance PDE 265V Extended Cooling Performance Electric Heat Data Electric Shock Hazard Power Cord Information 230/208V Models onlyElectrical Rating Tables Electrical Wiring for 265 Volt Models To Chassis Junction Remote Control Thermostat Installation Desk Control Terminals Digital Temperature Friedrich Digital Control Features+*&-.4-*2+4 #$%&#*%&+,-*&./0#&1!0*$# DIP SwitchDigital Control Diagnostics Fan can’t run or the fan speed is too slow Malfunction AnalysisKeep the air tightness well. Try not to use the electic Supply voltage is abnormal Capacitors Components TestingCapacitor Check with Capacitor Analyzer Capacitor ConnectionsDrain PAN Valve Heater Elements and Limit SWITCHES’ SpecificationsRefrigeration Sequence of Operation Equipment Required 410A Sealed Refrigeration System RepairsEquipment Must be Capable Risk of Electric ShockUndercharged Refrigerant Systems Method Of Charging / RepairsBurn Hazard Freeze HazardRestricted Refrigerant System Overcharged Refrigerant SystemsMetering Device Hermetic Components CheckCheck Valve Capillary Tube SystemsChecking the Reversing Valve Testing the CoilReversing Valve DESCRIPTION/OPERATION Fire Hazard Procedure For Changing Reversing ValveTouch Test in Heating/Cooling Cycle Compressor Checks Ground Test Single Phase Resistance TestExternal Overload High Temperatures Compressor ReplacementRecommended procedure for compressor replacement Electrical Shock Hazard Routine MaintenanceTroubleshooting Chart Heating Troubleshooting Chart CoolingYES Electrical Troubleshooting Chart Heat PumpSystem Cools When Heating is Desired Electronic Control Board Electronic Control Board Component ID Wiring DiagramRT6 5558+131!8 Resistance Table for Air Indoor Temperature Sensor Temp Resistance Friedrich Packaged Terminal AIR Conditioners and Heat Pumps Ptac Exploded View Ptac Parts List PDE Models Ptac Parts List PDH Models Friedrich AIR Conditioning CO