Friedrich PTAC - R410A service manual Digital Packaged Terminal Air Conditioners & Heat Pumps

Page 8

Digital Packaged Terminal Air Conditioners & Heat Pumps

Cooling: 7600 – 15,000 Btuh

Heating: 7600 – 14500 Btuh (Heat Pump) 6824 – 17060 Btuh (Electric Heat)

Friedrich Models: PDE – Cooling with or without electric heat PDH – Heat Pump with electric heat

All units shall be factory assembled, piped, wired and fully charged with

310 for air conditioners and ARI standard 380 for heat pumps. Units shall be UL listed and carry a UL label. All units shall be factory run- tested to check operation and be Friedrich or equivalent.

The basic unit shall not exceed 16” high x 42” wide. Overall depth of the unit from the rear of the Friedrich wall sleeve to the front of the decorative front cover shall not exceed 21 ¼”. The unit shall be designed so that room intrusion may be as little as 7 ½”. Installations in walls deeper than 13 ¼” may be accomplished with the use of a deep wall sleeve (PDXWSEXT). Unit shall draw in ambient air through both sides of an outdoor architectural louver or grille measuring 42” wide x 16” high and shall exhaust air out middle portion of the louver. The architectural louver and wall sleeve shall be designed so that the louver may be installed from the inside of the building.

REFRIGERATION SYSTEM – The refrigeration system shall be her- metically sealed and consist of a rotary compressor that is externally mounted on vibration isolators no smaller than 1 3/8” dia. x 1 ½” high; condenser and evaporator coils constructed of copper tubes and

and have a drain pan capable of retaining 1 ½ gallons of condensate. A tertiary condensate removal system shall also be incorporated for

of the building as a safeguard against damage to the interior room.

INDOOR AIR HANDLING SECTION – The indoor air handling sec- tion shall consist of a tangential blower wheel direct driven by a totally enclosed motor. The air handling system shall be designed to minimize

fan must have three fan speeds that may be selected by the user.

throughout the room. The grille shall be reversible to allow a change

personal injury or damage to the unit.

and reusable by cleaning with water or by vacuuming.

The chassis shall have a built-in damper capable of providing at least

damper closed to ensure a proper seal.

OUTDOOR AIR HANDLING SECTION – The outdoor air section shall consist of a single injection molded fan shroud that incorporates the outdoor motor mount into a single piece for ease of service and assembly. The outdoor motor shall be totally enclosed, ball-bearing, permanently lubricated and directly drive the outdoor fan/slinger ring.

CONTROLS – Covered controls shall be accessible in a compartment at least 7½” wide with the controls no deeper than 1 ¼” in the opening to facilitate easy operation of the unit.

The unit controls shall feature a soft blue LED readout that can display either room temperature or setpoint temperature. The unit shall re- ceive input from the digital control panel through push buttons labeled: ‘Cool’, ‘Heat’, ‘High Fan’, ‘Med Fan’, ‘Low Fan’, ￿ ’, ‘￿’ and ‘Power’. When ‘Off’, the unit may be put directly into cooling or heating mode by pressing the ‘Cool’ or ‘Heat’ button.

The unit must have the following energy saving and convenience features built-in:

Quiet start/stop fan delay

Fan cycle control for cooling and heating independently

Room freeze protection

Random compressor restart

Electronic temperature limiting

The PTAC must also offer the ability to be controlled by a remote wall- mounted thermostat without additional accessories. Low voltage inputs will include: C (common), R (24V power), Y (cooling), GL (fan low), GH (fan high), W (heat) and O (reversing valve on PDH heat pumps only).

PTAC models shall use a single stage cool / single stage heat ther- mostat. PTHP models shall use a single stage cool / two-stage heat thermostat. An accessory thermostat must be available from the manufacturer, RT6 or equivalent. The RT6 thermostat will provide temperature setpoint, mode selection from cool, heat and fan modes. The thermostat must also allow the selection of fan speed between high and low speed.

Other controls accessible without removal of the chassis shall include fan cycle switch, fresh air vent control and emergency heat override switch (heat pump only).

ELECTRICAL CONNECTION – All PTAC/PTHP units shall come from the factory with a power cord installed. All 230/208V power cords shall feature a leakage current detection device on the plug head. All units shall feature a 6-pin connector for removal of the power cord. The power cord shall be interchangeable to allow changes to the heater output based on the property/electrical requirements.

GENERAL CONSTRUCTION – The wall sleeve shall be constructed of 18-gauge Galvanized zinc-coated steel. It shall be prepared by a process where it is zinc phosphate pretreated and sealed with a

cured for durability. The sleeve shall be shipped with a protective weatherboard and a structural center support, and be insulated for

shipped separately and made from stamped or extruded anodized aluminum. All louvers shall be in the horizontal plane.

clips. As an option the cover may be attached by two screws to pre- vent tampering. The front panel will feature a contoured discharge with no sharp corners.

CORROSION PROTECTION – The unit shall have corrosion-resistant fans, fan shroud and drain pan for corrosion protection and to prevent rust on the side of the building below the outdoor louver. The unit shall

-

rioration. The outdoor coil shall have Diamonblue corrosion protection

applications including seacoast environments. All outdoor coils shall also have stainless steel endplates to eliminate rusting of the endplates.

WARRANTY – The warranty is one year on all parts and 5 years on the sealed system including compressor, indoor and outdoor coils and refrigerant tubing.

6

Image 8
Contents Ptac R410A Models Technical Support Contact Information Table of Contents Important Safety Information Your safety and the safety of others are very importantPersonal Injury or Death Hazards Introduction Mechanical HazardsGeneral Product Features Digital Packaged Terminal Air Conditioners & Heat Pumps Component Identification Accessories Pxfta Unit Identification Chassis Specifications Cooling & Heating Performance PDE 265V Extended Cooling Performance Electric Heat Data Electric Shock Hazard Power Cord Information 230/208V Models onlyElectrical Rating Tables Electrical Wiring for 265 Volt Models To Chassis Junction Remote Control Thermostat Installation Desk Control Terminals Friedrich Digital Control Features Digital Temperature+*&-.4-*2+4 DIP Switch #$%&#*%&+,-*&./0#&1!0*$#Digital Control Diagnostics Malfunction Analysis Fan can’t run or the fan speed is too slowKeep the air tightness well. Try not to use the electic Supply voltage is abnormal Components Testing CapacitorsCapacitor Check with Capacitor Analyzer Capacitor ConnectionsHeater Elements and Limit SWITCHES’ Specifications Drain PAN ValveRefrigeration Sequence of Operation 410A Sealed Refrigeration System Repairs Equipment RequiredEquipment Must be Capable Risk of Electric ShockMethod Of Charging / Repairs Undercharged Refrigerant SystemsBurn Hazard Freeze HazardOvercharged Refrigerant Systems Restricted Refrigerant SystemHermetic Components Check Metering DeviceCheck Valve Capillary Tube SystemsChecking the Reversing Valve Testing the CoilReversing Valve DESCRIPTION/OPERATION Fire Hazard Procedure For Changing Reversing ValveTouch Test in Heating/Cooling Cycle Compressor Checks Ground Test Single Phase Resistance TestExternal Overload High Temperatures Compressor ReplacementRecommended procedure for compressor replacement Routine Maintenance Electrical Shock HazardTroubleshooting Chart Cooling Troubleshooting Chart HeatingYES Electrical Troubleshooting Chart Heat PumpSystem Cools When Heating is Desired Electronic Control Board Electronic Control Board Wiring Diagram Component IDRT6 5558+131!8 Resistance Table for Air Indoor Temperature Sensor Temp Resistance Friedrich Packaged Terminal AIR Conditioners and Heat Pumps Ptac Exploded View Ptac Parts List PDE Models Ptac Parts List PDH Models Friedrich AIR Conditioning CO