Friedrich PTAC - R410A service manual Supply voltage is abnormal

Page 28

Protector is

activated due to

overheating of the compressor

Refrigerant is insuffi cient or super abundance

Capillary is blocked and the suction

temperature is rising

The compressor can run smoothly or is stuck.

The air discharge valve is damaged.

Adjust the quantity of the refrigerant

Replace capillary

Replace the compressor

Compressor

is ON-OFF frequently

 

 

 

 

Use the multimeter to check whether the contact point of the

 

Protector has malfunction

 

 

 

compressor is conducted at the timer of non-subheating. If it

 

 

 

 

 

 

 

can’t be conducted, please replace the protector.

 

 

 

 

 

 

 

 

 

 

 

 

 

Supply voltage is abnormal

 

 

Check the reason, improve the power supply condition and

 

 

 

add the regulated power supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The radiating for evaporator and condensor is

 

 

Get rid of the dust on the evaporator and condensor, remove

 

not good; Poor air ventilation

 

 

the obstacles at the air outlet

 

 

 

 

 

 

 

 

 

The air conditioner capability does not match

 

 

 

 

the area of the room, i.e. so called “Big system,

 

 

Slect the A/C which is applicable to the room areas

 

 

 

 

 

 

 

small room”.

 

 

 

 

 

 

 

 

 

 

 

 

Reveiving distance of remote control

is too short

LCD display fl ashes or when pressing the transmit button the entire screen is displayed.

Replace the battery

Battery’s capacity is insuffi cient

Replace the battery

Replace the battery

LED display is found short of stroke

The LCD frame hasn’t fi xed well

Fix the LCD frame properly

Vibration and noise are abnormal

The compressor hasn’t installed well and the

base is unstable

The unit hasn’t placed fl atly and stable

The unit’s support is unstable

Check whether the base is fi rm

Adjust the unit’s position

Strengthen the support or refi t it

There are foreign objects on the unit

Get rid of the foreign objects

Screws are loosened

Tighten the screws

As for the above malfunction analysis, there aren’t malfunction related to heating for the cooling only unit.

26

Image 28
Contents Ptac R410A Models Technical Support Contact Information Table of Contents Important Safety Information Your safety and the safety of others are very importantPersonal Injury or Death Hazards Introduction Mechanical HazardsGeneral Product Features Digital Packaged Terminal Air Conditioners & Heat Pumps Component Identification Accessories Pxfta Unit Identification Chassis Specifications Cooling & Heating Performance PDE 265V Extended Cooling Performance Electric Heat Data Electrical Rating Tables Power Cord Information 230/208V Models onlyElectric Shock Hazard Electrical Wiring for 265 Volt Models To Chassis Junction Remote Control Thermostat Installation Desk Control Terminals Friedrich Digital Control Features Digital Temperature+*&-.4-*2+4 DIP Switch #$%&#*%&+,-*&./0#&1!0*$#Digital Control Diagnostics Malfunction Analysis Fan can’t run or the fan speed is too slowKeep the air tightness well. Try not to use the electic Supply voltage is abnormal Components Testing CapacitorsCapacitor Check with Capacitor Analyzer Capacitor ConnectionsHeater Elements and Limit SWITCHES’ Specifications Drain PAN ValveRefrigeration Sequence of Operation 410A Sealed Refrigeration System Repairs Equipment RequiredEquipment Must be Capable Risk of Electric ShockMethod Of Charging / Repairs Undercharged Refrigerant SystemsBurn Hazard Freeze HazardOvercharged Refrigerant Systems Restricted Refrigerant SystemHermetic Components Check Metering DeviceCheck Valve Capillary Tube SystemsReversing Valve DESCRIPTION/OPERATION Testing the CoilChecking the Reversing Valve Touch Test in Heating/Cooling Cycle Procedure For Changing Reversing ValveFire Hazard Compressor Checks External Overload Single Phase Resistance TestGround Test Recommended procedure for compressor replacement Compressor ReplacementHigh Temperatures Routine Maintenance Electrical Shock HazardTroubleshooting Chart Cooling Troubleshooting Chart HeatingSystem Cools When Heating is Desired Electrical Troubleshooting Chart Heat PumpYES Electronic Control Board Electronic Control Board Wiring Diagram Component IDRT6 5558+131!8 Resistance Table for Air Indoor Temperature Sensor Temp Resistance Friedrich Packaged Terminal AIR Conditioners and Heat Pumps Ptac Exploded View Ptac Parts List PDE Models Ptac Parts List PDH Models Friedrich AIR Conditioning CO