Friedrich PTAC - R410A service manual Hermetic Components Check, Metering Device, Check Valve

Page 35

HERMETIC COMPONENTS CHECK

WARNING

BURN HAZARD

Proper safety procedures must be followed, and proper protective clothing must be worn when working with a torch.

Failure to follow these procedures could result in moderate or serious injury.

WARNING

CUT/SEVER HAZARD

Be careful with the sharp edges and corners. Wear protective clothing and gloves, etc.

Failure to do so could result in serious injury.

METERING DEVICE

Capillary Tube Systems

All units are equipped with capillary tube metering devices.

Checking for restricted capillary tubes.

1.Connect pressure gauges to unit.

2.Start the unit in the cooling mode. If after a few minutes of operation the pressures are normal, the check valve and the cooling capillary are not restricted.

3.Switch the unit to the heating mode and observe the gauge readings after a few minutes running time. If the system pressure is lower than normal, the heating capillary is restricted.

4.If the operating pressures are lower than normal in both the heating and cooling mode, the cooling capillary is restricted.

CHECK VALVE

A unique two-way check valve is used on the reverse cycle heat pumps. It is pressure operated and used to direct the

ow of refrigerant through a single fi lter drier and to the proper capillary tube during either the heating or cooling cycle.

One-way Check Valve

(Heat Pump Models)

NOTE: The slide (check) inside the valve is made of tefl on. Should it become necessary to replace the check valve, place a wet cloth around the valve to prevent overheating during the brazing operation.

CHECK VALVE OPERATION

In the cooling mode of operation, high pressure liquid enters the check valve forcing the slide to close the opposite port (liquid line) to the indoor coil. Refer to refrigerant fl ow chart. This directs the refrigerant through the fi lter drier and cooling capillary tube to the indoor coil.

In the heating mode of operation, high pressure refrigerant enters the check valve from the opposite direction, closing

the port (liquid line) to the outdoor coil. The fl ow path of the refrigerant is then through the fi lter drier and heating capillary to the outdoor coil.

Failure of the slide in the check valve to seat properly in either mode of operation will cause fl ooding of the cooling coil. This is due to the refrigerant bypassing the heating or cooling capillary tube and entering the liquid line.

COOLING MODE

In the cooling mode of operation, liquid refrigerant from condenser (liquid line) enters the cooling check valve forcing the heating check valve shut. The liquid refrigerant is directed into the liquid dryer after which the refrigerant is metered through cooling capillary tubes to evaporator. (Note: liquid refrigerant will also be directed through the heating capillary tubes in a continuous loop during the cooling mode).

HEATING MODE

In the heating mode of operation, liquid refrigerant from the indoor coil enters the heating check valve forcing the cooling check valve shut. The liquid refrigerant is directed into the liquid dryer after which the refrigerant is metered through the heating capillary tubes to outdoor coils. (Note: liquid refrigerant will also be directed through the cooling capillary tubes in a continuous loop during the heating mode).

33

Image 35
Contents Ptac R410A Models Technical Support Contact Information Table of Contents Your safety and the safety of others are very important Important Safety InformationPersonal Injury or Death Hazards Mechanical Hazards IntroductionGeneral Product Features Digital Packaged Terminal Air Conditioners & Heat Pumps Component Identification Accessories Pxfta Unit Identification Chassis Specifications Cooling & Heating Performance PDE 265V Extended Cooling Performance Electric Heat Data Electric Shock Hazard Power Cord Information 230/208V Models onlyElectrical Rating Tables Electrical Wiring for 265 Volt Models To Chassis Junction Remote Control Thermostat Installation Desk Control Terminals Digital Temperature Friedrich Digital Control Features+*&-.4-*2+4 #$%&#*%&+,-*&./0#&1!0*$# DIP SwitchDigital Control Diagnostics Fan can’t run or the fan speed is too slow Malfunction AnalysisKeep the air tightness well. Try not to use the electic Supply voltage is abnormal Capacitor Connections Components TestingCapacitors Capacitor Check with Capacitor AnalyzerDrain PAN Valve Heater Elements and Limit SWITCHES’ SpecificationsRefrigeration Sequence of Operation Risk of Electric Shock 410A Sealed Refrigeration System RepairsEquipment Required Equipment Must be CapableFreeze Hazard Method Of Charging / RepairsUndercharged Refrigerant Systems Burn HazardRestricted Refrigerant System Overcharged Refrigerant SystemsCapillary Tube Systems Hermetic Components CheckMetering Device Check ValveChecking the Reversing Valve Testing the CoilReversing Valve DESCRIPTION/OPERATION Fire Hazard Procedure For Changing Reversing ValveTouch Test in Heating/Cooling Cycle Compressor Checks Ground Test Single Phase Resistance TestExternal Overload High Temperatures Compressor ReplacementRecommended procedure for compressor replacement Electrical Shock Hazard Routine MaintenanceTroubleshooting Chart Heating Troubleshooting Chart CoolingYES Electrical Troubleshooting Chart Heat PumpSystem Cools When Heating is Desired Electronic Control Board Electronic Control Board Component ID Wiring DiagramRT6 5558+131!8 Resistance Table for Air Indoor Temperature Sensor Temp Resistance Friedrich Packaged Terminal AIR Conditioners and Heat Pumps Ptac Exploded View Ptac Parts List PDE Models Ptac Parts List PDH Models Friedrich AIR Conditioning CO