Lincoln Electric SAE-300 manual Gfci Testing and Resetting, PROCEDuRE

Page 21

D-4

MAINTENANCE

D-4

 

 

 

GFCI TESTING AND RESETTING

PROCEDuRE

The GFCI should be properly tested at least once every month or whenever it is tripped. To properly test and reset the GFCI :

If the GFCI has tripped, first carefully remove any load and check it for damage.

If the equipment has been shut down, it must be restarted.

The equipment needs to be operating at high idle speed and any necessary adjustments made on the control panel so that the equipment is providing at least 80 volts to the receptacle input terminals.

The circuit breaker for this receptacle must not be tripped. Reset if necessary.

Push the "Reset" button located on the GFCI. This will assure normal GFCI operation.

Plug a night-light (with an "ON/OFF" switch) or other product (such as a lamp) into the Duplex receptacle and turn the product "ON".

Push the "Test" button located on the GFCI. The night-light or other product should go "OFF".

Push the "Reset" button, again. The light or other product should go "ON" again.

If the light or other product remains "ON" when the "Test" button is pushed, the GFCI is not working prop- erly or has been incorrectly installed (miswired). If your GFCI is not working properly, contact a qualified, certified electrician who can assess the situation, rewire the GFCI if necessary or replace the device.

SAE-300®

Image 21
Contents SAE-300 California Proposition 65 Warnings SafetyElectric ShOCK can kill ARC Rays can burnFuMES and Gases can be dangerous Welding and CuTTING Sparks can Cause fire or explosion Cylinder may explode if damagedIii Sûreté Pour Soudage a L’Arc PRÉCAuTIONS DE SûretéOn-Line Product Registration Please Examine Carton and Equipment For Damage ImmediatelyTAbLE of Contents TEChNICAL Specifications SAE-300 InstallationDescription Volts @ Rated Amps CycleDesign FEATuRES General DescriptionReceptacle Trailer see Optional FEATuRES PRE-OPERATION InstallationLocation / Ventilation MAChINE GROuNDINGPRE-OPERATION Service OILCooling System BATTERY ChARGING 5INSTALLATIONA-5To prevent ExPLOSION when To prevent Electrical Damage whenENGINE OPERATION OperationStarting ThE SAE-300 404D-22 Diesel Engine Cold WEAThER StartingWelder Operation Engine bREAK-INStick / TIG Welding Idler Operation MIG WeldingOptional FEATuRES Field Installed AccessoriesWire Feeder Options Safety PRECAuTIONS MaintenanceGeneral INSTRuCTIONS Cooling SystemNameplates Idler MaintenancePuRGING AIR from FuEL System Perkins 404D-22 Engine Vent Screw Priming LeverMaintenance PROCEDuRE Gfci Testing and ResettingHOW to uSE TROubLEShOOTING GuIDE TROubLEShOOTINGSymptoms PRObLEMSPOSSIbLE CAuSE RecommendedYour local Lincoln Authorized POSSIbLE Areas of MISADJuSTMENTSSOpen Closed Electronic Idler TROubLEShOOTING GuIDEDefective -- Will Not Close Auxiliary Power Load is Turned onContact your local Lincoln Authorized Field Service FacilityWater passage. Flush the system Ing on Faulty light wiring Diagrams S10766-14 Atenção Atenção