A-6

INSTALLATION

A-6

 

 

 

8.Connect input supply voltage per the Auxiliary Input Power Connection Instructions listed earlier.

9.The relays could also be used to provide contact closure for any interfacing signals out using the nor- mally open contacts. An external auxiliary supply voltage would not be necessary to use the relays as hard contact closure out signals. NOTE - The CR1 relay as shipped does not have AUX leads connect- ed to it. This relay has two normally open contacts that close at the start of the weld cycle and open at the end of the weld cycle. These hard contact clo- sures could be used as a signal out when interfac- ing to PLC’s or custom controls.

Shutdown Inputs:

The POWER FEED™ 10A CONTROLLER has two shutdown inputs available on the terminal strip. These are independent, normally closed inputs that can be used for limit switches, PLC inputs, etc, in order to shut down the welding operation for any reason. Shutdown #1 is located on terminal strip blocks #24 and #25. Shutdown #2 is located on terminal strip blocks #26 and #27.

1.Remove all input power to the POWER FEED™ 10A CONTROLLER including any auxiliary power supplies.

2.Remove the wire duct cover to gain access to the leads on the right side of the terminal strip.

3.Remove one of the plug buttons located on the bot- tom of the POWER FEED™ 10A CONTROLLER control box and install some type of strain relief for the auxiliary control leads.

4.Connect the external shutdown circuit to either of the shutdown terminal blocks, #24 & #25, and/or #26 & #27. A normally closed circuit must be con- nected – the POWER FEED™ 10A CONTROLLER will recognize an open circuit as a shutdown com- mand.

5.Remove the shorting jumpers imbedded in the cen- ter of the terminal strip with a small screwdriver for the shutdown circuits to be used.

When a shutdown input is received, all welding will stop and an error message will be displayed on the POWER FEED™ 10A CONTROLLER. The shutdown circuit must be closed before resetting Controller. To reset the system, the Mode Select Panel display will prompt the user to press the left Mode Select Panel Pushbutton.

Shutdown #2 can be configured for Output Lockout mode by enabling option P.21 in the Setup Menu (Refer to Section B, General Setup Mode Options). when the input is opened, output is disabled, but cold feed of wire is still possible.

Stop Input:

The POWER FEED™ 10A CONTROLLER has a Stop Input available on the terminal strip. The Stop Input will work just like pressing the STOP Pushbutton. This circuit is in parallel with the STOP Pushbutton located on the Switch Panel. Unlike the Shutdown Inputs, which completely shutdown all welding and auxiliary equipment, the STOP Input will allow all welding and auxiliary motion to continue based on the END OPTIONS configurations in the POWER FEED™ 10A

CONTROLLER.

1.Remove all input power to the POWER FEED™ 10A CONTROLLER including any auxiliary power supplies.

2.Remove the wire duct cover to gain access to the leads on the right side of the terminal strip.

3.Remove one of the plug buttons located on the bot- tom of the POWER FEED™ 10A CONTROLLER control box and install some type of strain relief for the auxiliary control leads.

4.Connect the external Stop Input circuit to terminal blocks #28 and #29.

The Stop Input is not necessary if the POWER FEED™ 10A CONTROLLER is configured for Remote Interfacing, mentioned earlier, due to the fact that the Stop circuit can be accessed, in this configuration, on terminal strip blocks #39 and #41. The Stop Input was intended to be used when the Switch Panel is still included in the system, either on the Controller, or in the Pendant.

Note: the STOP circuit only needs a momentary clo- sure to be recognized by the POWER FEED™ 10A CONTROLLER. If the STOP button is held, the START and INCH buttons are not recognized.

POWER FEED™ 10A CONTROLLER

Image 13
Contents Power Feed 10A Controller California Proposition 65 Warnings SafetyElectric Shock can kill Iii Welding and Cutting Sparks can Cause fire or explosionSûreté Pour Soudage a L’Arc Précautions DE SûretéThank You Table of Contents Power Feed 10A Controller Technical Specifications Power Feed 10A ControllerGeneral Information Safety Precaution InstallationAuxiliary Input Power Connection Instructions Interfacing to the Power Feed 10A ControllerConverting Switch Panel to a remote pendant Interfacing to the Switch Panel Controls Figure A.2 Controlling NON-LINCOLN Auxiliary EquipmentStop Input Shutdown InputsPower Feed 10A Controller Control BOX Connection Diagram SystemWelding with Multiple Arcs Remote Sense Lead SpecificationsOperation Design FeaturesDefinitions of Welding Modes Common Welding AbbreviationsRecommended Processes Product DescriptionProcess Limitations Equipment LimitationsLocating Front Panel Controls and INPUT, Ouput Connections Control BOX Without Door Power Feed 10A ControllerControl BOX With Door LED condition Definition Case Front Controls Case Front Control DescriptionsWire Feeder Setup POWER-UP SequenceInch Wire Feed Speed Setting Travel ModeMode Select Panel 4 MSP4 Changing Weld Modes Weld Mode DescriptionTable B.1 DescriptionStart Options AC ControlSet Timers Setup Mode OptionsSetup END OptionsWeld Sequence Parameter List Parameter Units Range Default Value Where is IT SET?General Setup Mode Options LOCKOUT/SECURITY Infrared IR ControlPanel Multi Procedure Welding Procedure Memory VS. User MemoryMemory Recalling Memory SavingHigh Limit Limit SettingAttribute General Options Accessories AccessoriesSafety Precautions MaintenanceRoutine Maintenance Periodic MaintenanceHOW to USE Troubleshooting Guide TroubleshootingYour local Lincoln Authorized Field Service Facility LINC-NET System Error CodesYour local Lincoln Authorized Field Service FacilityContact your local Lincoln Output Problems Troubleshooting Power Feed 10A Controller M20414 DimensionprintPrecaucion Warnung