INSTALLATION

A-4

 

 

 

230V INPUT

The equipment is provided with a 230/115V cable, 6.6ft.(2m) in length with a 230V 6-50P attachment plug.

The Invertec V205-T performs best when connected to 230VAC inputs. This input allows full output of the machine (200 amps).

115V INPUT

A suitable 115V attachment plug must be installed on the power cord to use the V205-T with a 115V input supply. The rated output of the V205-T is available when con- nected to a 30A branch circuit. When connected to a branch circuit with lower amp rating, lower welding cur- rent and duty cycle must be used. An output guide is pro- vided below. The values are approximate and must be adjusted downward if the fuse or circuit breaker trips off. Other loads on the circuit and fuse/circuit breaker char- acteristics will affect the available output. Do not exceed these welding conditions:

15A branch circuit

10% duty cycle Stick: 75A TIG: 105A

20A branch circuit

10% duty cycle Stick: 90A TIG: 130A

ATTACHMENT PLUG INSTALLATION

Connect the white (neutral) wire under terminal clamp with silver screw, and black (hot) wire under terminal clamp with brass screw. Connect green wire under terminal clamp with green screw.

WARNING

Failure to wire as instructed may cause personal injury or damage to equipment. To be installed or checked by an electrician or qualified person only.

---------------------------------------------------------------------------

In all cases, the green or green/yellow grounding wire must be connected to the grounding pin of the plug, usu- ally identified by a green screw.

Attachment plugs must comply with the Standard for Attachment Plugs and Receptacles, UL498.

The product is considered acceptable for use only when an attachment plug as specified is properly attached to the supply cord.

For use on engine drives, keep in mind the above input draw restrictions and the following precaution.

ENGINE DRIVEN GENERATOR

The Invertec V205-T DC & V205-T AC/DC can be operated on engine driven generators as long as the

230 volt auxiliary meets the following conditions:

The AC waveform peak voltage is below 400 volts.

The AC waveform frequency is between 45 and 65Hz.

The following Lincoln engine drives meet these condi- tions when run in the high idle mode:

Ranger 250, 250 LPG, 305 G, 305 D*

Vantage 300, 400, 500 & Air Vantage 500*

Some engine drives do not meet these conditions (e.g. Miller Bobcats, etc). Operation of the Invertec V205-T AC/DC is not recommended on engine drives not conforming to these conditions. Such drives may deliver unacceptably high voltage levels to the Invertec power source.

*Ranger and Vantage Engine Drives require the full KVA Adapter Kit (K1816-1)

V205-T DC & V205-T AC/DC TIG

Image 13
Contents Invertec V205-T DC & V205-T AC/DC TIG April California Proposition 65 Warnings SafetyElectric Shock can kill Iii Welding and Cutting Sparks can Cause fire or explosionSûreté Pour Soudage a LʼArc Précautions DE SûretéV205-T DC & V205-T AC/DC TIG Safety Thank You Table of Contents Operating Temperature Range Installation Storage Temperature Range Stacking Select Suitable LocationTilting Environmental AreaInput Connections Reconnect ProcedureTable A.1 Nominal Range230V Input Attachment Plug Installation115V Input Engine Driven GeneratorOutput Connection for Stick Welding Figure A.2 Output and GAS Connection for TIG Welding Figure A.1Work Cable Connection Shielding GAS Connection Remote Control ConnectionOperation Safety InstructionsGeneral Description Welding CapabilityFigure B.1 Rear Control Panel Figure B.1Figure B.2 Controls and SettingsStep Diagram TIG DC Indicator Parameter Default SET UP MenuWelding Polarity Output LimitationsAlternating Current AC/DC model only Pulsed TIGCopper TIG Welding Steel TIG WeldingTips for AC TIG Welding Filler MaterialProtective GAS Tips for Improved TIG StartingAC TIG AC TIG Welding Quick Start UPDC TIG Welding Quick Start UP Optional Accessories AccessoriesCompatible Equipment Cable PlugsSafety Precautions MaintenanceInput Filter Capacitor Discharge Procedure Routine MaintenanceHOW to USE Troubleshooting Guide TroubleshootingTroubleshooting Field Service Facility Problems TIG WeldingYour local Lincoln Authorized Display FailuresV205-T DC Wiring Diagram for Wiring DiagramsV205-T AC/DC Wiring Diagram for V205-T DC & V205-T AC/DC TIG V205-T DC & V205-T AC/DC TIG Precaucion Warnung