COMPLAINT

CAUSE

 

REMEDY

 

 

 

 

 

 

 

 

Fan motor noise.

Fan

 

If cracked, out of balance, or partially missing,

 

 

 

 

 

replace it.

 

 

 

 

 

 

 

 

 

 

Blower

 

If cracked, out of balance, or partially missing,

 

 

 

 

 

replace it.

 

 

 

 

 

 

 

 

 

 

Loose set screw

 

Tighten it.

 

 

 

 

 

 

 

 

 

 

Worn bearings

 

If knocking sounds continue when running or

 

 

 

 

 

loose, replace the motor. If the motor hums or

 

 

 

 

 

noise appears to be internal while running,

 

 

 

 

 

replace motor.

 

 

 

 

 

 

Compressor will not run,

Voltage

 

Check voltage. See the limits on the preceding

 

fan motor runs.

 

 

page. If not within limits, call an electrician.

 

 

 

 

 

 

 

 

 

 

Wiring

 

Check the wire connections; if loose, repair or

 

 

 

 

 

replace the terminal. If the wires are discon-

 

 

 

 

 

nected, refer to wiring diagram for identification,

 

 

 

 

 

and replace the wires. Check the wire connections;

 

 

 

 

 

If not according to the wiring diagram, correct

 

 

 

 

 

the connections.

 

 

 

 

 

 

 

 

 

 

Rotary Swtich

 

Check for continuity,

refer to the

 

 

 

 

for terminal identification. Replace the switch if

 

 

 

 

 

the circuit is open.

 

 

 

 

 

 

 

 

 

 

Thermostat

 

Check the position of knob. If not at the coldest

 

 

 

 

 

setting, advance the knob to this setting and

 

 

 

 

 

restart the unit.

 

 

 

 

 

 

 

 

 

 

 

Check the continuity of the thermostat. Replace

 

 

 

 

 

the thermostat if the circuit is open.

 

 

 

 

 

 

 

 

 

 

Capacitor (discharge

 

Check the capacitor.

 

 

 

capacitor before

 

Replace if not within ±10% of manufacturer’s

 

 

 

servicing.)

 

rating, replace if shorted, open, or damaged.

 

 

 

 

 

 

 

 

 

 

Compressor

 

Check the compressor for open circuit or

 

 

 

 

 

ground. If open or grounded, replace the

 

 

 

 

 

compressor.

 

 

 

 

 

 

 

 

 

 

Overload

 

Check the compressor overload if externally mounted.

 

 

 

 

 

Replace if open. (If the compressor temperature is

 

 

 

 

 

high, remove the overload, cool, and retest.)

 

 

 

 

 

 

 

Compressor cycles on

Voltage

 

Check the voltage. See the limits on the

 

overload.

 

 

preceding page. If voltage is not within these limits,

 

 

 

 

 

call an electrician.

 

 

 

 

 

 

 

 

 

Overload

 

Check overload, if externally mounted.

 

 

 

 

 

Replace if open. (If the compressor temperature

 

 

 

 

 

is high, remove the overload, cool, and retest.)

 

 

 

 

 

 

 

 

 

 

 

—17

Image 17
Contents Room Air Conditioner Service and Parts Manual ZStar Contents Preface FeaturesSpecifications Insulation Resistance Test Safety PrecautionsLocations of Controls Mechanical Parts Disassembly InstructionsFront Grille CabinetORIFICE, Turbo FAN and FAN AIR Handling PartsAIR Guide Upper Overload Protector Electrical PartsAIR Guide Compressor Rotary SwitchCapacitor ThermostatCondenser Power CordRefrigerant Cycle Capillary Tube EVAPORATOR/CONDENSERPulling Vacuum Outside Dimensions unit mm Troubleshooting GuideCondenser Coils Piping SystemUnit is running but cooling is ineffective Troubleshooting GuideFails to Start Room AIR Conditioner Voltage Limits Check for continuity Refer to Complaint Cause Remedy Model ZQ05B10,ZQ07B10 Circuit DiagramExploded View ZQ05B10 Service Parts ListZQ07B10 Memo Use Factory Certified Parts