Friedrich ZQ07B10, ZQ05B10 manual Evaporator/Condenser, Capillary Tube

Page 10

2.4.2 EVAPORATOR/CONDENSER

1.Remove the cabinet.

2.Discharge the refrigerant by using a refrigerant recovery system.

3.Remove the air guide upper. (Refer to Section 2.2.1)

4.After discharging the refrigerant completely, unbraze the interconnecting tube at the proper connections.

5.Remove the proper coil.

6.Re-install by referring to the procedures above.

2.4.3 CAPILLARY TUBE

1.Remove the cabinet.

2.Discharge the refrigerant by using a refrigerant recovery system.

3.Remove the air guide upper. (Refer to Section 2.2.1)

4.After discharging the refrigerant completely, unbraze the interconnecting tube of the capillary tube.

5.Remove the capillary tube.

6.Re-install by referring to the procedures above.

NOTES

Replacement of the refrigeration cycle.

1.When replacing the refrigeration cycle, be sure to discharge the refrigerant by using a refrigerant recovery system.

2.After discharging the unit completely, remove the desired components, and unbraze the pinch-off tubes.

3.Solder service valves into the pinch-off tube ports, leaving the valves open.

4.Solder the pinch-off tubes with service valves.

5.After completing the above procedures, the valve must be closed and left in place on the system for any subsequent procedures.

6.Evacuate as follows:

6-1. Connect the vacuum pump, as illustrated in figure 21A.

6-2. Start the vacuum pump. Slowly open manifold valves A and B with two full turns counter- clockwise and leave the valves closed.

The vacuum pump is now pulling through valves A and B up to valve C by means of manifold and the entire system.

CAUTION : If high vacuum equipment is used, just crack valves A and B for a few minutes, then open slowly with the two full turns counterclock-

wise. This will keep oil from foaming and being drawn into the vacuum pump.

6-3. Operate the vacuum pump for 20 to 30 min- utes, until 600 micron vacuum is obtained. Close valves A and B and observe vacuum gauge for a few minutes.

A rise in pressure would indicate a possible leak or moisture remaining in the system. With valves A and B closed, stop the vacuum pump.

6-4. Remove the hose from the vacuum pump and place it on the charging cylinder. See figure 21B. Open valve C.

Discharge the line at the manifold connection. 6-5. The system is now ready for final charging.

7.Recharge as follows:

7-1. Refrigeration cycle systems are charged from the high-side. If the total charge cannot be put in the high-side, the balance will be put in the suction line through the access valve which is installed as the system is opened.

7-2. Connect the charging cylinder as shown in fig- ure 21B. With valve C open, discharge the hose at the manifold connection.

7-3. Open valve A and allow the proper charge to enter the system. Valve B is still closed.

7-4. If more charge is required, the high-side will not take it. Close valve A.

7-5. With the unit running, open valve B and add the balance of the charge.

a.Do not add the liquid refrigerant to the low- side.

b.Watch the low-side gauge, allow pressure to rise to 30 lbs.

c.Turn off valve B and allow the pressure to drop.

d.Repeat steps b. and c. until the balance of the charge is in the system.

7-6. When the unit is operating correctly, use the pinch-off tool with the unit still running and clamp on the pinch-off tube. Using a tube cut- ter, cut the pinch-off tube about 2 inches from the pinch-off . Use sil-fos solder and solder the pinch-off tube closed. Turn off the unit, allow unit to sit for a while and then test the leakage of the pinch-off connection.

— 10—

Image 10
Contents Room Air Conditioner Service and Parts Manual ZStar Contents Specifications FeaturesPreface Locations of Controls Safety PrecautionsInsulation Resistance Test Front Grille Disassembly InstructionsMechanical Parts CabinetAIR Guide Upper AIR Handling PartsORIFICE, Turbo FAN and FAN AIR Guide Electrical PartsOverload Protector Capacitor Rotary SwitchCompressor ThermostatRefrigerant Cycle Power CordCondenser EVAPORATOR/CONDENSER Capillary TubePulling Vacuum Troubleshooting Guide Outside Dimensions unit mmPiping System Condenser CoilsTroubleshooting Guide Unit is running but cooling is ineffectiveFails to Start Room AIR Conditioner Voltage Limits Check for continuity Refer to Complaint Cause Remedy Circuit Diagram Model ZQ05B10,ZQ07B10Exploded View Service Parts List ZQ05B10ZQ07B10 Memo Use Factory Certified Parts