1.3 LOCATIONS OF CONTROLS
  | Operation | Off  | : Turns air conditioner off.  | |
  | 
  | 
  | ||
  | 
  | Off  | Hi Fan  | : High speed fan operation without  | 
  | 
  | 
  | cooling.  | |
  | Hi  | Hi  | 
  | |
  | 
  | 
  | ||
  | Fan O  | Cool  | Lo Fan  | : Low speed fan operation without  | 
  | 
  | 
  | ||
Lo  | O  | Lo  | 
  | cooling.  | 
Fan  | Cool  | 
  | 
  | |
  | 
  | 
  | Hi Cool  | : Cooling with high speed fan  | 
  | 
  | 
  | 
  | operation.  | 
  | 
  | Mode  | Lo Cool  | : Cooling with low speed fan  | 
  | 
  | 
  | ||
  | 
  | 
  | 
  | operation.  | 
  | 
  | 
  | 
  | |
  | Thermostat | 
  | 
  | |
  | 
  | 
  | This automatically controls the temperature of the  | |
  | 
  | 
  | indoor air.  | 
  | 
  | 
  | 
  | Turn the knob so that the arrow points to the  | |
  | 
  | 
  | larger marks for greater cooling. Point the arrow to  | |
  | 
  | 
  | the smaller marks for more moderate cooling.  | |
  | 
  | 
  | (i.e. the higher the number, the greater the  | |
Warmer  | Cooler  | cooling)  | 
  | |
  | Temperature  | 
  | ||
  | 
  | 
  | ||
  | 
  | 
  | 
  | 
  | 
CAUTION : After switching the air conditioner from Cool to Off or Fan, wait at least 3 minutes before switching it back to Cool.
1.4 SAFETY PRECAUTIONS
1.When servicing, set the ROTARY SWITCH to Off and unplug the power cord.
2.Observe the original lead dress.
If a short circuit is found, replace all parts which have been overheated or damaged by the short cir- cuit.
3.After servicing, make an insulation resistance test to prevent the customer from being exposed to shock hazards.
1.5 INSULATION RESISTANCE TEST
1.Unplug the power cord and connect a jumper between 2 pins (black and white).
2.The grounding conductor (green or green and yel- low) is to be open.
3.Measure the resistance value with an ohm meter between the jumpered lead and each exposed metallic part on the equipment at all position [except Off] of the ROTARY SWITCH.
4.The value should be over 1 MΩ .