Friedrich 000 BTU'S, 9 service manual External Static Pressure

Page 22

External Static Pressure

External Static Pressure can best be defined as the pressure difference (drop) between the Positive Pressure (discharge) and the Negative Pressure (intake) sides of the blower. External Static Pressure is developed by the blower as a result of resistance to airflow (Friction) in the air distribution system EXTERNAL to the VERT-I-PAK cabinet.

Resistance applied externally to the VERT-I-PAK (i.e. duct work, coils, filters, etc.) on either the supply or return side of the system causes an INCREASE in External Static Pressure accompanied by a REDUCTION in airflow.

External Static Pressure is affected by two (2) factors.

1.Resistance to Airflow as already explained.

2.Blower Speed. Changing to a higher or lower blower speed will raise or lower the External Static Pressure accordingly.

These affects must be understood and taken into consideration when checking External Static Pressure/Airflow to insure that the system is operating within design conditions.

Operating a system with insufficient or excessive airflow can cause a variety of different operating problems. Among these are reduced capacity, freezing evaporator coils, premature compressor and/or heating component failures. etc.

System airflow should always be verified upon completion of a new installation, or before a change-out, compressor replacement, or in the case of heat strip failure to insure that the failure was not caused by improper airflow.

Checking External Static Pressure

The airflow through the unit can be determined by measuring the external static pressure of the system, and consulting the blower performance data for the specific VERT-I-PAK.

1. Set up to measure external static pressure at the

supply and return air.

2. Ensure the coil and filter are clean, and that all the

registers are open.

7.Recheck the external static pressure with the new speed. External static pressure (and actual airflow) will have changed to a higher or lower value depending upon speed selected. Recheck the actual airflow (at this "new" static pressure) to confirm speed selection.

8.Repeat steps 8 and 9 (if necessary) until proper airflow has been obtained.

EXAMPLE: Airflow requirements are calculated as follows: (Having a wet coil creates additional resistance to airflow. This addit ional resistance must be taken into consideration to obtain accurate airflow information.

1 ½ TON SYSTEM ( 18,000 Btu)

Operating on high speed @ 230 volts with dry coil measured external static pressure .20

Air Flow = 500 CFM

In the same SYSTEM used in the previous example but having a WET coil you must use a correction factor of

.94 (i.e. 500 x .94=470 CFM) to allow for the resistance (internal) of the condensate on the coil.

It is important to use the proper procedure to check external Static Pressure and determine actual airflow. Since in the case of the VERT-I-PAK, the condensate will cause a reduction in measured External Static Pressure for the given airflow.

It is also important to remember that when dealing with VERT-l-PAK units that the measured External Static Pressure increases as the resistance is added externally to the cabinet. Example: duct work, filters, grilles.

Checking Approximate Airflow

If an inclined manometer or Magnehelic gauge is not available to check the External Static Pressure, or the blower performance data is unavailable for your unit, approximate air flow call be calculated by measuring the temperature rise, then using tile following criteria.

KILOWATTS x 3413

3. Determine the external static pressure with the

Temp Rise x 1.08

= CFM

blower operating.

4. Refer to the Air Flow Data for your VERT-I-PAK

system to find the actual airflow for factory-selected

fan speeds.

5. If the actual airflow is either too high or too low, the

blower speed will need to be changed to appropriate

setting or the ductwork will need to be reassessed

and corrections made as required.

6. Select a speed, which most closely provides the

required airflow for the system.

Electric Heat Strips

The approximate CFM actually being delivered can be calculated by using the following formula:

DO NOT simply use the Kilowatt Rating of the heater (i.e. 2.5, 3.4, 5.0) as this will result in a less-than-correct airflow calculation. Kilowatts may be calculated by multiplying the measured voltage to the unit (heater) times the measured current draw of all heaters (ONLY) in operation to obtain watts. Kilowatts are than obtained by dividing by 1000.

20

Image 22
Contents Single Package Vertical Air Conditioning System Technical Support Contact Information Table of Contents Important Safety Information Your safety and the safety of others are very importantRefrigeration System Hazards Introduction Property Damage HazardsSerial Number Identification Guide Chassis Specifications Electric Heat DataExtended Cooling Performance VEA Extended Cooling PerformanceVEA/VHA09-24 VEA Extended Cooling Performance Electrical Requirements Electric Shock HazardRemote Thermostat and Low Voltage Control Connections RT5 Two speed fan RT4 One speed fanThermostat Connections Electronic Control Board Features Quiet Start/StopElectronic Control Configuration Diagnostics Electronic control error codes diagnostics and test modeTest Mode Power On and Off Features on the Electronic Control Cool mode control features for cool with electric heat units Compressor operation depends on t-stat settings Component description / A-Series specifications VERT-I-PAK Single Packaged Vertical AIR ConditionersExternal Static Pressure Indoor Airflow Data Capacitor Check with Capacitor Analyzer Components TestingCapacitors Capacitor ConnectionsHeater Elements and Limit SWITCHES’ Specifications Components TestingDrain PAN Valve Refrigeration Assembly Refrigeration Sequence of OperationService CUT/SEVER HazardEquipment Must be Capable Sealed Refrigeration System RepairsEquipment Required Risk of Electric ShockBurn Hazard Method Of Charging / RepairsFreeze Hazard Undercharged Refrigerant Systems Overcharged Refrigerant SystemsRestricted Refrigerant System Check Valve Hermetic Components CheckMetering Device Capillary Tube SystemsReversing Valve DESCRIPTION/OPERATION Testing the Coil Checking the Reversing ValveFire Hazard Procedure For Changing Reversing ValveTouch Test in Heating/Cooling Cycle Explosion HazardCompressor Checks Ground Test Single Phase Resistance TestChecking Compressor Efficiency Recommended procedure for compressor replacement Compressor ReplacementHigh Temperatures Rotary Compressor Special Troubleshooting and Service Blower Wheel / Housing / Condenser FAN / Shroud Routine MaintenanceCoils and Base PAN Excessive Weight Hazard AIR FilterFront Cover Routine MaintenanceSleeve / Drain Condensate Disposal SystemElectrical Troubleshooting Chart Cooling 9K BTU, 12K BTU, & 18K BTUElectrical Troubleshooting Chart Cooling 24K BTU Circuit Breakers areElectrical Troubleshooting Chart Heat Pump Heat Pump ModeTroubleshooting Chart Cooling Troubleshooting Chart HeatingVEA 09/12/18 with 2.5 KW, 3.4 KW or 5KW Electric HeatVHA 09/12/18 with 2.5 KW, 3.4 KW or 5KW Cool with Electric Heat Heat Pump with Electric Heat Cool with Electric Heat Heat Pump with Electric Heat Outdoor Coil Return Air Indoor Coil Wall Plenum AccessoriesDrain PAN Friedrich Air Conditioning Company Technical Support Contact Information Friedrich AIR Conditioning CO