Friedrich 000 BTU'S Routine Maintenance, AIR Filter, Coils and Base PAN Excessive Weight Hazard

Page 40

ROUTINE MAINTENANCE

WARNING

ELECTRIC SHOCK HAZARD

Turn off electric power before inspections, maintenances, or service.

Extreme care must be used, if it becomes necessary to work on equipment with power applied.

Failure to do so could result in serious injury or death.

NOTICE

Units are to be inspected and serviced by qualified service personnel only. Use proper protection on surrounding property. Failure to follow this notice could result in moderate or serious property damage.

AIR FILTER

Clean the unit air intake filter at least every 300 to 350 hours of operation. Clean the filters with a mild detergent in warm water and allow to dry thoroughly before reinstalling.

COILS AND BASE PAN

WARNING

EXCESSIVE WEIGHT HAZARD

Use two people to lift or carry the unit, and wear proper protective clothing.

Failure to do so may result in personal injury.

NOTICE

Do not use a caustic coil cleaning agent on coils or base pan. Use a biodegradable cleaning agent and degreaser, to prevent damage to the coil and/or base pan.

WARNING

CUT/SEVER HAZARD

Be careful with the sharp edges and corners.

Wear protective clothing and gloves, etc.

Failure to do so could result in serious injury.

The indoor coil (evaporator coil), the outdoor coil (condenser coil) and base pan should be inspected periodically (yearly or bi-yearly) and cleaned of all debris (lint, dirt, leaves, paper, etc.). Clean the coils and base pan with a soft brush and compressed air or vacuum. If using a pressure washer, be careful not to bend the aluminium fin pack. Use a sweeping up and down motion in the direction of the vertical aluminum fin pack when pressure cleaning coils. Cover all electrical components to protect them from water or spray. Allow the unit to dry thoroughly before reinstalling it in the sleeve.

BLOWER WHEEL / HOUSING / CONDENSER FAN / SHROUD

Inspect the indoor blower housing, evaporator blade, condenser fan blade and condenser shroud periodically (yearly or bi-yearly) and clean of all debris (lint, dirt, mold, fungus, etc.). Clean the blower housing area and blower wheel with an antibacterial / antifungal cleaner. Use a biodegradable cleaning agent and degreaser on condenser fan and condenser shroud. Use warm or cold water when rinsing these items. Allow all items to dry thoroughly before reinstalling them.

ELECTRONIC / ELECTRICAL / MECHANICAL

Periodically (at least yearly or bi-yearly): inspect all control components: electronic, electrical and mechanical, as well as the power supply. Use proper testing instruments (voltmeter, ohmmeter, ammeter, wattmeter, etc.) to perform elec- trical tests. Use an air conditioning or refrigeration thermometer to check room, outdoor and coil operating tempera- tures. Use a sling psychrometer to measure wet bulb temperatures indoors and outdoors.

Inspect the surrounding area (inside and outside) to ensure that the unit’s clearances have not been compromised or altered.

38

Image 40
Contents Single Package Vertical Air Conditioning System Technical Support Contact Information Table of Contents Important Safety Information Your safety and the safety of others are very importantRefrigeration System Hazards Introduction Property Damage HazardsSerial Number Identification Guide Chassis Specifications Electric Heat DataExtended Cooling Performance VEA Extended Cooling PerformanceVEA/VHA09-24 VEA Extended Cooling Performance Electrical Requirements Electric Shock HazardRemote Thermostat and Low Voltage Control Connections RT5 Two speed fan RT4 One speed fanThermostat Connections Electronic Control Board Features Quiet Start/StopElectronic Control Configuration Diagnostics Electronic control error codes diagnostics and test modeTest Mode Power On and Off Features on the Electronic Control Cool mode control features for cool with electric heat units Compressor operation depends on t-stat settings Component description / A-Series specifications VERT-I-PAK Single Packaged Vertical AIR ConditionersExternal Static Pressure Indoor Airflow Data Components Testing CapacitorsCapacitor Check with Capacitor Analyzer Capacitor ConnectionsHeater Elements and Limit SWITCHES’ Specifications Components TestingDrain PAN Valve Refrigeration Assembly Refrigeration Sequence of OperationService CUT/SEVER HazardSealed Refrigeration System Repairs Equipment RequiredEquipment Must be Capable Risk of Electric ShockBurn Hazard Method Of Charging / RepairsFreeze Hazard Undercharged Refrigerant Systems Overcharged Refrigerant SystemsRestricted Refrigerant System Hermetic Components Check Metering DeviceCheck Valve Capillary Tube SystemsReversing Valve DESCRIPTION/OPERATION Testing the Coil Checking the Reversing ValveProcedure For Changing Reversing Valve Touch Test in Heating/Cooling CycleFire Hazard Explosion HazardCompressor Checks Ground Test Single Phase Resistance TestChecking Compressor Efficiency Recommended procedure for compressor replacement Compressor ReplacementHigh Temperatures Rotary Compressor Special Troubleshooting and Service Routine Maintenance Coils and Base PAN Excessive Weight HazardBlower Wheel / Housing / Condenser FAN / Shroud AIR FilterRoutine Maintenance Sleeve / DrainFront Cover Condensate Disposal SystemElectrical Troubleshooting Chart Cooling 9K BTU, 12K BTU, & 18K BTUElectrical Troubleshooting Chart Cooling 24K BTU Circuit Breakers areElectrical Troubleshooting Chart Heat Pump Heat Pump ModeTroubleshooting Chart Cooling Troubleshooting Chart HeatingVEA 09/12/18 with 2.5 KW, 3.4 KW or 5KW Electric HeatVHA 09/12/18 with 2.5 KW, 3.4 KW or 5KW Cool with Electric Heat Heat Pump with Electric Heat Cool with Electric Heat Heat Pump with Electric Heat Outdoor Coil Return Air Indoor Coil Wall Plenum AccessoriesDrain PAN Friedrich Air Conditioning Company Technical Support Contact Information Friedrich AIR Conditioning CO