Friedrich 9, 000 BTU'S Single Phase Resistance Test, Ground Test, Checking Compressor Efficiency

Page 37

Single Phase Resistance Test

WARNING

ELECTRIC SHOCK HAZARD

Turn off electric power before service or installation. Extreme care must be used, if it becomes necessary to work on equipment with power applied.

Failure to do so could result in serious injury or death.

Remove the leads from the compressor terminals and set the ohmmeter on the lowest scale (R x 1).

Touch the leads of the ohmmeter from terminals common to start (“C” to “S”). Next, touch the leads of the ohmmeter from terminals common to run (“C” to “R”).

Add values “C” to “S” and “C” to “R” together and check resistance from start to run terminals (“S” to “R”). Resistance “S” to “R” should equal the total of “C” to “S” and “C” to “R.”

In a single phase PSC compressor motor, the highest value will be from the start to the run connections (“S” to “R”). The next highest resistance is from the start to the common connections (“S” to “C”). The lowest resistance is from the run to common. (“C” to “R”) Before replacing a compressor, check to be sure it is defective.

GROUND TEST

Use an ohmmeter set on its highest scale. Touch one lead to the compressor body (clean point of contact as a good connection is a must) and the other probe in turn to each compressor terminal. If a reading is obtained the compressor is grounded and must be replaced.

Check the complete electrical system to the compressor and compressor internal electrical system, check to be certain that compressor is not out on internal overload.

Complete evaluation of the system must be made whenever you suspect the compressor is defective. If the compressor has been operating for sometime, a careful examination must be made to determine why the compressor failed.

Many compressor failures are caused by the following conditions:

1.Improper air flow over the evaporator.

2.Overcharged refrigerant system causing liquid to be returned to the compressor.

3.Restricted refrigerant system.

4.Lack of lubrication.

5.Liquid refrigerant returning to compressor causing oil to be washed out of bearings.

6.Noncondensables such as air and moisture in the system. Moisture is extremely destructive to a refrigerant system.

7.Capacitor test (see page 21).

CHECKING COMPRESSOR EFFICIENCY

The reason for compressor inefficiency is normally due to broken or damaged suction and/or discharge valves, reducing the ability of the compressor to pump refrigerant gas.

This condition can be checked as follows:

1.Install a piercing valve on the suction and discharge or liquid process tube.

2.Attach gauges to the high and low sides of the system.

3.Start the system and run a “cooling or heating perfor- mance test.” If test shows:

A.Below normal high side pressure

B.Above normal low side pressure

C.Low temperature difference across coil

The compressor valves are faulty - replace the compressor.

35

Image 37
Contents Single Package Vertical Air Conditioning System Technical Support Contact Information Table of Contents Your safety and the safety of others are very important Important Safety InformationRefrigeration System Hazards Property Damage Hazards IntroductionSerial Number Identification Guide Electric Heat Data Chassis SpecificationsVEA Extended Cooling Performance Extended Cooling PerformanceVEA/VHA09-24 VEA Extended Cooling Performance Electric Shock Hazard Electrical RequirementsRT5 Two speed fan RT4 One speed fan Remote Thermostat and Low Voltage Control ConnectionsThermostat Connections Quiet Start/Stop Electronic Control Board FeaturesElectronic Control Configuration Diagnostics Electronic control error codes diagnostics and test modeTest Mode Power On and Off Features on the Electronic Control Cool mode control features for cool with electric heat units Compressor operation depends on t-stat settings VERT-I-PAK Single Packaged Vertical AIR Conditioners Component description / A-Series specificationsExternal Static Pressure Indoor Airflow Data Capacitors Components TestingCapacitor Check with Capacitor Analyzer Capacitor ConnectionsHeater Elements and Limit SWITCHES’ Specifications Components TestingDrain PAN Valve Refrigeration Sequence of Operation Refrigeration AssemblyCUT/SEVER Hazard ServiceEquipment Required Sealed Refrigeration System RepairsEquipment Must be Capable Risk of Electric ShockBurn Hazard Method Of Charging / RepairsFreeze Hazard Overcharged Refrigerant Systems Undercharged Refrigerant SystemsRestricted Refrigerant System Metering Device Hermetic Components CheckCheck Valve Capillary Tube SystemsReversing Valve DESCRIPTION/OPERATION Checking the Reversing Valve Testing the CoilTouch Test in Heating/Cooling Cycle Procedure For Changing Reversing ValveFire Hazard Explosion HazardCompressor Checks Ground Test Single Phase Resistance TestChecking Compressor Efficiency Recommended procedure for compressor replacement Compressor ReplacementHigh Temperatures Rotary Compressor Special Troubleshooting and Service Coils and Base PAN Excessive Weight Hazard Routine MaintenanceBlower Wheel / Housing / Condenser FAN / Shroud AIR FilterSleeve / Drain Routine MaintenanceFront Cover Condensate Disposal System9K BTU, 12K BTU, & 18K BTU Electrical Troubleshooting Chart CoolingCircuit Breakers are Electrical Troubleshooting Chart Cooling 24K BTUHeat Pump Mode Electrical Troubleshooting Chart Heat PumpTroubleshooting Chart Heating Troubleshooting Chart CoolingElectric Heat VEA 09/12/18 with 2.5 KW, 3.4 KW or 5KWVHA 09/12/18 with 2.5 KW, 3.4 KW or 5KW Cool with Electric Heat Heat Pump with Electric Heat Cool with Electric Heat Heat Pump with Electric Heat Outdoor Coil Return Air Indoor Coil Wall Plenum AccessoriesDrain PAN Friedrich Air Conditioning Company Technical Support Contact Information Friedrich AIR Conditioning CO