TESTING THE COIL
WARNING
ELECTRIC SHOCK HAZARD
Unplug and/or disconnect all electrical power to the unit before performing inspections, maintenances or service.
Failure to do so could result in electric shock, serious injury or death.
The solenoid coil is an electromagnetic type coil mounted on the reversing valve and is energized during the operation of the compressor in the heating cycle.
1.Turn off high voltage electrical power to unit.
2.Unplug line voltage lead from reversing valve coil.
3.Check for electrical continuity through the coil. If you do not have continuity replace the coil.
4.Check from each lead of coil to the copper liquid line as it leaves the unit or the ground lug. There should be no continuity between either of the coil leads and ground; if there is, coil is grounded and must be replaced.
5.If coil tests okay, reconnect the electrical leads.
6.Make sure coil has been assembled correctly.
NOTE: Do not start unit with solenoid coil removed from valve, or do not remove coil after unit is in operation. This will cause the coil to burn out.
CHECKING THE REVERSING VALVE
NOTE: You must have normal operating pressures before the reversing valve can shift.
WARNING
HIGH PRESSURE HAZARD
Sealed Refrigeration System contains refrigerant and oil under high pressure.
Proper safety procedures must be followed, and proper protective clothing must be worn when working with refrigerants.
Failure to follow these procedures could result in serious injury or death.
Check the operation of the valve by starting the system and switching the operation from “Cooling” to “Heating” and then back to “Cooling”. Do not hammer on valve.
Occasionally, the reversing valve may stick in the heating or cooling position or in the
When sluggish or stuck in the
Should the valve fail to shift from coooling to heating, block the air flow through the outdoor coil and allow the discharge
pressure to build in the system. Then switch the system from heating to cooling.
If the valve is stuck in the heating position, block the air flow through the indoor coil and allow discharge pressure to build in the system. Then switch the system from heating to cooling.
Should the valve fail to shift in either position after increasing the discharge pressure, replace the valve.
Dented or damaged valve body or capillary tubes can prevent the main slide in the valve body from shifting.
If you determing this is the problem, replace the reversing valve.
After all of the previous inspections and checks have been made and determined correct, then perform the “Touch Test” on the reversing valve.
Reversing Valve in Heating Mode
Reversing Valve in Cooling Mode
32