Friedrich 000 BTU'S, 9 service manual Electronic Control Configuration

Page 16

Electronic Control Configuration

The adjustable control dip switches are located at the lower left hand portion of the digital Smart Center. The inputs are only visible and accessible with the front cover removed from the Unit.

Factory Dip Switch Configuration

O

1

2

3

4

5

6

7

8

 

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dip Switch Setting

Switches 1-4 ON

Switch 5-7 OFF

Switch 8 ON

Room Freeze Protection – Switch 6

Units are shipped from the factory with the room freeze protec- tion disabled. Room Freeze Protection can be switched on at the owner’s preference by moving Dip Switch 6 to ‘ON’. This feature will monitor the indoor room conditions and in the event that the room falls below 40°F the unit will cycle on high fan with the electric heater. This occurs regardless of mode.

Emergency Heat Override – Switch 7

Units are shipped from the factory with the room emergency heat override disabled. In the unlikely event of a compressor failure a heat pump unit may be switched to operate in only the electric heat mode until repairs can be made, by moving Dip Switch 7 to ‘ON’.

Discharge Air Sensor Override – Switch 8

This switch MUST remain in the “ON” position for Vert-I-Pak models, since they do not use a discharge air sensor. If the switch is positioned in the “OFF” position on these models it will result in the erroneous display Error Code 14 indicating that the Discharge air temperature sensor is open or shorted.

Note: In order for the control to recognize “Dip” switch setting changes, the unit must be disconnected from power supply when making any configuration changes.

Electronic Control Error Code Diagnostics and Test Mode

Error Code Diagnostics

The VPAK electronic control continuously monitors the Vert-I-Pak unit operation and will store error codes if certain conditions are witnessed. In some cases the unit may take action and shut the unit off until conditions are corrected.

To access the error code menu press the ‘HEAT’ and ‘HIGH

FAN’ buttons simultaneously for three seconds. If error codes are present they will be displayed. If multiple codes exist you can toggle between error codes using the temp up ▲ button. To clear all codes press the temp down ▼ button for three seconds while in the error code mode. To exit without losing codes press the ‘Low Fan’ button.

Button Location for Vert-I-Pak Models

With the remote thermostat escutcheon installed, the button locations to access the diagnostics mode can be located as shown below.

Cool

 

 

High fan

 

Heat

Temp

Power

Temp

 

Fan only

Low fan

*Heat and high fan - access error codes

*Temp up ▲ and temp down ▼ - toggle between error codes

*Low fan - exit error code mode without losing stored error codes.

*Temp down ▼ - clears all error codes

NOTE: Hold buttons down for three seconds.

14

Image 16
Contents Single Package Vertical Air Conditioning System Technical Support Contact Information Table of Contents Important Safety Information Your safety and the safety of others are very importantRefrigeration System Hazards Introduction Property Damage HazardsSerial Number Identification Guide Chassis Specifications Electric Heat DataExtended Cooling Performance VEA Extended Cooling PerformanceVEA/VHA09-24 VEA Extended Cooling Performance Electrical Requirements Electric Shock HazardRemote Thermostat and Low Voltage Control Connections RT5 Two speed fan RT4 One speed fanThermostat Connections Electronic Control Board Features Quiet Start/StopElectronic Control Configuration Diagnostics Electronic control error codes diagnostics and test modeTest Mode Power On and Off Features on the Electronic Control Cool mode control features for cool with electric heat units Compressor operation depends on t-stat settings Component description / A-Series specifications VERT-I-PAK Single Packaged Vertical AIR ConditionersExternal Static Pressure Indoor Airflow Data Components Testing CapacitorsCapacitor Check with Capacitor Analyzer Capacitor ConnectionsHeater Elements and Limit SWITCHES’ Specifications Components TestingDrain PAN Valve Refrigeration Assembly Refrigeration Sequence of OperationService CUT/SEVER HazardSealed Refrigeration System Repairs Equipment RequiredEquipment Must be Capable Risk of Electric ShockBurn Hazard Method Of Charging / RepairsFreeze Hazard Undercharged Refrigerant Systems Overcharged Refrigerant SystemsRestricted Refrigerant System Hermetic Components Check Metering DeviceCheck Valve Capillary Tube SystemsReversing Valve DESCRIPTION/OPERATION Testing the Coil Checking the Reversing ValveProcedure For Changing Reversing Valve Touch Test in Heating/Cooling CycleFire Hazard Explosion HazardCompressor Checks Ground Test Single Phase Resistance TestChecking Compressor Efficiency Recommended procedure for compressor replacement Compressor ReplacementHigh Temperatures Rotary Compressor Special Troubleshooting and Service Routine Maintenance Coils and Base PAN Excessive Weight HazardBlower Wheel / Housing / Condenser FAN / Shroud AIR FilterRoutine Maintenance Sleeve / DrainFront Cover Condensate Disposal SystemElectrical Troubleshooting Chart Cooling 9K BTU, 12K BTU, & 18K BTUElectrical Troubleshooting Chart Cooling 24K BTU Circuit Breakers areElectrical Troubleshooting Chart Heat Pump Heat Pump ModeTroubleshooting Chart Cooling Troubleshooting Chart HeatingVEA 09/12/18 with 2.5 KW, 3.4 KW or 5KW Electric HeatVHA 09/12/18 with 2.5 KW, 3.4 KW or 5KW Cool with Electric Heat Heat Pump with Electric Heat Cool with Electric Heat Heat Pump with Electric Heat Outdoor Coil Return Air Indoor Coil Wall Plenum AccessoriesDrain PAN Friedrich Air Conditioning Company Technical Support Contact Information Friedrich AIR Conditioning CO