Friedrich 9, 000 BTU'S service manual Indoor Airflow Data

Page 23

EXAMPLE: Measured voltage to unit (heaters) is 230 volts. Measured Current Draw of strip heaters is 11.0 amps.

230 x 11.0 = 2530 2530/1000 = 2.53 Kilowatts 2.53 x 3413 = 8635

Supply Air

 

95 F

Return Air

 

°

 

75 F

Temperature Rise

 

°

20°

20 x 1.08 = 21.6

 

 

863521.6 = 400 CFM

Indoor Airflow Data

The Vert-I-Pak A series units must be installed with a free return air configuration. The table below lists the indoor airflow at corresponding static pressures. All units are rarted at low speed.

The Vert-I-Pak units are designed for either single speed or two fan speed operation. For single speed operation refer to the airflow table below and select the most appropriate CFM based on the ESP level. Connect the fan output from the thermostat to the unit on either the GL terminal for low speed or to the GH terminal for high speed operation.

For thermostats with two-speed fan outputs connect the low speed output to the unit GL terminal and the high speed output to the GH terminal.

Determining the Indoor CFM: Chart A – CFM

 

 

 

Model

 

 

 

VEA09/VHA09

VEA12/VHA12

VEA18/VHA18

ESP (")

Low

High

Low

High

Low

High

.00"

340

385

420

470

430

480

.10"

300

340

350 *

420 **

400

450

.20"

230

280

290

350

340

400

.30”

140

190

250

300

290

330

Highlighted values indicate rated performance point.

Rated performance for

*VEA12

Rated Performance for

**VHA12

 

 

Model

 

VEA24/VHA24

ESP (")

Low

 

High

.00"

690

 

740

.10"

610

 

700

.20"

560

 

640

.30"

510

 

580

.40"

450

 

520

Highlighted values indicate rated performance point.

Correct CFM (if needed):

Chart B – Correction Multipliers

Ductwork Preparation

Duct ESP:

To determine your system's indoor external static pressure (ESP, in inches of water) use a duct calculator (as provided by your duct supplier). Include all flex duct transitions and discharge grille(s). If flex duct is used, be sure all the slack is pulled out of the flex duct. Flex duct ESP can increase considerably when not fully extended. DO NOT EXCEED a total of .30 ESP, as this is the MAXIMUM design limit for the VERT-I-PAK A-Series unit.

Ductwork Preparation

Pull the flex duct tight. Extra flex duct slack can greatly increase static pressure

IMPORTANT: FLEX DUCT CAN COLLAPSE AND CAUSE AIRFLOW RESTRICTIONS. DO NOT USE FLEX DUCT FOR: 90 DEGREE BENDS, OR UNSUPPORTED RUNS OF 5 FT. OR MORE.

Explanation of charts

Chart A is the nominal dry coil VERT-I-PAK CFMs. Chart B is the correction factors beyond nominal conditions.

Fresh Air Door

The Fresh Air Door is an “intake” system. The fresh air door opened via a slide on the front of the chassis located just above the indoor coil. Move the slide left to open and right to close the fresh air door. The system is capable of up to 60 CFM of fresh air @ ~.3” H20 internal static pressure.

21

Image 23
Contents Single Package Vertical Air Conditioning System Technical Support Contact Information Table of Contents Your safety and the safety of others are very important Important Safety InformationRefrigeration System Hazards Property Damage Hazards IntroductionSerial Number Identification Guide Electric Heat Data Chassis SpecificationsVEA Extended Cooling Performance Extended Cooling PerformanceVEA/VHA09-24 VEA Extended Cooling Performance Electric Shock Hazard Electrical RequirementsRT5 Two speed fan RT4 One speed fan Remote Thermostat and Low Voltage Control ConnectionsThermostat Connections Quiet Start/Stop Electronic Control Board FeaturesElectronic Control Configuration Test Mode Electronic control error codes diagnostics and test modeDiagnostics Power On and Off Features on the Electronic Control Cool mode control features for cool with electric heat units Compressor operation depends on t-stat settings VERT-I-PAK Single Packaged Vertical AIR Conditioners Component description / A-Series specificationsExternal Static Pressure Indoor Airflow Data Capacitor Connections Components TestingCapacitors Capacitor Check with Capacitor AnalyzerDrain PAN Valve Components TestingHeater Elements and Limit SWITCHES’ Specifications Refrigeration Sequence of Operation Refrigeration AssemblyCUT/SEVER Hazard ServiceRisk of Electric Shock Sealed Refrigeration System RepairsEquipment Required Equipment Must be CapableFreeze Hazard Method Of Charging / RepairsBurn Hazard Overcharged Refrigerant Systems Undercharged Refrigerant SystemsRestricted Refrigerant System Capillary Tube Systems Hermetic Components CheckMetering Device Check ValveReversing Valve DESCRIPTION/OPERATION Checking the Reversing Valve Testing the CoilExplosion Hazard Procedure For Changing Reversing ValveTouch Test in Heating/Cooling Cycle Fire HazardCompressor Checks Checking Compressor Efficiency Single Phase Resistance TestGround Test High Temperatures Compressor ReplacementRecommended procedure for compressor replacement Rotary Compressor Special Troubleshooting and Service AIR Filter Routine MaintenanceCoils and Base PAN Excessive Weight Hazard Blower Wheel / Housing / Condenser FAN / ShroudCondensate Disposal System Routine MaintenanceSleeve / Drain Front Cover9K BTU, 12K BTU, & 18K BTU Electrical Troubleshooting Chart CoolingCircuit Breakers are Electrical Troubleshooting Chart Cooling 24K BTUHeat Pump Mode Electrical Troubleshooting Chart Heat PumpTroubleshooting Chart Heating Troubleshooting Chart CoolingElectric Heat VEA 09/12/18 with 2.5 KW, 3.4 KW or 5KWVHA 09/12/18 with 2.5 KW, 3.4 KW or 5KW Cool with Electric Heat Heat Pump with Electric Heat Cool with Electric Heat Heat Pump with Electric Heat Outdoor Coil Return Air Indoor Coil Drain PAN AccessoriesWall Plenum Friedrich Air Conditioning Company Technical Support Contact Information Friedrich AIR Conditioning CO