Friedrich 9 Touch Test in Heating/Cooling Cycle, Procedure For Changing Reversing Valve

Page 35

Touch Test in Heating/Cooling Cycle

WARNING

BURN HAZARD

Certain unit components operate at temperatures hot enough to cause burns.

Proper safety procedures must be followed, and proper protective clothing must be worn.

Failure to follow these procedures could result in minor to moderate injury.

The only definite indications that the slide is in the mid- position is if all three tubes on the suction side of the valve are hot after a few minutes of running time.

NOTE: A condition other than those illustrated above, and on Page 31, indicate that the reversing valve is not shifting properly. Both tubes shown as hot or cool must be the same corresponding temperature.

Procedure For Changing Reversing Valve

WARNING

HIGH PRESSURE HAZARD

Sealed Refrigeration System contains refrigerant and oil under high pressure.

Proper safety procedures must be followed, and proper protective clothing must be worn when working with refrigerants.

Failure to follow these procedures could result in serious injury or death.

NOTICE

FIRE HAZARD

The use of a torch requires extreme care and proper judgment. Follow all safety recommended precautions and protect surrounding areas with fire proof materials. Have a fire extinguisher readily available. Failure to follow this notice could result in moderate to serious property damage.

1.Install Process Tubes. Recover refrigerant from sealed system. PROPER HANDLING OF RECOVERED REFRIGERANT ACCORDING TO EPA REGULATIONS IS REQUIRED.

2.Remove solenoid coil from reversing valve. If coil is to be reused, protect from heat while changing valve.

3.Unbraze all lines from reversing valve.

4.Clean all excess braze from all tubing so that they will slip into fittings on new valve.

5.Remove solenoid coil from new valve.

6.Protect new valve body from heat while brazing with plastic heat sink (Thermo Trap) or wrap valve body with wet rag.

7.Fit all lines into new valve and braze lines into new valve.

WARNING

EXPLOSION HAZARD

The use of nitrogen requires a pressure regulator. Follow all safety procedures and wear protective safety clothing etc.

Failure to follow proper safety procedures could result in serious injury or death.

8.Pressurize sealed system with a combination of R-22 and nitrogen and check for leaks, using a suitable leak detector. Recover refrigerant per EPA guidelines.

9.Once the sealed system is leak free, install solenoid coil on new valve and charge the sealed system by weighing in the proper amount and type of refrigerant as shown on rating plate. Crimp the process tubes and solder the ends shut. Do not leave Schrader or piercing valves in the sealed system.

NOTE: When brazing a reversing valve into the system, it is of extreme importance that the temperature of the valve does not exceed 250°F at any time.

Wrap the reversing valve with a large rag saturated with water. “Re-wet” the rag and thoroughly cool the valve after each brazing operation of the four joints involved.

The wet rag around the reversing valve will eliminate conduction of heat to the valve body when brazing the line connection.

33

Image 35
Contents Single Package Vertical Air Conditioning System Technical Support Contact Information Table of Contents Your safety and the safety of others are very important Important Safety InformationRefrigeration System Hazards Property Damage Hazards IntroductionSerial Number Identification Guide Electric Heat Data Chassis SpecificationsVEA Extended Cooling Performance Extended Cooling PerformanceVEA/VHA09-24 VEA Extended Cooling Performance Electric Shock Hazard Electrical RequirementsRT5 Two speed fan RT4 One speed fan Remote Thermostat and Low Voltage Control ConnectionsThermostat Connections Quiet Start/Stop Electronic Control Board FeaturesElectronic Control Configuration Test Mode Electronic control error codes diagnostics and test modeDiagnostics Power On and Off Features on the Electronic Control Cool mode control features for cool with electric heat units Compressor operation depends on t-stat settings VERT-I-PAK Single Packaged Vertical AIR Conditioners Component description / A-Series specificationsExternal Static Pressure Indoor Airflow Data Capacitor Connections Components TestingCapacitors Capacitor Check with Capacitor AnalyzerDrain PAN Valve Components TestingHeater Elements and Limit SWITCHES’ Specifications Refrigeration Sequence of Operation Refrigeration AssemblyCUT/SEVER Hazard ServiceRisk of Electric Shock Sealed Refrigeration System RepairsEquipment Required Equipment Must be CapableFreeze Hazard Method Of Charging / RepairsBurn Hazard Overcharged Refrigerant Systems Undercharged Refrigerant SystemsRestricted Refrigerant System Capillary Tube Systems Hermetic Components CheckMetering Device Check ValveReversing Valve DESCRIPTION/OPERATION Checking the Reversing Valve Testing the CoilExplosion Hazard Procedure For Changing Reversing ValveTouch Test in Heating/Cooling Cycle Fire HazardCompressor Checks Checking Compressor Efficiency Single Phase Resistance TestGround Test High Temperatures Compressor ReplacementRecommended procedure for compressor replacement Rotary Compressor Special Troubleshooting and Service AIR Filter Routine MaintenanceCoils and Base PAN Excessive Weight Hazard Blower Wheel / Housing / Condenser FAN / ShroudCondensate Disposal System Routine MaintenanceSleeve / Drain Front Cover9K BTU, 12K BTU, & 18K BTU Electrical Troubleshooting Chart CoolingCircuit Breakers are Electrical Troubleshooting Chart Cooling 24K BTUHeat Pump Mode Electrical Troubleshooting Chart Heat PumpTroubleshooting Chart Heating Troubleshooting Chart CoolingElectric Heat VEA 09/12/18 with 2.5 KW, 3.4 KW or 5KWVHA 09/12/18 with 2.5 KW, 3.4 KW or 5KW Cool with Electric Heat Heat Pump with Electric Heat Cool with Electric Heat Heat Pump with Electric Heat Outdoor Coil Return Air Indoor Coil Drain PAN AccessoriesWall Plenum Friedrich Air Conditioning Company Technical Support Contact Information Friedrich AIR Conditioning CO