vpak electronic control board and wall thermostat sequence of operation (Continued)
cool mode control features for cool with electric heat units
Reversing valve:
Always
Compressor operation:
If ambient indoor temperature is above set point temperature depending on
Compressor time delay:
The time delay feature is
240 seconds. Compressor time delay is initiated every time the compressor is “off” due to:
(1)Satisfying the temperature set point,
(2)Changing mode to fan only
(3 )Turning the unit off.
(4)Control is first energized or when power is restored after failure Note: Time delay is disabled during Test Mode.
Indoor coil frost protection (Error Code 07):
While in cool mode: If the indoor coil frost protection sensor reads 30°F for 2 minutes continu- ously, turn off the compressor, but continue fan operation. While the compressor is out and the fan is running: when the indoor coil frost protection sensor reaches 45°F, turn on the compres- sor. However, the compressor must still wait a standard time of 180 to 240 seconds. While 07 flash, heat operation is disabled.
Fan delay:
This is only for fan ‘cycle’ mode and not for fan ‘continuous’ mode. When unit cycles cool- ing ON – start the fan 5 seconds EARLY. When unit cycles cooling OFF – DELAY the fan off for 30 seconds. Note: the fan delay is disabled during Test Mode.
electric heat mode control features for cool with electric heat units
Reversing valve: Always
Compressor operation: Compressor does not operate in this mode.
Electric heat operation: If temp is below set point, depending on
heat.
Fan delay: This is only for fan ‘cycle’ mode and not for fan ‘continuous’ mode. When unit cycles heating ON – start the fan 5 seconds EARLY. When unit cycles heating OFF – DELAY the fan off for 15 seconds. Note: the fan delay is disabled during Test Mode.
17