Recreational Vehicle Installation
4.Allow 13 cm (minimum) of clearance around the unit and allow for a supply of fresh air to the cooling fan. Do not block any of the vents or louvers. The fan pulls air from outside the unit. It blows the air across the internal components, particularly the transformer and heat sinks, then out the side vents.
5.The mounting location should be as close to the batteries as possible. The battery cables can be extended, however each cable must not be over 3.04 m in total length from the inverter to battery terminals. Do not use the RV chassis as a negative conductor.
WARNING: Fire hazard and equipment damage
Do not mount the unit in an enclosed battery compartment. Take precautions to keep road dirt and spray out of the unit.
Grounding
For safety purposes, the chassis of the Freedom 10 must be connected to your AC ground system. The chassis ground bonding lug is located on the bottom of the unit. This connector can accept two wires. The first is used to connect the unit to AC ground. The second can be used to connect other AC equipment to ground.
Use 5.0 mm2 ES (Euro Standard) green insulated wire. Strip one end and use a screwdriver to secure it to the chassis ground bonding lug. This wire will connect to the ground in your AC electrical system, typically the vehicle chassis. Make sure the connection is clean and tight.
This procedure will connect the chassis of your Freedom 10 to AC ground. In addition, the AC input and AC output green/yellow wires are connected to chassis ground. It is important to connect these wires to the AC ground bus in the circuit breaker panel.
Please note that the battery cables are not connected to ground or the chassis of the Freedom 10.
Neutral Bonding
For safety purposes, the Freedom 10 internally bonds the blue AC output neutral wire to the green/yellow AC ground wire when the unit is OFF or in the inverter mode. When incoming AC power is applied and the transfer switch is engaged, the internal
This means that when the RV is in a campground, the grounding system is connected to the shore power ground, where neutral and earth ground are bonded together. This technique ensures safety in all conditions and conforms to the requirements of numerous electrical codes. Refer to other applicable electrical codes regarding connections between AC ground and DC ground.