Operation
Battery Charger Voltage Settings
Table 3-5 Battery Charger Voltage Settings
Battery Type and | Acceptance Voltage/ |
|
| |
Temperature | Max Time | Float Voltage | Equalize Voltage | |
|
|
|
|
|
14.0 | / 1 hour | 13.1 | 15.8 | |
warm temperature |
|
|
|
|
14.4 | / 1 hour | 13.5 | 16.3 | |
cool temperature |
|
|
|
|
13.8 | / 3 hours | 13.3 | 14.1** | |
warm temperature |
|
|
|
|
14.1 | / 3 hours | 13.6 | 14.1** | |
cool temperature |
|
|
|
|
28.0 | / 1 hour | 26.2 | 31.6 | |
warm temperature |
|
|
|
|
28.8 | / 1 hour | 27.0 | 32.6 | |
cool temperature |
|
|
|
|
27.6 | / 3 hours | 26.6 | 27.6 | |
warm temperature |
|
|
|
|
28.2 | / 3 hours | 27.2 | 28.2 | |
cool temperature |
|
|
|
|
|
|
|
|
|
** When set for gel cells, the equalize mode is disabled.