Xantrex Technology 10 owner manual Charging Over-Discharged Batteries

Page 53

Battery Charging

Equalizing is not required on gel cell batteries. You will note that if the DIP switches are set in one of the two gel cell positions, the equalizing charge voltage is the same as the bulk charge voltage, therefore equalizing is equivalent to an 8- hour acceptance stage and is not harmful.

Equalize charging is current limited to 16 A DC. Remove all DC loads from the output of the inverter/charger.

CAUTION: Damage to batteries

Do not equalize gel cell batteries with the remote programmed for wet cells.

Always monitor the equalize charge. Provide proper ventilation for battery fumes. Do not allow any sparks during equalizing. If one or more cells begin to overflow, terminate the equalize cycle.

Check and top up the battery electrolyte both before and after the equalizing charge. Do not expose the battery plates to air. Leave the battery caps on while equalizing.

Remove all loads from the DC system before equalizing. Some DC loads may not tolerate the high charge voltage.

Do not leave the equalize DIP switch in the ON position. It must be cycled OFF and left in the OFF position. If left ON, the unit will engage the equalizing cycle every time the battery charger is engaged.

Charging Over-Discharged Batteries

Charging into a battery bank with a terminal voltage of less than 8 volts (16 in a 24-volt system) presents a special problem for the Freedom 10.

If this situation arises, the unit will attempt to charge for 1 minute. If the inverter senses excessive ripple voltage, it will shut down to protect itself.

To successfully charger an over-discharged battery, you must remove as much DC load as possible. Then, set DIP switches 7 and 8 to the ON position to limit the amount of charge current and the resulting ripple voltage. After the battery voltage has reached 10 volts (20 volts in a 24-volt system), these switches can be set to their previous positions.

Please note that if a continuous DC load in excess of 100 amps (50 amps in a 24-volt system) is placed on the battery bank, eventually the battery voltage will drop below 8 volts (16 volts in a 24-volt system) and the battery charger will shut off. This load must be significantly reduced and the power to the charger cycled to resume charging.

Blinking of the BATTERY LED on the remote control while charging is a warning that an over-discharge is imminent and that the DC load should be reduced.

975-0251-01-01

3–15

Image 53
Contents Freedom Inverter/Charger Page Freedom 10 Inverter/Charger Date and Revision Audience Purpose ScopeConventions Used Related InformationPage Important Safety Instructions Precautions When Working With Batteries Explosive gas precautionsPrecautions for Using Rechargeable Appliances Viii Contents Specifications TroubleshootingOperation GlossaryIntroduction 1Freedom 10 Inverter/Charger IntroductionCircuit Breaker Protection Things You Should KnowIntended Use Inverter ldle Circuit Power SharingElectronic Protection Installation Appropriate Applications Installation PrecautionsKey Installation Points Location Recreational Vehicle InstallationNeutral Bonding GroundingWire Color Description AC WiringResidual Current Circuit Breaker Remote Control WiringDC End DC Wiring4Fuse installation Battery Cable Fusing5Ground, AC, and Remote Connection Locations Marine InstallationMarine Installation 6AC Compartment Cover Plate Screws Residual Current Circuit Breaker DC Wiring 8Fuse installation 9Ground, AC, and Remote Connection Locations Residential Solar InstallationResidential Solar Installation 10AC Compartment Cover Plate Screws Residential Solar Installation 11 DC End 12Fuse installation Page Operation Models Freedom 10 Power SwitchRemote Control Panel Power Switch DC Volts Bar Graph 4Freedom Remote Control Dip Switches DIP Switch Status Remote Power Consumption Link 2000 Remote Control PanelBatteries Battery TypesSeries Battery InterconnectionParallel 4Typical Power Consumption Freedom Battery Charger Battery ChargingConventional Battery Chargers Bulk Charge Equalizing Batteries Charging Over-Discharged Batteries 5Battery Charger Voltage Settings Battery Charger Voltage SettingsTroubleshooting Troubleshooting Guide Using the Remote Control DC Amps LED Bar GraphSpecifications 12 VDC 24 VDC SpecificationsGlossary AWG Glossary of TermsLED Page Warranty Warranty and Return InformationExclusions DisclaimerProduct Out of Warranty Service Return Material Authorization PolicyReturn Procedure Purchased From Purchase Date Information About Your SystemPage Xantrex Technology Inc