4.3.4DIMENSIONING THE ALTERNATIVE ENERGY SOURCES

In a hybrid system, the alternative energy sources such as the solar generator, wind power and small hydropower should, in principle, be dimensioned in such a way as to be able to cover the average daily consumption.

4.4 Wiring diagrams

The diagrams shown in the appendix of this document are subsidiary. The applicable local installation regulations and standards must be adhered to.

The elements referred to with an uppercase letter denote the alternate current (AC) part. The elements referred to with a lowercase letter denote the direct current (DC) part.

4.5 Connecting the battery

Lead batteries are usually available in 2 V, 6 V or 12 V block types. In the majority of cases, in order to obtain an operating voltage that is correct for Xtender usage, several batteries must be connected in series or in parallel depending on the circumstances.

In multi-unit systems, all Xtenders from the same system must be connected according to the same battery bank.

The various cabling options are presented in figures 5a-5b (12 V), 5c-5e (24 V) and 6a to 6d (48 V) in appendix I of this manual.

4.5.1MINIMUM BATTERY CABLE CROSS-SECTION

XTH3000-12

XTH5000-24

XTH6000-48

XTH8000-48

 

 

 

 

90 mm2

90 mm2

70 mm2

90 mm2

 

 

 

 

The cable sections recommended above are valid for lengths less than 3 m. beyond this length it is strongly recommended to over-section the battery cables.

The battery cables must also be as short as possible.

It is always preferable to keep the cable at the negative pole of the battery as short as possible.

4.5.2CONNECTING THE BATTERY (XTENDER SIDE)

Insert the conduit glands supplied on the battery cable before tightening the cable clamp. Crimp the cable clamps and fasten the conduit gland on the device. Repeat this for the second battery cable. Fix the battery cables to the appropriate connections „+ Battery “and „- Battery “. The M8 screws must be very well tightened.

4.5.3DC INPUT PROTECTION

In order to avoid any further loss and protection redundancy, the Xtender does not have an internal fuse. A protection device (f) must be installed as close as possible to the battery and sized as per the table opposite:

Unit

XTH-3000-12

XTH-5000-24

XTH-6000-48

XTH-8000-48

Fuse on the battery side

400A

350A

250A

300A

Installation and operating Instructions

Xtender V1.3

Page 12

Image 12
Contents Xtender Table of Contents Introduction General informationOperating instructions Quality and warranty ConventionsExclusion of Liability Assembly and installation Installation siteHandling and moving StorageFastening ConnectionsPos Description CommentCabling Choice of systemEarthing system Recommendations for dimensioning the system Wiring diagrams Connecting the batteryFuse on the battery side XTH3000-12 XTH5000-24 XTH6000-48 XTH8000-48BATTERY-SIDE Connection Connecting the Consumers AT the 230 V AC Output Powering up the installation Connecting the batteryCircuit diagram Description and functioningDescription of the main functions Fast voltage loss detection mode fast transfer Temperature is increased or the ventilation Limiting the Input Current by Limiting the Charger Current Input Current Controlled by Input Voltage Auxiliary Contacts Multi-unit configurations Accessories RCC-02 RCC-03Indicated alarm Comment ControlMain on/off control Display and control partsCheck the cause of this excess voltage. The equipment will Maintenance of the installation Product recyclingEC declaration of conformity Comments of annexes’ figures Example of installation in a vehicle AC part Installation example in a boat, with isolation transformerExample of a hybrid installation Example of parallel connection of 2 or 3 XtendersFigure elements DC part Elem Description CommentFigure elements AC part Elements of connexion cabinet a Control and display parts for the Xtender b Type plate elements bStuder Innotec Xtender Table of standard configurations Studer Innotec Xtender Technical data Model XTH 3000-12 XTH 5000-24 XTH 6000-48 XTH