Studer Innotec XTH 5000-24, XTH 6000-48, XTH 8000-48 Input Current Controlled by Input Voltage

Page 20

STUDER Innotec

Xtender

control is required. When this function is activated {1126}, it allows the current from the battery to be supplied to the user in order to guarantee that the current at the input of the device does not exceed the limit set {1107}.

If the input current limit is exceeded, the transfer relay will be opened immediately, thereby protecting the upstream protection device. If the exceeding of the input current value limit is due to a short-circuit downstream, the transfer relay will remain activated and the protection upstream of the Xtender (H) will be requested.

The installation cabling must take this particular function into account, which allows a current equivalent to the sum of all power outputs in the inverter and the AC source to be available at the output.

If you have, for example, a 5 kW (22 A) source and an Xtender of 5 kW, the power available at the output will be 10 kW. The downstream cabling must therefore be dimensioned accordingly. In this example, the output cable must be dimensioned to support a current of 45 A. A dimensioning table, fig. 1a, will help you to determine the output currents that dimension the protection devices and the cable sections to be applied.

If the Xtender is connected to a generator, this must have a power at least equal to half of the power of the Xtender(s) to which it is connected.

6.2.7INPUT CURRENT CONTROLLED BY INPUT VOLTAGE

When AC sources with variable power are connected to the Xtender's ACin, a particular parameter setting insure a permanent availability of the nominal power at the Xtender's output thanks to the Smartboost function. It's notably the case with "Dynawatt" 230Vac alternator coupled with variable speed traction engines. These kinds of sources have a variable voltage according to the available power. For this type of application, it's necessary to activate the parameter {1527}. So, the input current limit {1107} will be regulated between zero to the programmed value, for an input voltage whitch varies between {1309} and {1309}+{1433}

6.2.8BATTERY PROTECTION

The battery is protected in all cases against deep discharge. The indicator (52) flashes once when the battery has reached the disconnection threshold {1108} and the inverter will stop some time after {1190}. This threshold can be dynamically corrected {1191} with an advanced algorithm tha computes automatically the battery voltage compensation in function of the instantaneous power. This correction may also be manually fixed {1532} by setting the low voltage disconnection at full load {1109}. These dynamic corrections can be desactivated by stting the parameter {1191} . The inverter will stop immediately if a critically low voltage value set by the configuration {1188} is reached. The inverter will restart automatically when the battery voltage has reached the restarting threshold {1110}.

This restarting threshold {1110} can be automatically readjusted if the parametewr {1194} is activated, in order to better protect the battery against repeated cycling in an "almost empty " state of charge. The restarting threshold is then incremented {1298} up to a maximum value {1195}, whenever the LVD (low voltage disconnection) is reached. The restarting threshold will be reset to its initial value when the value of parameter {1307} is reached.

If the inverter is repeatedly {1304} encountering a low voltage disconnection in a short period {1404}, it will stop permanently and will only start again via an operator’s manual restart.

6.2.9XTENDER PROTECTION

The Xtender is protected electronically against overloads, short-circuit, overheating and reverse current (cabling of a voltage source on AC out).

In the event of overload or short-circuit at the output, the inverter stops for some seconds and restarts. If the inverter is repeatedly encountering this situation {1300} in a short period, it will stop permanently and will only start again via an operator’s manual control.

If the battery voltage exceeds the value set by the configuration {1121} the inverter stops and starts up again when the voltage is less than {1110}. If the Xtender is repeatedly encountering this situation {1303} in a short period {1403}, it will stop permanently and will only start up again via an operator’s manual control.

Installation and operating Instructions

Xtender V1.3

Page 20

Image 20
Contents Xtender Table of Contents Operating instructions IntroductionGeneral information Quality and warranty ConventionsExclusion of Liability Assembly and installation Installation siteHandling and moving StorageFastening ConnectionsPos Description CommentCabling Choice of systemEarthing system Recommendations for dimensioning the system Wiring diagrams Connecting the batteryFuse on the battery side XTH3000-12 XTH5000-24 XTH6000-48 XTH8000-48BATTERY-SIDE Connection Connecting the Consumers AT the 230 V AC Output Powering up the installation Connecting the batteryDescription of the main functions Circuit diagramDescription and functioning Fast voltage loss detection mode fast transfer Temperature is increased or the ventilation Limiting the Input Current by Limiting the Charger Current Input Current Controlled by Input Voltage Auxiliary Contacts Multi-unit configurations Accessories RCC-02 RCC-03Indicated alarm Comment ControlMain on/off control Display and control partsCheck the cause of this excess voltage. The equipment will EC declaration of conformity Maintenance of the installationProduct recycling Comments of annexes’ figures Example of installation in a vehicle AC part Installation example in a boat, with isolation transformerExample of a hybrid installation Example of parallel connection of 2 or 3 XtendersFigure elements DC part Elem Description CommentFigure elements AC part Elements of connexion cabinet a Control and display parts for the Xtender b Type plate elements bStuder Innotec Xtender Table of standard configurations Studer Innotec Xtender Technical data Model XTH 3000-12 XTH 5000-24 XTH 6000-48 XTH