Studer Innotec XTH 6000-48, XTH 8000-48, XTH 5000-24 Cabling, Choice of system

Page 9

STUDER Innotec

 

Xtender

 

 

 

 

 

 

12

-BAT

 

Negative pole battery

and when tightening the clamp.

 

 

 

 

connection terminals

 

 

13

AC Input

 

Connection terminals for the

See chapter 4.5.7 - p. 14.

 

 

 

 

alternative power supply

Note: It is imperative that the PE terminal

 

 

 

 

(generator or public network)

be connected.

 

14

AC Output

 

Connection terminals for the

See chapter 4.5.6 - p. 14.

 

 

 

 

device output.

Note: Increased voltages may appear on

 

 

 

 

 

the terminals, even in the absence of

 

 

 

 

 

voltage at the input of the inverter.

 

4 Cabling

The connection of the Xtender inverter / charger is an important installation step.

It may only be carried out by qualified personnel and in accordance with the applicable local regulations and standards. The installation must always comply with these standards.

Pay attention that connections are completely tightened and that each wire is connected at the right place.

4.1 Choice of system

The Xtender may be used in different system types, each of which must meet the standards and particular requirements associated with the application or site of installation. Only an appropriately qualified installer can advise you effectively on the applicable standards with regard to the various systems and the country concerned.

Examples of cabling are presented in appendix I of this manual, fig. 5 and following. Please carefully read the notes associated with these examples in the tables on p. 27 and following.

4.1.1HYBRID TYPE STAND-ALONE SYSTEMS

The Xtender can be used as a primary supply system for grid-remote sites where a renewable energy source (solar or hydraulic) is generally available and a generator is used as backup. In this case, batteries are generally recharged by a supply source such as solar modules, wind power or small hydropower systems. These supply sources must have their own voltage and/or current regulation system and are connected directly to the battery. (Example, fig. 11)

When the energy supply is insufficient, a generator is used as a back-up energy source. This allows the batteries to be recharged and direct supply to consumers via the Xtender transfer relay.

When the input voltage source is a low power generator (lower than the Xtender power) the factory settings (adapted to grid-connection) must be modified according to the “generator” column in the configuration table on p. 34.

4.1.2GRID-CONNECTED EMERGENCY SYSTEMS

The Xtender can be used as an emergency system, also known as an uninterruptible power supply (UPS) – enabling a reliable supply to a site connected to an unreliable network. In the event of an interruption to the energy supply from the public network, the Xtender, connected to a battery, substitutes the faulty source and enables a support supply to the users connected downstream. These will be supplied as long as the energy stored in the battery allows. The battery will quickly be recharged at the next reconnection to the public grid.

Various application examples are described in figs. 8a – 8c in appendix I.

The use of the Xtender as a UPS must be carried out by qualified personnel who have been checked by the responsible local authorities. The diagrams in the appendix are given for information and as a supplement. The applicable local standards and regulations must be adhered to.

4.1.3INTEGRATED MOBILE SYSTEMS

These systems are meant to be temporarily connected to the grid and ensure the supply of the mobile system when this is disconnected from the grid. The main applications are for boats, service

Installation and operating Instructions

Xtender V1.3

Page 9

Image 9
Contents Xtender Table of Contents Introduction General informationOperating instructions Conventions Quality and warrantyExclusion of Liability Installation site Assembly and installationHandling and moving StorageConnections FasteningDescription Comment PosChoice of system CablingEarthing system Recommendations for dimensioning the system Connecting the battery Wiring diagramsFuse on the battery side XTH3000-12 XTH5000-24 XTH6000-48 XTH8000-48BATTERY-SIDE Connection Connecting the Consumers AT the 230 V AC Output Connecting the battery Powering up the installationCircuit diagram Description and functioningDescription of the main functions Fast voltage loss detection mode fast transfer Temperature is increased or the ventilation Limiting the Input Current by Limiting the Charger Current Input Current Controlled by Input Voltage Auxiliary Contacts Multi-unit configurations RCC-02 RCC-03 AccessoriesControl Indicated alarm CommentMain on/off control Display and control partsCheck the cause of this excess voltage. The equipment will Maintenance of the installation Product recyclingEC declaration of conformity Comments of annexes’ figures Installation example in a boat, with isolation transformer Example of installation in a vehicle AC partExample of a hybrid installation Example of parallel connection of 2 or 3 XtendersElem Description Comment Figure elements DC partFigure elements AC part Elements of connexion cabinet a Type plate elements b Control and display parts for the Xtender bStuder Innotec Xtender Table of standard configurations Studer Innotec Xtender Model XTH 3000-12 XTH 5000-24 XTH 6000-48 XTH Technical data