Studer Innotec XTH 8000-48, XTH 6000-48, XTH 5000-24 Example of installation in a vehicle AC part

Page 28

 

STUDER Innotec

Xtender

 

 

 

 

 

 

Fig.

Description and comment

 

 

 

10a

Example of installation in a vehicle (AC part)

 

 

 

 

Special features: The connection of the neutral (C) is not permitted (presence of a socket

 

 

upstream). The earth-neutral connection is absent in inverter mode (neutral stand-alone

 

 

system). The safety is guaranteed by the equipotential bonding (frame). The automatic re-

 

 

establishment of the earth-neutral connection downstream of the device in inverter mode

 

 

can be programmed. Consult the table of figures, item (V).

 

 

 

 

See also chapter 4.2.1 – p. 10.

 

 

 

10b

Example of installation in a boat without an isolation transformer (AC part)

 

 

 

 

Special feature: Where there are multiple sources, for example connection to the dock and

 

 

on-board generator, a source reverser (X) guaranteeing switching with phase and neutral

 

 

interruption must be installed.

 

 

 

10c

Installation example in a boat, with isolation transformer

 

 

 

 

Characteristic: With several power sources, like shore connection and onboard generator,

 

 

a switchover (X) must be installed, to safely switch between the different voltage supplies

 

 

with guaranteed interruption of the phase and neutral conductors. Moreover, an earth

 

 

must be formed (E) after the isolation transformer.

 

 

11Example of a hybrid installation:

This is the most common system used to establish an emergency system or a hybrid system (grid-remote sites) ensuring a single-phase supply from a generator and/or the battery.

Special feature: In a hybrid installation, the sources for recharging a battery (k-m) are connected directly to the batterie via their own control system. This does not interfere with the Xtender charger. See also chapter 4.1.1 – p. 9.

12Example of parallel connection of 2 or 3 Xtenders

1.Only Xtenders of the same power output may be connected in parallel.

2.Wiring precautions: The cable lengths and cross-sections of AC in input (A) and AC out output (B) must be the same for all inverters in parallel in the same phase.

3.Variant: The sum of the lengths of the cables (A1) + (B1) of Xtender 1 must be the same as the sum of the lengths of the cables (A1) + (B1) of Xtender 2, and ditto for Xtender 3

4.The AC input for each Xtender must be protected individually by a protection device

(H) of the appropriate size.

5.The protection device at the output of the Xtender (F) can be shared and of appropriate calibre at the sum of the currents of the devices in parallel.

6.If necessary, the ON/OFF remote control (r) will be implemented on only one of the devices of the installation and suspends or authorises the operation of all the Xtenders in the installation.

13Example of three-phase cabling of 3 Xtenders – three-phase input

Special features: When 3 Xtenders are cabled to form a three-phase grid, the cabled phases at the input determine the jumper position for selecting the phase (10). It is vital to determine and select the phase for each Xtender.

See also chapter 6.3.1 – p. 22.

The comments for fig. 12 - 4 to 6 are valid.

14Example of three-phase cabling of 3 Xtenders – single-phase input

Special feature: In a three-phase configuration, if only one phase is available as a source, only one Xtender will be wired on that source. Phase 2 and 3 will be permanently fed from the two other units connected only to the battery (not connected to ACin).

It is vital to determine and select the phase for each Xtender. See also chapter 6.3.1– p. 22.

The comments for fig. 12 are valid.

15Example of three-phase, input and output wired, with reinforced phase

Special feature: This installation allows a three-phase supply with a reinforced phase The reinforced phase may be incorporated on two or even three inverters in parallel. The protection device at the output on which 2 or 3 Xtenders are cabled must be calibrated according to the sum of the maximum currents of the devices in parallel.

The comments for fig. 12 to 13 are valid.

Installation and operating Instructions

Xtender V1.3

Page 28

Image 28
Contents Xtender Table of Contents General information IntroductionOperating instructions Quality and warranty ConventionsExclusion of Liability Assembly and installation Installation siteHandling and moving StorageFastening ConnectionsPos Description CommentCabling Choice of systemEarthing system Recommendations for dimensioning the system Wiring diagrams Connecting the batteryFuse on the battery side XTH3000-12 XTH5000-24 XTH6000-48 XTH8000-48BATTERY-SIDE Connection Connecting the Consumers AT the 230 V AC Output Powering up the installation Connecting the batteryDescription and functioning Circuit diagramDescription of the main functions Fast voltage loss detection mode fast transfer Temperature is increased or the ventilation Limiting the Input Current by Limiting the Charger Current Input Current Controlled by Input Voltage Auxiliary Contacts Multi-unit configurations Accessories RCC-02 RCC-03Indicated alarm Comment ControlMain on/off control Display and control partsCheck the cause of this excess voltage. The equipment will Product recycling Maintenance of the installationEC declaration of conformity Comments of annexes’ figures Example of installation in a vehicle AC part Installation example in a boat, with isolation transformerExample of a hybrid installation Example of parallel connection of 2 or 3 XtendersFigure elements DC part Elem Description CommentFigure elements AC part Elements of connexion cabinet a Control and display parts for the Xtender b Type plate elements bStuder Innotec Xtender Table of standard configurations Studer Innotec Xtender Technical data Model XTH 3000-12 XTH 5000-24 XTH 6000-48 XTH