5 Programming (possible only with the remote control RCC-01)
The
It is possible to reinitialize (RESET) the
5.1Standard setting
The
Auxiliary contact: active in case of defect or manual turn off with the LED 10/11/12/13
Battery voltage : | Low voltage | 11.6V / 23.2V / 46.4V |
| Float Charge | 13.5V / 27.0V / 54.0V |
| End of Charge Voltage | 14.4V / 28.8V / 57.6V |
| Equalization | 15.6V / 31.2V / 62.4V |
Absorption Time : |
| 2 Hours |
Equalizing Time : |
| 20 Minutes |
5.2Reset value (default settings)
To come back to the default settings, press simultaneously on the push buttons 20/21 during at least 2 seconds. A beep will confirm the comeback to the factory settings. The inverter switches off after this operation. It can be turned on again after the beep.
5.3Battery voltages and absorption time
5.3.1Set the voltage and timing threshold The programming is done in accordance with the following steps:
Push and hold down, the Push Button 21 (Program) and the Push Button 19 (Change status) for minimum 2 seconds simultaneously.
With the Push Button 20 (select) select which of the battery level and of the absorption time have to be changed.
These four red LED’s show the function set:
Low voltage | LED 13 | (ON/OFF) |
Float charge | LED 12 | (Batt. Low/high) |
Absorption (End of charge) | LED 11 | (Overload) |
Equalization | LED 10 | (Overtemp.) |
Absorption Time | LED 10/11/12/13 (altogether) |