Studer Innotec C-IP23 Disabling some of the XP-COMPACT functions, Diagram of the different modes

Page 23

STUDER INNOTEC

XP-COMPACT

The Auxiliary Contact can be operated at any time with the Push Button 21 (AUX. CONTACT). The LED 6 „Contact manual“ lights up as information that the Contact is manually operated, and LED 5 „Contact active“ lights up when the Contact is active. By pushing the Push Button 21 a second time, the Contact is disabled. By pushing it the third time, automatic functions are restored.

5.5Disabling some of the XP-COMPACT functions

Each different function charger, inverter and transfer can be disabled. This is useful for specific applications witch required to disable some of these three functions.

If you press the buttons 19 and 20 more than 2 seconds you can have access to the different possibilities, shown in the following diagram.

In programming mode the display shows only the different types of program with the three LED’s 2, 7 and 9 to each function. To change the type of programming, press shortly the button 20 until you reach the right function used according to the table below. After 10 seconds the XP-COMPACT exits the programming mode and loads the new change.

In user mode, the disabled functions are displayed by blinking LED. So you can see which mode is disabled.

5.5.1 Diagram of the different modes

Shows an off LED

Shows a blinking LED

Shows a lighted LED

All the functions are enabled. This is the factory setting.

The inverter is disabled. Only the transfer switch and the charger will work normal- ly.

Inverter and charger are both disabled. Only the transfer switch function is ena- bled in input voltage and frequency is OK

Charger and transfer switch are disabled the inverter will work continuously even if there is a correct AC voltage at the input.

XP-COMPACT V5.4

25/77

Image 23
Contents Studer Innotec Sine wave Inverter, Battery charger, TransfersystemXP-COMPACT Operating instructions Quality and WarrantyWarranty Disclaimer General InformationLiability Disclaimer Special precautionsIntroduction Principle schematicDescription of the main functions Battery connecting Connections Mounting and installingInstallation place FixingSolar + Connection PlanProtection cover of the terminals connections Connection to the 230Vac-consumer appliances AC Output Pre-installation settingsConnection to battery CablingDisplay and control parameters ControlTransfer ChargerSolar ChargeInverter Push buttonsTurning Knobs Battery charger Equalization charging Default values for battery voltage thresholdsCharging current Transfer systemSet the transfer voltage threshold Fast UPS- Mode for the Transfer SwitchDelayed mode of the Transfer System CompactMultifunctional Contact Solar charge controller optionXP-COMPACT Temperature sensor CT-35Battery voltages and absorption time Programming possible only with the remote control RCC-01Standard setting Reset value default settingsProgramming of the Auxiliary Contact Auxiliary contactTable of voltage and timing threshold PrincipleManual operating of Auxiliary Contact Power cut of the second priority loadsAuxiliary Contact as generator starter Disabling some of the XP-COMPACT functions Diagram of the different modesDeclaration of CE Compliance Installation MaintenanceTechnical Data