are automatically stored and the
5.4.3Auxiliary Contact as generator starter
As per the battery capacity
When in the programming of the Auxiliary Contact, the Battery Capacity (LED
If you have to start an emergency
Example: start of a generator with the XP-COMPACT
In order to program the auxiliary contact to start at 25% and to stop at 75% of the battery
− Press the key AUX. CONTACT (Program) 21 during at least 2 seconds. Then the states will be displayed blinking (factory settings LED’s 10/11/12/13). As these states are not wished for the start of the generator, they must be disabled.
− With the key (select) 20, select the LED’s to disable (the active LED’s are blinking) and disable them with the key 19 Change Status. Select the other LED’s to switch off with the key (select) 20 and switch them off with the key 19 Change Status until all are disabled.
− Then select the LED 17 with the key (select) 20 and activate the contact with the key 19 Change Status. The generator will start once the LED 17 switches of.
− Then select the LED 16 with the key (select) 20 and activate the contact with the
key 19 Change Status. The generator will stop once the LED 16 switches on.
− If no key is activated during 30 seconds, the normal operation states are displayed automatically again.
For a control the key Program can be pressed at least 2 seconds. The values set are displayed blinking.
5.4.4Auxiliary Contact as Twilight Witch (with solar charger option)
The Auxiliary Contact of the
5.4.5 Power cut of the second priority loads
The auxiliary contact can also be used to cut the power of less priority loads when the battery state of charge is lower than a given threshold. In that case, only one of the battery state of charge, or the “transfer” function will be programmed as power cut criteria.
The second priority loads will be supplied only when the generator is ON or when the battery has a sufficient threshold.
5.4.6 Manual operating of Auxiliary Contact