Bryant 589A user manual 588A018-042 With Optional Base Rail, Unit Dimensions, Ð3Ð

Page 3

REQ'D CLEARANCES FOR SERVICING. in. (mm)

Duct panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0

Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)

Side opposite ducts

.

. 36

(914)

Compressor access

.

. 36

(914)

(Except for NEC requirements)

 

 

 

REQ'D CLEARANCES TO COMBUSTIBLE MAT'L. in. (mm)

 

 

 

Maximum extension of overhangs . . . . . . . . . . . . . . . 48 (1219)

Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)

Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . . 2 (51)

Side opposite ducts

. . . . . . . 14 (356)

Bottom of unit

. .

. .

. . . . . . 0

Flue panel

. .

. .

.

. . 36 (914)

NEC REQ'D CLEARANCES. in. (mm)

 

 

 

 

Between units, control box side

. . . . . . 42 (1067)

Unit and ungrounded surfaces, control box side . .

. .

. .

.

. . 36 (914)

Unit and block or concrete walls and other grounded

 

 

 

 

surfaces, control box side

. .

. .

.

. 42 (1067)

UNIT

ELECTRICAL

UNIT WEIGHT

 

CORNER WEIGHT

 

UNIT HEIGHT

 

 

(lb/kg)

 

(in./mm)

588A

CHARACTERISTICS

 

 

 

 

 

lb

kg

A

B

 

C

D

E

 

 

 

018040

208/230-1-60

296

135

87/40

68/31

 

82/37

59/27

27.4/697

024040

208/230-1-60

327

149

103/47

49/22

 

129/59

46/21

27.4/697

024060

208/230-1-60

339

155

106/48

52/24

 

132/60

49/22

27.4/697

030040

208/230-1-60, 208/230-3-60

344

157

106/48

53/24

 

132/60

53/24

27.4/697

030060/080

208/230-1-60, 208/230-3-60

356

162

102/46

71/32

 

123/56

60/27

27.4/697

036060/080

208/230-1-60, 208/230-3-60, 460-3-60

360

164

92/42

82/37

 

117/53

69/31

27.4/697

036100/120

208/230-1-60, 208/230-3-60, 460-3-60

372

169

95/43

85/39

 

120/55

72/33

27.4/697

042060/080

208/230-1-60, 208/230-3-60, 460-3-60

399

181

101/46

92/42

 

125/57

81/37

31.4/798

042100/120

208/230-1-60, 208/230-3-60, 460-3-60

411

187

104/47

95/43

 

128/58

84/38

31.4/798

 

 

 

 

 

 

 

 

 

 

UNIT

F

G

CENTER OF GRAVITY in./mm

588A

in./mm

in./mm

X

 

Y

Z

018040

 

 

25.04/636

22.72/577

 

024040

 

 

26.90/683.3

20.17/512.3

 

024060

 

 

26.82/681.2

20.22/513.6

 

030040

197¤8/504.8

221¤4/565.4

26.57/674.9

20.1

/509.3

13.16/334.3

030060/080

 

 

26.93/684

21.1

/535.4

 

036060/080

 

 

27.31/693.7

21.0

/532.6

 

036100/120

 

 

27.23/691.6

21.0

/533.1

 

042060/080

237¤8/606.4

261¤4/666.8

26.87/682.5

21.0

/533.1

14.96/380

042100/120

26.81/681

21.0

/533.7

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

 

 

CG

Ð

Center of Gravity

MAT'L

Ð

Material

COND

Ð Condenser

NEC

Ð National Electrical Code

LV

Ð

Low Voltage

REQ'D

Ð

Required

NOTES:

1.Clearances must be maintained to prevent recirculation of air from outdoor- fan discharge.

2.Adequate clearance around air openings into combustion chamber must be provided.

Fig. 3 Ð 588A018-042 With Optional Base Rail, Unit Dimensions

Ð3Ð

Image 3
Contents Contents Safety ConsiderationsGeneral Ð2Ð 588A018-042 Without Base Rail, Unit DimensionsÐ3Ð 588A018-042 With Optional Base Rail, Unit DimensionsÐ4Ð 588A048,060 Without Base Rail, Unit DimensionsÐ5Ð 588A048,060 With Optional Base Rail, Unit DimensionsÐ6Ð 589A024-036 Without Base Rail, Unit DimensionsÐ7Ð 589A024-036 With Optional Base Rail, Unit DimensionsÐ8Ð 589A042-060 Without Base Rail, Unit DimensionsÐ9Ð 589A042-060 With Optional Base Rail, Unit DimensionsIV. Ð Provide Clearances Receiving and Installation Check EquipmentII. Ð Provide Unit Support III. Ð Field Fabricate DuctworkÐ11Ð Part NumberCurb Weight Unit MAXUnit VI. Ð Connect Condensate Drain VII. Ð Install Flue HoodVIII. Ð Install GAS Piping Units With Optional Base RailÐ14Ð Physical Data Ð Unit 588AÐ15Ð Physical Data Ð Unit 589AConguring Units for Down¯ow Vertical Discharge IX. Ð Install Duct ConnectionsMaximum Gas Flow Capacity Ð17ÐInternal Length of PIPE, FT² Iron Pipe Diameter Size High-Voltage Connections Install Electrical ConnectionsÐ19Ð Ð Electrical Data Ð Unit 588AÐ Electrical Data Ð Unit 589A Ð20ÐRLA LRA FLA High- and Control-Voltage Connections Special Procedures for 208-V OperationPRE-START-UP Transformer ProtectionCheck Heating Control II. Start UP Heating Section and Make AdjustmentsAdjust Gas Input START-UP Check for Refrigerant LeaksOrifices Rated Gas Inputs at Indicated Manifold PressuresGAS Supply Pressure Manifold Natural GAS Propane Number PressureHeating Temperature Rise F Input Check Burner FlameÐ25Ð III. Start UP Cooling Section and Make Adjustments Ð27Ð 208/230-1-60 Wiring Diagram, Units 588A018-060Ð28Ð 208/230-3-60 Wiring Diagram, Units 588A030-060Ð29Ð 460-3-60 Wiring Diagram, Units 588A036-060Ð30Ð 208/230-1-60 Wiring Diagram, Units 589A024-042Ð31Ð 208/230-1-60 Wiring Diagram, Units 589A048,060Ð32Ð 208/230-3-60 Wiring Diagram, Units 589A036-042Ð33Ð 208/230-3-60 Wiring Diagram, Units 589A048,060Ð34Ð 460-3-60 Wiring Diagram, Units 589A036-048Checking and Adjusting Refrigerant Charge Indoor Air¯ow and Air¯ow AdjustmentsSpeed Ð Superheat Charging Table, 588A018 Ð Superheat Charging Table, 588A024Ð36Ð Ð37Ð Ð Superheat Charging Table, 588A030Ð Superheat Charging Table, 588A036 Ð Superheat Charging Table, 588A042Ð38Ð Ð Superheat Charging Table, 588A060Ð39Ð Ð Superheat Charging Table, 589A024Ð Superheat Charging Table, 589A030 Ð Superheat Charging Table, 589A036Ð40Ð Ð Superheat Charging Table, 589A042Ð Superheat Charging Table, 589A048 Ð Superheat Charging Table, 589A060Ð41Ð Required Suction-Tube Temperature FÐ42Ð Unit 589A Ð43ÐUnit Size Airflow Pressure Drop MaintenanceWet Coil Pressure Drop Cooling Sequence of OperationIV. Flue GAS Passageways AIR FilterII. Unit TOP Removal III. Evaporator Blower and MotorVIII. Main Burners VI. Limit SwitchCOMBUSTION-AIR Blower VII. Burner IgnitionXIII. GAS Input XI. Electrical Controls and WiringCondenser FAN XII. Refrigerant CircuitSymptom Cause Remedy TroubleshootingMotor IFM runs when itPoor ¯ame characteristics Integrated controlLED OFF Service TrainingPage III. START-UP Electrical START-UP ChecklistTemperatures Preliminary Information
Related manuals
Manual 27 pages 52.72 Kb

589A, 588A specifications

The Bryant 588A is a high-efficiency gas furnace celebrated for its advanced technology and superior performance in residential heating. Known for its reliability and durable construction, this model is ideal for homeowners looking for warmth and comfort during colder months.

One of the standout features of the Bryant 588A is its remarkable AFUE (Annual Fuel Utilization Efficiency) rating, which can reach up to 96.5%. This high efficiency means that a significant portion of the fuel consumed is converted into usable heat, leading to lower energy bills and a reduced carbon footprint. The furnace utilizes a two-stage heating system, which improves comfort levels by providing more consistent temperatures and reducing the frequency of temperature swings in the home.

Another notable characteristic is the incorporation of a multi-speed blower motor. This innovation enhances airflow and optimizes energy use by adjusting the fan speed according to the heating needs of the home. The variable speed operation also helps to minimize noise levels, creating a quieter environment compared to traditional single-speed furnaces.

The Bryant 588A features an advanced control system that allows for better system management and can be integrated with smart home technologies. This allows homeowners to monitor and adjust their heating settings remotely, offering convenience and efficiency. Additionally, the furnace is compatible with Bryant’s Evolution System, which provides advanced diagnostic features and improved energy performance.

Durability is a key characteristic of the Bryant 588A, as it is constructed with a heavy-duty cabinet designed to withstand the rigors of daily use and harsh weather conditions. The unit also includes a corrosion-resistant heat exchanger, ensuring longevity and reliability.

Furthermore, the Bryant 588A operates quietly, thanks to its insulated cabinet and advanced design. This feature is especially appreciated by homeowners seeking a peaceful living environment free from disruptive noises typically associated with heating systems.

In summary, the Bryant 588A gas furnace combines high efficiency, innovative technology, and durable construction. Its effective heating capabilities paired with user-friendly features make it a smart investment for anyone looking to enhance their home heating system while enjoying lower energy costs and increased comfort.