B. Units With Optional Base Rail

Lifting holes are provided in optional base rail as shown in Fig. 13. Operating weights are shown in Tables 1 and 2. Re- fer to rigging instructions on unit.

Protective wood support must be removed from unit before unit is mounted to curb. Remove 4 screws that secure sup- port above rigging holes in rails. Slide support out through rectangular hole in rail. See Fig. 13.

VI. STEP 6 Ð CONNECT CONDENSATE DRAIN

NOTE: When installing condensate drain connection be sure to comply with local codes and restrictions.

Model 588A, 589A disposes of condensate water through a 3¤4 in. NPT ®tting which exits through the compressor access panel. See Fig. 2-9 for location.

Condensate water can be drained directly onto the roof in roof- top installations (where permitted) or onto a gravel apron in ground-level installations. Install a ®eld-supplied conden- sate trap at end of condensate connection to ensure proper drainage. Make sure that the outlet of the trap is at least 1 in. lower than the drain-pan condensate connection to pre- vent the pan from over¯owing. See Fig. 14. Prime the trap with water. When using a gravel apron, make sure it slopes away from the unit.

If the installation requires draining the condensate water away from the unit, install a 2-in. trap at the condensate connec- tion to ensure proper drainage. See Fig. 14. Make sure that the outlet of the trap is at least 1 in. lower than the drain- pan condensate connection to prevent the pan from over¯ow- ing. Prime the trap with water. Connect a drain tube using a minimum of 3¤4-in. PVC or 3¤4-in. copper pipe (all ®eld- supplied) at the outlet end of the 2-in. trap. Do not undersize the tube. Pitch the drain tube downward at a slope of at least one in. for every 10 ft of horizontal run. Be sure to check the drain tube for leaks.

Fig. 14 Ð Condensate Trap

VII. STEP 7 Ð INSTALL FLUE HOOD

The ¯ue hood assembly is shipped screwed to the control box in the burner compartment. Remove the burner access panel to locate the assembly.

For units being installed in California Air Quality Manage- ment Districts which require NOx emissions of 40 nanograms/ joule or less, kit CRLOWNOX001A00 must be installed.

CAUTION: The venting system is designed to en- sure proper venting. The ¯ue hood assembly must be installed as indicated in this section of the unit instal- lation instructions.

Install the ¯ue hood as follows:

1.This installation must conform with local building codes and with the National Fuel Gas Code (NFGC), Ameri- can National Standards Institute (ANSI) Z223.1 (in Canada, CAN/CGA B149.1, and B149.2) or NFPA (Na- tional Fire Protection Association) latest revision. Refer to Provincial and local plumbing or wastewater codes and other applicable local codes.

2.Remove from shipping location. Place vent cap assem- bly over ¯ue panel. Orient screw holes in vent cap with holes in the ¯ue panel.

3.Secure ¯ue hood to ¯ue panel by inserting a single screw on the right side, the left side, and the top of the hood.

VIII. STEP 8 Ð INSTALL GAS PIPING

The gas supply pipe enters the unit through the access hole provided. The gas connection to the unit is made to the 1¤2-in. FPT gas inlet on the manual shutoff or gas valve.

Install a gas supply line that runs to the heating section. Re- fer to Table 3 and the NFGC for gas pipe sizing. Do not use cast-iron pipe. It is recommended that a black iron pipe is used. Check the local utility for recommendations concern- ing existing lines. Size gas supply piping for 0.5 in. wg maxi- mum pressure drop. Never use pipe smaller than the 1¤2-in. FPT gas inlet on the unit gas valve.

For natural gas applications, the gas pressure at unit gas con- nection must not be less than 4.0 in. wg or greater than 13 in. wg while the unit is operating. For propane applica- tions, the gas pressure must not be less than 4.0 in. wg or greater than 13 in. wg at the unit connection.

An 1¤8-in. NPT plugged tapping accessible for test gage con- nection must be installed immediately upstream of the gas supply connection to the furnace.

When installing the gas supply line, observe local codes per- taining to gas pipe installations. Refer to the NFGC ANSI Z223.1-1988 NFPA latest edition (in Canada, CAN/CGA B149.1,

(2)-M86). In the absence of local building codes, adhere to the following pertinent recommendations:

1.Avoid low spots in long runs of pipe. Grade all pipe 1¤4 inch in every 15 ft to prevent traps. Grade all hori- zontal runs downward to risers. Use risers to connect to heating section and to meter.

2.Protect all segments of piping system against physical and thermal damage. Support all piping with appropri- ate straps, hangers, etc. Use a minimum of one hanger every 6 ft. For pipe sizes larger than 1¤2 in., follow rec- ommendations of national codes.

3.Apply joint compound (pipe dope) sparingly and only to male threads of joint when making pipe connections. Use only pipe dope that is resistant to action of lique®ed petroleum gases as speci®ed by local and/or national codes. Never use Te¯on tape.

4.Install sediment trap in riser leading to heating section per Fig. 15. This drip leg functions as a trap for dirt and condensate.

5.Install an accessible, external, manual main shutoff valve in gas supply pipe within 6 ft of heating section.

6.Install ground-joint union close to heating section be- tween unit manual shutoff and external manual main shutoff valve.

7.Pressure-test all gas piping in accordance with local and national plumbing and gas codes before connecting pip- ing to unit.

NOTE: Pressure test the gas supply system after the gas sup- ply piping is connected to the gas valve. The supply piping must be disconnected from the gas valve during the testing of the piping systems when test pressure is in excess of

0.5psig. Pressure test the gas supply piping system at pres- sures equal to or less than 0.5 psig. The unit heating section must be isolated from the gas piping system by closing the external main manual shutoff valve and slightly opening the ground-joint union.

Ð13Ð

Image 13
Contents Safety Considerations ContentsGeneral Ð2Ð 588A018-042 Without Base Rail, Unit DimensionsÐ3Ð 588A018-042 With Optional Base Rail, Unit DimensionsÐ4Ð 588A048,060 Without Base Rail, Unit DimensionsÐ5Ð 588A048,060 With Optional Base Rail, Unit DimensionsÐ6Ð 589A024-036 Without Base Rail, Unit DimensionsÐ7Ð 589A024-036 With Optional Base Rail, Unit DimensionsÐ8Ð 589A042-060 Without Base Rail, Unit DimensionsÐ9Ð 589A042-060 With Optional Base Rail, Unit DimensionsII. Ð Provide Unit Support Receiving and Installation Check EquipmentIII. Ð Field Fabricate Ductwork IV. Ð Provide ClearancesPart Number Ð11ÐCurb Unit MAX WeightUnit VIII. Ð Install GAS Piping VII. Ð Install Flue HoodUnits With Optional Base Rail VI. Ð Connect Condensate DrainÐ14Ð Physical Data Ð Unit 588AÐ15Ð Physical Data Ð Unit 589AConguring Units for Down¯ow Vertical Discharge IX. Ð Install Duct ConnectionsÐ17Ð Maximum Gas Flow CapacityInternal Length of PIPE, FT² Iron Pipe Diameter Size High-Voltage Connections Install Electrical ConnectionsÐ19Ð Ð Electrical Data Ð Unit 588AÐ20Ð Ð Electrical Data Ð Unit 589ARLA LRA FLA High- and Control-Voltage Connections Special Procedures for 208-V OperationPRE-START-UP Transformer ProtectionAdjust Gas Input II. Start UP Heating Section and Make AdjustmentsSTART-UP Check for Refrigerant Leaks Check Heating ControlGAS Supply Pressure Manifold Natural GAS Propane Number Rated Gas Inputs at Indicated Manifold PressuresPressure OrificesCheck Burner Flame Heating Temperature Rise F InputÐ25Ð III. Start UP Cooling Section and Make Adjustments Ð27Ð 208/230-1-60 Wiring Diagram, Units 588A018-060Ð28Ð 208/230-3-60 Wiring Diagram, Units 588A030-060Ð29Ð 460-3-60 Wiring Diagram, Units 588A036-060Ð30Ð 208/230-1-60 Wiring Diagram, Units 589A024-042Ð31Ð 208/230-1-60 Wiring Diagram, Units 589A048,060Ð32Ð 208/230-3-60 Wiring Diagram, Units 589A036-042Ð33Ð 208/230-3-60 Wiring Diagram, Units 589A048,060Ð34Ð 460-3-60 Wiring Diagram, Units 589A036-048Indoor Air¯ow and Air¯ow Adjustments Checking and Adjusting Refrigerant ChargeSpeed Ð Superheat Charging Table, 588A024 Ð Superheat Charging Table, 588A018Ð36Ð Ð Superheat Charging Table, 588A036 Ð Superheat Charging Table, 588A030Ð Superheat Charging Table, 588A042 Ð37ÐÐ38Ð Ð Superheat Charging Table, 588A060Ð Superheat Charging Table, 589A030 Ð Superheat Charging Table, 589A024Ð Superheat Charging Table, 589A036 Ð39ÐÐ Superheat Charging Table, 589A048 Ð Superheat Charging Table, 589A042Ð Superheat Charging Table, 589A060 Ð40ÐÐ41Ð Required Suction-Tube Temperature FÐ42Ð Unit 589A Ð43ÐWet Coil Pressure Drop MaintenanceCooling Sequence of Operation Unit Size Airflow Pressure DropII. Unit TOP Removal AIR FilterIII. Evaporator Blower and Motor IV. Flue GAS PassagewaysCOMBUSTION-AIR Blower VI. Limit SwitchVII. Burner Ignition VIII. Main BurnersCondenser FAN XI. Electrical Controls and WiringXII. Refrigerant Circuit XIII. GAS InputSymptom Cause Remedy TroubleshootingPoor ¯ame characteristics IFM runs when itIntegrated control MotorLED OFF Service TrainingPage Temperatures START-UP ChecklistPreliminary Information III. START-UP Electrical
Related manuals
Manual 27 pages 52.72 Kb

589A, 588A specifications

The Bryant 588A is a high-efficiency gas furnace celebrated for its advanced technology and superior performance in residential heating. Known for its reliability and durable construction, this model is ideal for homeowners looking for warmth and comfort during colder months.

One of the standout features of the Bryant 588A is its remarkable AFUE (Annual Fuel Utilization Efficiency) rating, which can reach up to 96.5%. This high efficiency means that a significant portion of the fuel consumed is converted into usable heat, leading to lower energy bills and a reduced carbon footprint. The furnace utilizes a two-stage heating system, which improves comfort levels by providing more consistent temperatures and reducing the frequency of temperature swings in the home.

Another notable characteristic is the incorporation of a multi-speed blower motor. This innovation enhances airflow and optimizes energy use by adjusting the fan speed according to the heating needs of the home. The variable speed operation also helps to minimize noise levels, creating a quieter environment compared to traditional single-speed furnaces.

The Bryant 588A features an advanced control system that allows for better system management and can be integrated with smart home technologies. This allows homeowners to monitor and adjust their heating settings remotely, offering convenience and efficiency. Additionally, the furnace is compatible with Bryant’s Evolution System, which provides advanced diagnostic features and improved energy performance.

Durability is a key characteristic of the Bryant 588A, as it is constructed with a heavy-duty cabinet designed to withstand the rigors of daily use and harsh weather conditions. The unit also includes a corrosion-resistant heat exchanger, ensuring longevity and reliability.

Furthermore, the Bryant 588A operates quietly, thanks to its insulated cabinet and advanced design. This feature is especially appreciated by homeowners seeking a peaceful living environment free from disruptive noises typically associated with heating systems.

In summary, the Bryant 588A gas furnace combines high efficiency, innovative technology, and durable construction. Its effective heating capabilities paired with user-friendly features make it a smart investment for anyone looking to enhance their home heating system while enjoying lower energy costs and increased comfort.