Bryant 588A Integrated control, Units 589A048,060 208/230, IFM does not run, Motor units

Page 49

Cooling (cont)

SYMPTOM

 

CAUSE

REMEDY

 

 

 

 

Integrated control

 

Blower wheel not secured to shaft

Properly tighten blower wheel to shaft.

motor

 

 

 

 

Insufficient voltage at motor

Determine cause and correct.

(units 589A048,060

 

 

 

 

208/230 v)

 

Power connectors not properly

Connectors should snap easily; do not

IFM does not run.

 

seated

force.

 

 

 

 

Integrated control

 

Motor programmed with a delay

Allow a few minutes for motor to shut off.

motor (units

 

pro®le

 

589A048,060

 

 

 

 

With thermostat in OFF the voltage

If measured voltage is more than 1¤2, the

208/230 v)

 

on G,Y1,Y/Y2,W with respect to

thermostat is incompatible with motor. If

IFM runs when it

 

 

common, should be 1¤2 of actual

voltage is less than 1¤2, the motor has failed.

should be off.

 

low voltage supply

 

 

 

 

 

 

 

 

Integrated control

 

Water dripping into motor

Verify proper drip loops in connector wires.

motor (units

 

 

 

589A048,060

 

 

 

 

Connectors not ®rmly seated

Gently pull wires individually to be sure they

208/230 v) IFM

 

 

 

are crimped into the housing.

operation is

 

 

intermittent.

 

 

 

IFM Ð Evaporator (Indoor) Fan Motor

 

 

Heating

SYMPTOM

CAUSE

 

REMEDY

 

 

 

Burners will not ignite.

Water in gas line

Drain. Install drip leg.

 

No power to furnace

Check power supply fuses, wiring, or circuit breaker.

 

No 24-v power supply to control

Check transformer.

 

circuit

NOTE: Some transformers have internal overcurrent

 

 

protection that requires a cool-down period to reset.

 

Miswired or loose connections

Check all wiring and wirenut connections.

 

Burned-out heat anticipator in

Replace thermostat.

 

thermostat

 

 

 

Broken thermostat wire

Run continuity check. Replace wire if necessary.

 

Misaligned spark electrodes

Check ¯ame ignition and sense electrode positioning.

 

 

Adjust as necessary.

 

No gas at main burners

1.

Check gas line for air. Purge as necessary.

 

 

 

NOTE: After purging gas line of air, wait at least

 

 

 

5 minutes for any gas to dissipate before attempt-

 

 

 

ing to light unit.

 

 

2.

Check gas valve.

Inadequate heating.

Dirty air ®lter

Clean or replace ®lter as necessary.

 

Gas input to furnace too low

Check gas pressure at manifold. Match with that on

 

 

unit nameplate.

 

Unit undersized for application

Replace with proper unit or add additional unit.

 

Restricted air¯ow

Clean or replace ®lter. Remove any restriction.

 

Blower speed too low

Use faster speed tap if available, or install alternate

 

 

motor.

 

Limit switch cycles main burners

Check rotation of blower, thermostat heat antic-

 

 

ipator settings, temperature rise of unit. Adjust as

 

 

necessary.

Poor ¯ame characteristics.

Incomplete combustion results in:

1.

Tighten all screws around burner compartment.

 

Aldehyde odors, carbon monox-

2.

Cracked heat exchanger. Replace.

 

ide, sooting ¯ame, ¯oating ¯ame

3. Unit over®red. Reduce input (change ori®ces or

 

 

 

adjust gas line or manifold pressure).

 

 

4.

Check burner alignment.

Ð49Ð

Image 49
Contents Safety Considerations ContentsGeneral Ð2Ð 588A018-042 Without Base Rail, Unit DimensionsÐ3Ð 588A018-042 With Optional Base Rail, Unit DimensionsÐ4Ð 588A048,060 Without Base Rail, Unit DimensionsÐ5Ð 588A048,060 With Optional Base Rail, Unit DimensionsÐ6Ð 589A024-036 Without Base Rail, Unit DimensionsÐ7Ð 589A024-036 With Optional Base Rail, Unit DimensionsÐ8Ð 589A042-060 Without Base Rail, Unit DimensionsÐ9Ð 589A042-060 With Optional Base Rail, Unit DimensionsII. Ð Provide Unit Support Receiving and Installation Check EquipmentIII. Ð Field Fabricate Ductwork IV. Ð Provide ClearancesPart Number Ð11ÐCurb Unit MAX WeightUnit VIII. Ð Install GAS Piping VII. Ð Install Flue HoodUnits With Optional Base Rail VI. Ð Connect Condensate DrainÐ14Ð Physical Data Ð Unit 588AÐ15Ð Physical Data Ð Unit 589AConguring Units for Down¯ow Vertical Discharge IX. Ð Install Duct ConnectionsÐ17Ð Maximum Gas Flow CapacityInternal Length of PIPE, FT² Iron Pipe Diameter Size High-Voltage Connections Install Electrical ConnectionsÐ19Ð Ð Electrical Data Ð Unit 588AÐ20Ð Ð Electrical Data Ð Unit 589ARLA LRA FLA High- and Control-Voltage Connections Special Procedures for 208-V OperationPRE-START-UP Transformer ProtectionAdjust Gas Input II. Start UP Heating Section and Make AdjustmentsSTART-UP Check for Refrigerant Leaks Check Heating ControlGAS Supply Pressure Manifold Natural GAS Propane Number Rated Gas Inputs at Indicated Manifold PressuresPressure OrificesCheck Burner Flame Heating Temperature Rise F InputÐ25Ð III. Start UP Cooling Section and Make Adjustments Ð27Ð 208/230-1-60 Wiring Diagram, Units 588A018-060Ð28Ð 208/230-3-60 Wiring Diagram, Units 588A030-060Ð29Ð 460-3-60 Wiring Diagram, Units 588A036-060Ð30Ð 208/230-1-60 Wiring Diagram, Units 589A024-042Ð31Ð 208/230-1-60 Wiring Diagram, Units 589A048,060Ð32Ð 208/230-3-60 Wiring Diagram, Units 589A036-042Ð33Ð 208/230-3-60 Wiring Diagram, Units 589A048,060Ð34Ð 460-3-60 Wiring Diagram, Units 589A036-048Indoor Air¯ow and Air¯ow Adjustments Checking and Adjusting Refrigerant ChargeSpeed Ð Superheat Charging Table, 588A024 Ð Superheat Charging Table, 588A018Ð36Ð Ð Superheat Charging Table, 588A036 Ð Superheat Charging Table, 588A030Ð Superheat Charging Table, 588A042 Ð37ÐÐ38Ð Ð Superheat Charging Table, 588A060Ð Superheat Charging Table, 589A030 Ð Superheat Charging Table, 589A024Ð Superheat Charging Table, 589A036 Ð39ÐÐ Superheat Charging Table, 589A048 Ð Superheat Charging Table, 589A042Ð Superheat Charging Table, 589A060 Ð40ÐÐ41Ð Required Suction-Tube Temperature FÐ42Ð Unit 589A Ð43ÐWet Coil Pressure Drop MaintenanceCooling Sequence of Operation Unit Size Airflow Pressure DropII. Unit TOP Removal AIR FilterIII. Evaporator Blower and Motor IV. Flue GAS PassagewaysCOMBUSTION-AIR Blower VI. Limit SwitchVII. Burner Ignition VIII. Main BurnersCondenser FAN XI. Electrical Controls and WiringXII. Refrigerant Circuit XIII. GAS InputSymptom Cause Remedy TroubleshootingPoor ¯ame characteristics IFM runs when itIntegrated control MotorLED OFF Service TrainingPage Temperatures START-UP ChecklistPreliminary Information III. START-UP Electrical
Related manuals
Manual 27 pages 52.72 Kb

589A, 588A specifications

The Bryant 588A is a high-efficiency gas furnace celebrated for its advanced technology and superior performance in residential heating. Known for its reliability and durable construction, this model is ideal for homeowners looking for warmth and comfort during colder months.

One of the standout features of the Bryant 588A is its remarkable AFUE (Annual Fuel Utilization Efficiency) rating, which can reach up to 96.5%. This high efficiency means that a significant portion of the fuel consumed is converted into usable heat, leading to lower energy bills and a reduced carbon footprint. The furnace utilizes a two-stage heating system, which improves comfort levels by providing more consistent temperatures and reducing the frequency of temperature swings in the home.

Another notable characteristic is the incorporation of a multi-speed blower motor. This innovation enhances airflow and optimizes energy use by adjusting the fan speed according to the heating needs of the home. The variable speed operation also helps to minimize noise levels, creating a quieter environment compared to traditional single-speed furnaces.

The Bryant 588A features an advanced control system that allows for better system management and can be integrated with smart home technologies. This allows homeowners to monitor and adjust their heating settings remotely, offering convenience and efficiency. Additionally, the furnace is compatible with Bryant’s Evolution System, which provides advanced diagnostic features and improved energy performance.

Durability is a key characteristic of the Bryant 588A, as it is constructed with a heavy-duty cabinet designed to withstand the rigors of daily use and harsh weather conditions. The unit also includes a corrosion-resistant heat exchanger, ensuring longevity and reliability.

Furthermore, the Bryant 588A operates quietly, thanks to its insulated cabinet and advanced design. This feature is especially appreciated by homeowners seeking a peaceful living environment free from disruptive noises typically associated with heating systems.

In summary, the Bryant 588A gas furnace combines high efficiency, innovative technology, and durable construction. Its effective heating capabilities paired with user-friendly features make it a smart investment for anyone looking to enhance their home heating system while enjoying lower energy costs and increased comfort.