Bryant 588A, 589A user manual Rated Gas Inputs at Indicated Manifold Pressures, Orifices

Page 24

Table 5 Ð Rated Gas Inputs at Indicated Manifold Pressures

 

 

GAS SUPPLY PRESSURE

MANIFOLD

NATURAL GAS

PROPANE*

 

NUMBER

 

(in. wg)

 

 

 

 

PRESSURE

 

 

 

 

UNIT 588A, 589A

OF

Natural

Propane

(in. wg)

Ori®ce

Heating

Ori®ce

Heating

 

ORIFICES

 

 

 

 

 

 

Drill

Input

Drill

Input

 

 

Min

Max

Min

Max

Natural

Propane

Size

(Btuh)²

Size

(Btuh)²

018040, 024040, 030040

1

4.0

13.0

4.0

13.0

3.5

3.1

32

40,000

41

40,000

024060, 030060, 036060, 042060

2

4.0

13.0

4.0

13.0

3.5

3.3

40

56,000

47

54,000

030080, 036080, 042080,

2

4.0

13.0

4.0

13.0

3.5

3.4

32

80,000

42

80,000

048080, 060080

 

 

 

 

 

 

 

 

 

 

 

036100, 042100, 048100, 060100

2

4.0

13.0

4.0

13.0

3.5

3.7

30

95,000

40

95,000

036120, 042120, 048120, 060120

3

4.0

13.0

4.0

13.0

3.5

3.5

32

120,000

42

115,000

048140, 060140

3

4.0

13.0

4.0

13.0

3.5

3.4

31

136,000

40

133,000

* When a unit is converted to propane, different size ori®ces must be used. See separate natural-to-propane conversion kit instructions.

²Based on altitudes from sea level to 2000 ft above sea level. For altitudes above 2000 ft: reduce input rating 4% for each additional 1000 ft above 2000 ft. In Canada, from 2000 ft above sea level to 4500 ft above sea level, derate the unit 10%.

NOTE: Unit size 018 is 588A only.

Measure Gas Flow (Natural Gas Units)

Minor adjustment to the gas ¯ow can be made by changing the manifold pressure. The manifold pressure must be main- tained between 3.4 and 3.6 in. wg. If larger adjustments are required, change main burner ori®ces following the recom- mendations of national and local codes.

NOTE: All other appliances that use the same meter must be turned off when gas ¯ow is measured at the meter.

Proceed as follows:

1.Turn off gas supply to unit.

2.Remove pipe plug on manifold (see Fig. 24), then con- nect manometer at this point. Turn on gas to unit.

3.Record number of seconds for gas meter test dial to make one revolution.

4.Divide number of seconds in Step 3 into 3600 (number of seconds in one hour).

5.Multiply result of Step 4 by the number of cu ft shown for one revolution of test dial to obtain cu ft of gas ¯ow per hour.

6.Multiply result of Step 5 by Btu heating value of gas to obtain total measured input in Btuh. Compare this value with heating input shown in Table 5. (Consult the local gas supplier if the heating value of gas is not known.)

EXAMPLE: Assume that the size of test dial is 1 cu ft, one revolution takes 30 seconds, and the heating value of the gas is 1050 Btu/ft3. Proceed as follows:

1.30 seconds to complete one revolution.

2.3600 ÷ 30 = 120.

3.120 x 1 = 120 ft3 of gas ¯ow/hr.

4.120 x 1050 = 126,000 Btuh input.

If the desired gas input is 120,000 Btuh, only a minor change in the manifold pressure is required.

Observe manifold pressure and proceed as follows to ad- just gas input:

1.Remove cover screw over regulator adjustment screw on gas valve.

2.Turn regulator adjustment screw clockwise to increase gas input, or turn regulator adjustment screw counter- clockwise to decrease input. Manifold pressure must be between 3.4 and 3.6 in. wg.

MANIFOLD

PIPE PLUG

Fig. 24 Ð Burner Assembly

WARNING: Unsafe operation of the unit may result if manifold pressure is outside this range. Personal in- jury or unit damage may result.

3.Replace cover screw cap on gas valve.

4.Turn off gas supply to unit. Remove manometer from pressure tap and replace pipe plug on gas valve. Turn on gas to unit and check for leaks.

Ð24Ð

Image 24
Contents Contents Safety ConsiderationsGeneral 588A018-042 Without Base Rail, Unit Dimensions Ð2Ð588A018-042 With Optional Base Rail, Unit Dimensions Ð3Ð588A048,060 Without Base Rail, Unit Dimensions Ð4Ð588A048,060 With Optional Base Rail, Unit Dimensions Ð5Ð589A024-036 Without Base Rail, Unit Dimensions Ð6Ð589A024-036 With Optional Base Rail, Unit Dimensions Ð7Ð589A042-060 Without Base Rail, Unit Dimensions Ð8Ð589A042-060 With Optional Base Rail, Unit Dimensions Ð9ÐReceiving and Installation Check Equipment II. Ð Provide Unit SupportIII. Ð Field Fabricate Ductwork IV. Ð Provide ClearancesÐ11Ð Part NumberCurb Weight Unit MAXUnit VII. Ð Install Flue Hood VIII. Ð Install GAS PipingUnits With Optional Base Rail VI. Ð Connect Condensate DrainPhysical Data Ð Unit 588A Ð14ÐPhysical Data Ð Unit 589A Ð15ÐIX. Ð Install Duct Connections Conguring Units for Down¯ow Vertical DischargeMaximum Gas Flow Capacity Ð17ÐInternal Length of PIPE, FT² Iron Pipe Diameter Size Install Electrical Connections High-Voltage ConnectionsÐ Electrical Data Ð Unit 588A Ð19ÐÐ Electrical Data Ð Unit 589A Ð20ÐRLA LRA FLA Special Procedures for 208-V Operation High- and Control-Voltage ConnectionsTransformer Protection PRE-START-UPII. Start UP Heating Section and Make Adjustments Adjust Gas InputSTART-UP Check for Refrigerant Leaks Check Heating ControlRated Gas Inputs at Indicated Manifold Pressures GAS Supply Pressure Manifold Natural GAS Propane NumberPressure OrificesHeating Temperature Rise F Input Check Burner FlameÐ25Ð III. Start UP Cooling Section and Make Adjustments 208/230-1-60 Wiring Diagram, Units 588A018-060 Ð27Ð208/230-3-60 Wiring Diagram, Units 588A030-060 Ð28Ð460-3-60 Wiring Diagram, Units 588A036-060 Ð29Ð208/230-1-60 Wiring Diagram, Units 589A024-042 Ð30Ð208/230-1-60 Wiring Diagram, Units 589A048,060 Ð31Ð208/230-3-60 Wiring Diagram, Units 589A036-042 Ð32Ð208/230-3-60 Wiring Diagram, Units 589A048,060 Ð33Ð460-3-60 Wiring Diagram, Units 589A036-048 Ð34ÐChecking and Adjusting Refrigerant Charge Indoor Air¯ow and Air¯ow AdjustmentsSpeed Ð Superheat Charging Table, 588A018 Ð Superheat Charging Table, 588A024Ð36Ð Ð Superheat Charging Table, 588A030 Ð Superheat Charging Table, 588A036Ð Superheat Charging Table, 588A042 Ð37ÐÐ Superheat Charging Table, 588A060 Ð38ÐÐ Superheat Charging Table, 589A024 Ð Superheat Charging Table, 589A030Ð Superheat Charging Table, 589A036 Ð39ÐÐ Superheat Charging Table, 589A042 Ð Superheat Charging Table, 589A048Ð Superheat Charging Table, 589A060 Ð40ÐRequired Suction-Tube Temperature F Ð41ÐÐ42Ð Ð43Ð Unit 589AMaintenance Wet Coil Pressure DropCooling Sequence of Operation Unit Size Airflow Pressure DropAIR Filter II. Unit TOP RemovalIII. Evaporator Blower and Motor IV. Flue GAS PassagewaysVI. Limit Switch COMBUSTION-AIR BlowerVII. Burner Ignition VIII. Main BurnersXI. Electrical Controls and Wiring Condenser FANXII. Refrigerant Circuit XIII. GAS InputTroubleshooting Symptom Cause RemedyIFM runs when it Poor ¯ame characteristicsIntegrated control MotorService Training LED OFFPage START-UP Checklist TemperaturesPreliminary Information III. START-UP Electrical
Related manuals
Manual 27 pages 52.72 Kb

589A, 588A specifications

The Bryant 588A is a high-efficiency gas furnace celebrated for its advanced technology and superior performance in residential heating. Known for its reliability and durable construction, this model is ideal for homeowners looking for warmth and comfort during colder months.

One of the standout features of the Bryant 588A is its remarkable AFUE (Annual Fuel Utilization Efficiency) rating, which can reach up to 96.5%. This high efficiency means that a significant portion of the fuel consumed is converted into usable heat, leading to lower energy bills and a reduced carbon footprint. The furnace utilizes a two-stage heating system, which improves comfort levels by providing more consistent temperatures and reducing the frequency of temperature swings in the home.

Another notable characteristic is the incorporation of a multi-speed blower motor. This innovation enhances airflow and optimizes energy use by adjusting the fan speed according to the heating needs of the home. The variable speed operation also helps to minimize noise levels, creating a quieter environment compared to traditional single-speed furnaces.

The Bryant 588A features an advanced control system that allows for better system management and can be integrated with smart home technologies. This allows homeowners to monitor and adjust their heating settings remotely, offering convenience and efficiency. Additionally, the furnace is compatible with Bryant’s Evolution System, which provides advanced diagnostic features and improved energy performance.

Durability is a key characteristic of the Bryant 588A, as it is constructed with a heavy-duty cabinet designed to withstand the rigors of daily use and harsh weather conditions. The unit also includes a corrosion-resistant heat exchanger, ensuring longevity and reliability.

Furthermore, the Bryant 588A operates quietly, thanks to its insulated cabinet and advanced design. This feature is especially appreciated by homeowners seeking a peaceful living environment free from disruptive noises typically associated with heating systems.

In summary, the Bryant 588A gas furnace combines high efficiency, innovative technology, and durable construction. Its effective heating capabilities paired with user-friendly features make it a smart investment for anyone looking to enhance their home heating system while enjoying lower energy costs and increased comfort.