Bryant 588A, 589A user manual Wet Coil Pressure Drop, Cooling Sequence of Operation, Maintenance

Page 44

Table 17 Ð Wet Coil Pressure Drop

UNIT SIZE

AIRFLOW

PRESSURE DROP

(cfm)

(in. wg)

 

 

600

0.069

018*

700

0.082

800

0.102

 

 

900

0.116

 

600

0.039

024

700

0.058

800

0.075

 

 

900

0.088

 

900

0.088

030

1000

0.095

 

1200

0.123

 

1000

0.068

036

1200

0.088

1400

0.108

 

 

1600

0.123

 

1000

0.048

042

1200

0.069

1400

0.088

 

 

1600

0.102

 

1400

0.068

048

1600

0.075

 

1800

0.088

 

1700

0.082

060

1900

0.095

2100

0.108

 

 

2300

0.123

 

 

 

*Unit 588A only.

D. Cooling Sequence of Operation

With the room thermostat SYSTEM switch in the COOL po- sition and the FAN switch in the AUTO. position, the cooling sequence of operation is as follows:

When the room temperature rises to a point that is slightly above the cooling control setting of the thermostat, the ther- mostat completes the circuit between thermostat terminal R to terminals Y and G. These completed circuits through the thermostat connect contactor coil (C) (through unit wire Y) and blower relay coil (BR) (through unit wire G) across the 24-v secondary of transformer (TRAN).

NOTE: The blower relay coil (BR) is used on standard non- ICM units, ICM units use evaporator (indoor) fan on (IFO) connection.

The normally-open contacts of energized contactor (C) close and complete the circuit through compressor motor (COMP) to condenser (outdoor) fan motor (OFM). Both motors start instantly.

On standard non-ICM units, the set of normally-open con- tacts of energized relay BR close and complete the circuit through evaporator blower (indoor) fan motor (IFM). On ICM units, the IFO completes the circuit through evaporator blower IFM. The blower motor starts instantly.

NOTE: Once the compressor has started and then has stopped, it should not be started again until 5 minutes have elapsed.

The cooling cycle remains ``on'' until the room temperature drops to point that is slightly below the cooling control set- ting of the room thermostat. At this point, the thermostat ``breaks'' the circuit between thermostat terminal R to termi- nals Y and G. These open circuits deenergize contactor coil C and relay coil BR. The condenser and compressor motors stop. After a 30-second delay, the blower motor stops. The unit is in a ``standby'' condition, waiting for the next ``call for cool- ing'' from the room thermostat.

MAINTENANCE

To ensure continuing high performance, and to minimize the possibility of premature equipment failure, periodic mainte- nance must be performed on this equipment. This combina- tion heating/cooling unit should be inspected at least once each year by a quali®ed service person. To troubleshoot heating or cooling of units, refer to tables at the back of the book.

NOTE TO EQUIPMENT OWNER: Consult your local dealer about the availability of a maintenance contract.

WARNING: The ability to properly perform mainte- nance on this equipment requires certain expertise, me- chanical skills, tools, and equipment. If you do not pos- sess these, do not attempt to perform any maintenance on this equipment other than those procedures recom- mended in the User's Manual. FAILURE TO HEED THIS WARNING COULD RESULT IN SERIOUS PERSONAL INJURY AND POSSIBLE DAMAGE TO THIS EQUIPMENT.

WARNING: Failure to follow these warnings could re- sult in serious personal injury:

1.Turn off gas supply, then turn off electrical power to the unit before performing any maintenance or serv- ice on the unit.

2.Use extreme caution when removing panels and parts. As with any mechanical equipment, personal injury can result from sharp edges, etc.

3.Never place anything combustible either on, or in con- tact with, the unit.

4.Should overheating occur, or the gas supply fail to shut off, shut off the external main manual gas valve to the unit, then shut off the electrical supply.

CAUTION: Errors made when reconnecting wires may cause improper and dangerous operation. Label all wires prior to disconnection when servicing.

The minimum maintenance requirements for this equipment are as follows:

1.Inspect air ®lter(s) each month. Clean or replace when necessary.

2.Inspect indoor coil, drain pan, and condensate drain each cooling season for cleanliness. Clean when necessary.

3.Inspect blower motor and wheel for cleanliness and check lubrication each heating and cooling season. Clean and lubricate (if required) when necessary. For ®rst heating season, inspect blower wheel bimonthly to determine proper cleaning frequency.

4.Check electrical connections for tightness and controls for proper operation each heating and cooling season. Service when necessary.

5.Check and inspect heating section before each heating season. Clean and adjust when necessary.

6.Check ¯ue hood screen and remove any obstructions if necessary.

7.Check vent screen and clean if necessary.

Ð44Ð

Image 44
Contents General ContentsSafety Considerations 588A018-042 Without Base Rail, Unit Dimensions Ð2Ð588A018-042 With Optional Base Rail, Unit Dimensions Ð3Ð588A048,060 Without Base Rail, Unit Dimensions Ð4Ð588A048,060 With Optional Base Rail, Unit Dimensions Ð5Ð589A024-036 Without Base Rail, Unit Dimensions Ð6Ð589A024-036 With Optional Base Rail, Unit Dimensions Ð7Ð589A042-060 Without Base Rail, Unit Dimensions Ð8Ð589A042-060 With Optional Base Rail, Unit Dimensions Ð9ÐReceiving and Installation Check Equipment II. Ð Provide Unit SupportIII. Ð Field Fabricate Ductwork IV. Ð Provide ClearancesCurb Ð11ÐPart Number Unit WeightUnit MAX VII. Ð Install Flue Hood VIII. Ð Install GAS PipingUnits With Optional Base Rail VI. Ð Connect Condensate DrainPhysical Data Ð Unit 588A Ð14ÐPhysical Data Ð Unit 589A Ð15ÐIX. Ð Install Duct Connections Conguring Units for Down¯ow Vertical DischargeInternal Length of PIPE, FT² Iron Pipe Diameter Size Maximum Gas Flow CapacityÐ17Ð Install Electrical Connections High-Voltage ConnectionsÐ Electrical Data Ð Unit 588A Ð19ÐRLA LRA FLA Ð Electrical Data Ð Unit 589AÐ20Ð Special Procedures for 208-V Operation High- and Control-Voltage ConnectionsTransformer Protection PRE-START-UPII. Start UP Heating Section and Make Adjustments Adjust Gas InputSTART-UP Check for Refrigerant Leaks Check Heating ControlRated Gas Inputs at Indicated Manifold Pressures GAS Supply Pressure Manifold Natural GAS Propane NumberPressure OrificesÐ25Ð Heating Temperature Rise F InputCheck Burner Flame III. Start UP Cooling Section and Make Adjustments 208/230-1-60 Wiring Diagram, Units 588A018-060 Ð27Ð208/230-3-60 Wiring Diagram, Units 588A030-060 Ð28Ð460-3-60 Wiring Diagram, Units 588A036-060 Ð29Ð208/230-1-60 Wiring Diagram, Units 589A024-042 Ð30Ð208/230-1-60 Wiring Diagram, Units 589A048,060 Ð31Ð208/230-3-60 Wiring Diagram, Units 589A036-042 Ð32Ð208/230-3-60 Wiring Diagram, Units 589A048,060 Ð33Ð460-3-60 Wiring Diagram, Units 589A036-048 Ð34ÐSpeed Checking and Adjusting Refrigerant ChargeIndoor Air¯ow and Air¯ow Adjustments Ð36Ð Ð Superheat Charging Table, 588A018Ð Superheat Charging Table, 588A024 Ð Superheat Charging Table, 588A030 Ð Superheat Charging Table, 588A036Ð Superheat Charging Table, 588A042 Ð37ÐÐ Superheat Charging Table, 588A060 Ð38ÐÐ Superheat Charging Table, 589A024 Ð Superheat Charging Table, 589A030Ð Superheat Charging Table, 589A036 Ð39ÐÐ Superheat Charging Table, 589A042 Ð Superheat Charging Table, 589A048Ð Superheat Charging Table, 589A060 Ð40ÐRequired Suction-Tube Temperature F Ð41ÐÐ42Ð Ð43Ð Unit 589AMaintenance Wet Coil Pressure DropCooling Sequence of Operation Unit Size Airflow Pressure DropAIR Filter II. Unit TOP RemovalIII. Evaporator Blower and Motor IV. Flue GAS PassagewaysVI. Limit Switch COMBUSTION-AIR BlowerVII. Burner Ignition VIII. Main BurnersXI. Electrical Controls and Wiring Condenser FANXII. Refrigerant Circuit XIII. GAS InputTroubleshooting Symptom Cause RemedyIFM runs when it Poor ¯ame characteristicsIntegrated control MotorService Training LED OFFPage START-UP Checklist TemperaturesPreliminary Information III. START-UP Electrical
Related manuals
Manual 27 pages 52.72 Kb

589A, 588A specifications

The Bryant 588A is a high-efficiency gas furnace celebrated for its advanced technology and superior performance in residential heating. Known for its reliability and durable construction, this model is ideal for homeowners looking for warmth and comfort during colder months.

One of the standout features of the Bryant 588A is its remarkable AFUE (Annual Fuel Utilization Efficiency) rating, which can reach up to 96.5%. This high efficiency means that a significant portion of the fuel consumed is converted into usable heat, leading to lower energy bills and a reduced carbon footprint. The furnace utilizes a two-stage heating system, which improves comfort levels by providing more consistent temperatures and reducing the frequency of temperature swings in the home.

Another notable characteristic is the incorporation of a multi-speed blower motor. This innovation enhances airflow and optimizes energy use by adjusting the fan speed according to the heating needs of the home. The variable speed operation also helps to minimize noise levels, creating a quieter environment compared to traditional single-speed furnaces.

The Bryant 588A features an advanced control system that allows for better system management and can be integrated with smart home technologies. This allows homeowners to monitor and adjust their heating settings remotely, offering convenience and efficiency. Additionally, the furnace is compatible with Bryant’s Evolution System, which provides advanced diagnostic features and improved energy performance.

Durability is a key characteristic of the Bryant 588A, as it is constructed with a heavy-duty cabinet designed to withstand the rigors of daily use and harsh weather conditions. The unit also includes a corrosion-resistant heat exchanger, ensuring longevity and reliability.

Furthermore, the Bryant 588A operates quietly, thanks to its insulated cabinet and advanced design. This feature is especially appreciated by homeowners seeking a peaceful living environment free from disruptive noises typically associated with heating systems.

In summary, the Bryant 588A gas furnace combines high efficiency, innovative technology, and durable construction. Its effective heating capabilities paired with user-friendly features make it a smart investment for anyone looking to enhance their home heating system while enjoying lower energy costs and increased comfort.